30kW Cold Plate Liquid Cooling Rack System | KITOZER

Table of Contents

30kW Rated Cooling Capacity Cold Plate Liquid Cooling Rack System — Technical Design Proposal

Project No.: LAIN-YL-2026-001

Design Firm: Guangzhou Lain Intelligent System Development Co., Ltd.

Brand: KITOZER

Version: V1.0

—

Table of Contents

  1. Company Profile
  2. Project Overview
  3. User Requirements Analysis
  4. Overall System Design Description
  5. Detailed Technical Specifications of System Products
  6. Project Configuration & Quotation List
  7. Core Solution Advantages
  8. Technical FAQ
  9. Construction Schedule Plan
  10. Construction Organization Plan
  11. After-Sales Service System
  12. Operation & Maintenance Training Program
  13. Representative Project Case Studies
  14. SEO Keyword System & Optimization Tags
  15. Website Backend Publishing Configuration
  16. Contact Information

—

Chapter 1 — Company Profile

Founded in 2002 and headquartered in Panyu District, Guangzhou, Guangzhou Lain Intelligent System Development Co., Ltd. is a national high-tech enterprise specializing in the R&D, manufacturing, and sales of data center infrastructure, intelligent computer rooms, liquid cooling thermal management systems, and electromagnetic shielding equipment. With over two decades of deep industry expertise, the company has built its proprietary core brand KITOZER, with a product portfolio spanning micro-module cold-aisle containment, integrated cabinets, outdoor enclosures, shielded rooms, shielded racks, containerized data centers, and liquid-cooled data center systems — covering the full spectrum of data center equipment and engineering services.

As a professional manufacturer and supplier, KITOZER delivers custom solutions and turnkey projects for government, financial, telecommunications, internet, education, healthcare, and industrial manufacturing sectors worldwide — from solution design, product customization, and manufacturing through to engineering implementation and lifecycle O&M support — all under one roof as a one-stop integrated solution provider.

The company operates a modern production base with a dedicated R&D team, holding core competencies in high-efficiency heat dissipation, electromagnetic shielding, intelligent environmental monitoring, and green energy conservation. We hold dozens of product patents and software copyrights and are certified under ISO9001 (Quality Management System), ISO14001 (Environmental Management System), and OHSAS18001 (Occupational Health & Safety Management System). Leveraging over 20 years of industry experience and technical accumulation, we tailor exclusive solutions to individual client requirements, providing multiple differentiated design proposals free of charge — precisely matching site conditions and business needs.

Guided by the product philosophy of “Efficient, Green, Innovative, Safe, and Convenient,” the company drives growth through technological innovation, continuously launching green data center products and solutions suited to next-generation computing demands. In the liquid cooling data center domain, KITOZER has independently developed both cold plate and immersion liquid cooling technologies, built on years of HVAC and structural design experience, capable of meeting ultra-high-density cooling demands from 10kW to over 100kW per rack — enabling data centers to achieve low PUE, high reliability, and easy maintenance in their green upgrade journey.

The company has established a full-process quality control system — from incoming raw materials to finished product dispatch, every stage is inspected. Key components are sourced from tier-one industry brands, with third-party testing agencies providing end-to-end quality assurance, ensuring every product meets national and industry standards. A 7×24 hour professional technical service system responds rapidly to customer issues, with a dedicated project manager assigned to every project for full-cycle support — from pre-sales solution design through post-sales maintenance — earning widespread recognition from enterprises and clients at home and abroad, including the USA, Europe, Southeast Asia, the Middle East, and Africa.

—

Chapter 2 — Project Overview

2.1 Project Background

With the rapid advancement of the digital economy, the proliferation of artificial intelligence, big data, cloud computing, and high-performance computing has driven continuous increases in data center server compute density. Per-rack power density has climbed rapidly from a traditional 3–5kW to 10kW, 20kW, and beyond 30kW. Conventional air-cooling is increasingly challenged by insufficient heat dissipation capacity, persistently high energy consumption, noise pollution, and poor space utilization — making it difficult to meet the cooling demands of ultra-high-density computing.

Liquid cooling technology — with its superior heat transfer efficiency, lower energy consumption, and better noise control — has become the core cooling solution for next-generation high-density data centers. Among the available approaches, cold plate liquid cooling is compatible with standard server architectures, offers low retrofit complexity and high reliability, and is currently one of the mainstream technical routes for high-density heat dissipation.

Against this backdrop, the present project addresses the client’s high-density computing room construction needs by adopting a mature and reliable cold plate liquid cooling architecture. The system comprises 205 cold plate liquid cooling cabinets with 30kW rated heat dissipation capacity, complemented by a computer-room-side cold source system, primary piping network, power supply & distribution system, and intelligent monitoring system — delivering a safe, reliable, energy-efficient, and intelligently operated cold plate liquid cooling data center solution that supports the client’s business-driven compute infrastructure requirements.

2.2 Project Overview

Item Description
— —
Project Name 30kW Cold Plate Liquid Cooling Cabinet System Construction Project
Construction Entity Guangzhou Lain Intelligent System Development Co., Ltd.
Technical Route Rack-level CDU secondary-side isolated cold plate liquid cooling system
Cabinet Quantity 205 units of 42U standard cold plate liquid cooling cabinets
Rated Cooling Capacity per Cabinet 30kW (peak 35kW)
Total Cooling Load 6,150kW
Cold Source Configuration Closed evaporative cooling tower + high-temperature screw chiller for supplemental cooling
System Architecture Primary/secondary side fully isolated, N+1 redundant design
Design Targets Annual comprehensive PUE ≤ 1.2; system availability ≥ 99.99%; meets Class A data center reliability requirements

2.3 Project Construction Objectives

Heat Dissipation Capacity Objective — Each cabinet achieves a rated cooling capacity of 30kW with a peak capacity of 35kW. Core heat-generating components such as server CPUs maintain stable operating temperatures within design limits, satisfying full-load operation requirements for high-density computing equipment.

Energy Efficiency Objective — Maximize utilization of natural cold sources, extend free-cooling hours, and adopt variable-frequency control to precisely match cooling output with IT load. Annual comprehensive PUE ≤ 1.2, significantly reducing cooling system energy consumption and operational costs.

Reliability Objective — Core equipment adopts N+1 redundancy; piping and connectors feature multi-layer sealing designs; comprehensive leak detection and safety protection systems are deployed. System availability ≥ 99.99%, meeting Class A data center reliability requirements.

Intelligence Objective — Full-system real-time operational status monitoring, automatic fault alarm, intelligent device linkage control, and support for integration with the client’s existing DCIM/BMS monitoring platform for unified O&M management — reducing operational complexity and labor costs.

Scalability Objective — Modular system architecture with expansion margin reserved across cold source, piping, power distribution, and monitoring subsystems. Supports future increases in cabinet count and per-cabinet power density, accommodating the client’s long-term business growth.

Safety & Compliance Objective — System design strictly adheres to national safety specifications, with multiple protection measures across electrical safety, pressure safety, leak prevention, and fire safety. All components comply with applicable safety certification requirements.

—

Chapter 3 — User Requirements Analysis

3.1 Core Heat Dissipation Requirements

  • Per-cabinet rated cooling capacity no less than 30kW, satisfying full-load heat dissipation for dual-socket high-TDP CPU servers, with ≥15% design margin to accommodate load fluctuations and extreme operating conditions.
  • Secondary-side supply liquid temperature stably controlled within 35°C; return liquid temperature not exceeding 45°C, keeping server chip operating temperatures in the optimal range for enhanced stability and extended equipment service life.
  • Working fluid: 25% concentration ethylene glycol-water solution with dedicated corrosion inhibitors and scale inhibitors — safe, environmentally friendly, non-corrosive to piping, heat exchangers, cold plates, and all system wetted materials.
  • Fully isolated primary/secondary architecture: primary-side cooling water never contacts server cold plates, preventing contamination and fouling from the primary side from affecting the secondary side — protecting critical IT equipment.

3.2 Cabinet Structural Requirements

  • Standard 42U cabinet, compliant with 19-inch standard mounting specifications, compatible with existing standard rack-mount servers without major structural modification.
  • Static load rating ≥ 1,500kg, satisfying the load requirements of high-density servers and liquid cooling components; structural strength per national standards.
  • Front and rear doors adopt high open-area perforated mesh design to support limited auxiliary air-cooling requirements while facilitating equipment maintenance; three-point locking anti-theft door latches ensure equipment security.
  • Cabinet top and base pre-drilled with ample liquid piping and cable entry openings, complete with sealing assemblies and fire-stop components — meeting computer room fire protection, dustproof, and rodent-proof requirements.
  • Fully implemented grounding system with dedicated grounding copper busbar, satisfying computer room equipotential bonding requirements for electrical safety.
  • Internal space reserved for liquid cooling piping, CDU equipment, and monitoring components with designated mounting points — rational layout enabling convenient installation and maintenance.

3.3 Power Supply & Distribution Requirements

  • Each cabinet equipped with dual-circuit intelligent PDU for redundant power supply, satisfying dual-power server reliability requirements — single-circuit failure does not affect equipment operation.
  • PDU supports full electrical parameter monitoring (current, voltage, power, energy, power factor), remote on/off control, overload protection, and comprehensive alarm functions.
  • Dedicated grounding busbar inside each cabinet; all equipment reliably grounded with grounding resistance per computer room specifications.
  • Cable entry via sealed cable glands with protection rating ≥ IP65, meeting dust and moisture resistance requirements.
  • Power distribution system reserves expansion capacity for future equipment additions and power upgrades.

3.4 Monitoring & Safety Requirements

  • Each cabinet configured with an independent locating leak detection system with leak position accuracy ≤ 10cm; immediate audible/visual alarm upon leak occurrence with linkage to close relevant valves.
  • Temperature, pressure, and flow sensors at critical system nodes for real-time monitoring of supply/return liquid temperature, pressure, and flow; automatic alarm on abnormal conditions.
  • Local touchscreen display per cabinet for on-site viewing of operating parameters, fault information, and operation control; supports remote data upload to the DCIM/BMS platform.
  • Multi-level alarm mechanism supporting audible/visual alarm, SMS alert, and system pop-up notification; all fault information traceable and queryable.
  • Centralized automatic control system at the cold station, enabling fully automatic linkage control of cold source equipment, pumps, and valves — unattended operation with automatic cooling output regulation based on load.

3.5 Reliability & Maintenance Requirements

  • Critical circulation pumps and cold source equipment adopt N+1 redundancy; standby equipment automatically activates on primary unit failure without system disruption.
  • All piping connectors use reliable sealed designs; server-side connections use self-sealing quick couplings enabling hot-swap maintenance without coolant leakage.
  • System features automatic venting, automatic pressure stabilization, and automatic water make-up — reducing manual O&M workload and simplifying operational procedures.
  • Modular equipment design allows online maintenance and replacement of key components without system shutdown, ensuring business continuity.
  • Filters designed for online replacement — blocked filter elements can be swapped without system downtime.
  • System designed for easy routine inspection and maintenance; high standardization of consumable parts, ample spare parts supply, and low maintenance cost.

3.6 Construction & Delivery Requirements

  • Overall project duration ≤ 90 days, covering equipment manufacturing, on-site installation, system commissioning, trial operation, and acceptance/delivery.
  • Construction strictly follows national and industry specifications, ensuring construction quality and safety with civilized, safe work practices.
  • Full technical documentation delivered upon handover: operation manuals, maintenance manuals, as-built drawings, and related deliverables.
  • Professional operator and maintenance training provided to enable the client’s O&M team to independently operate and perform routine maintenance.
  • Comprehensive after-sales service and warranty: ≥ 2 years full-system warranty; ≥ 3 years warranty on core components.

—

Chapter 4 — Overall System Design Description

4.1 Design Basis

This proposal strictly complies with the following national, industry standards and specifications:

Standard No. Standard Name
— —
GB 50174-2017 Code for Design of Data Centers
GB 50462-2016 Code for Construction and Acceptance of Data Center Infrastructure
GB/T 2887-2011 General Specification for Computer Field
T/CCSA 317-2021 Technical Specification for Liquid-Cooled Data Centers
YD/T 3984-2021 Technical Requirements for Data Center Liquid-Cooled Server Systems
GB/T 39661-2020 Technical Requirements and Test Methods for Cold Plate Liquid Cooling of Servers
GB 50316-2000 (2008 Edition) Code for Design of Industrial Metallic Piping
GB 50054-2011 Code for Design of Low-Voltage Electrical Installations
GB 50057-2010 Code for Design Protection of Structures Against Lightning
GB 40879-2021 Minimum Allowable Values of Energy Efficiency and Energy Efficiency Grades for Data Centers
— Client-provided computer room site conditions and business requirements documentation

4.2 Design Principles

4.2.1 Reliability First

System reliability is the highest priority. All core equipment and critical paths adopt redundant designs with mature, proven technical routes and high-quality components — ensuring long-term stable operation from architecture, component, and control perspectives, meeting Class A data center availability requirements. All critical components undergo rigorous reliability testing to guarantee stable performance under all operating conditions.

4.2.2 High Efficiency & Energy Conservation

High-efficiency liquid cooling technology substantially improves heat exchange efficiency, maximizes natural cold source utilization, extends free-cooling hours, and reduces mechanical refrigeration runtime. Variable-frequency control technology achieves precise matching between cooling output and IT load, maximizing system energy efficiency and reducing annual operating costs — supporting low-carbon, green data center operation.

4.2.3 Safety & Compliance

System design strictly adheres to national safety specifications with multiple protection layers across electrical safety, pressure safety, leak prevention, and fire safety. All electrical components meet CCC certification requirements; pressure components comply with pressure vessel codes; leak detection provides full coverage — safeguarding personnel and equipment alike.

4.2.4 Intelligent Operation & Maintenance

Full-digital monitoring architecture delivers comprehensive system awareness, intelligent analysis, and automated control. Local and remote two-tier monitoring systems support automatic fault diagnosis and alarming, reducing manual O&M burden while improving fault response speed and resolution efficiency — lowering operational complexity and labor costs.

4.2.5 Scalability

Modular system architecture with expansion margins reserved across cold source, piping, distribution, and monitoring subsystems. Standardized interfaces and protocols ensure seamless integration of new equipment into the existing system, accommodating long-term business growth.

4.2.6 Economic Applicability

System configuration is optimized to control construction cost while satisfying performance and reliability requirements. High-efficiency, energy-saving design reduces long-term operating costs, balancing initial investment against total lifecycle cost for optimal whole-life economics.

4.3 Overall System Architecture

The 30kW cold plate liquid cooling cabinet system adopts a two-stage isolated liquid cooling architecture structured in five functional layers from cold source to terminal heat dissipation. The architecture is clear, with independent layer functionality for simplified O&M management and fault isolation.

4.3.1 Cold Source Layer

Comprising closed evaporative cooling towers, high-temperature screw chillers, primary-side circulation pump sets, and header/collector assemblies — responsible for producing primary-side cooling water as the system’s cold source backbone. Supports evaporative cooling mode, dry cooling mode, and mechanical refrigeration supplemental mode, automatically switching based on outdoor ambient temperature to maximize natural cold source utilization and minimize energy consumption.

4.3.2 Main Piping Layer

Comprising the computer room’s main supply/return piping, row-level piping, valve assemblies, and insulation — responsible for delivering primary-side cooling water from the cold station to each cabinet’s CDU and returning heated water to the cold source for heat rejection. The main piping uses a loop design, ensuring uniform supply pressure and temperature across all cabinets.

4.3.3 Cabinet Heat Exchange Distribution Layer

Comprising the rack-level CDU (Coolant Distribution Unit) and manifold assemblies installed in each cabinet, achieving primary/secondary coolant isolation and heat exchange. The CDU integrates a plate heat exchanger, circulation pump, filter, expansion tank, sensors, and control unit — managing secondary-side coolant circulation, filtration, pressure stabilization, and flow regulation to deliver stable, clean coolant to server cold plates.

4.3.4 Terminal Heat Dissipation Layer

Comprising server CPU cold plates, thermal interface material (TIM), branch flex hoses, and quick couplings — in direct contact with server heat-generating components. Heat is carried away by coolant flow for precision cooling. Cold plates utilize micro-channel structures delivering high heat transfer efficiency and low flow resistance, compatible with mainstream server CPU specifications.

4.3.5 Monitoring & Management Layer

Comprising field sensors, cabinet-local control units, cold station PLC control systems, and DCIM integration platform — enabling full-system data acquisition, analysis, control, and alarm. Supports both local and remote O&M management, and can interface with the client’s existing BMS/DCIM platform for unified management.

4.4 Design Operating Conditions

4.4.1 Outdoor Design Conditions

Parameter Value
— —
Summer outdoor design dry-bulb temperature 35°C
Summer outdoor design wet-bulb temperature 28°C
Winter outdoor design dry-bulb temperature 5°C
Annual average temperature 22°C

4.4.2 System Design Conditions

Parameter Value
— —
Primary-side supply liquid temperature 30°C
Primary-side return liquid temperature 38°C
Primary-side supply/return temperature differential 8°C
Secondary-side supply liquid temperature 35°C
Secondary-side return liquid temperature 45°C
Secondary-side supply/return temperature differential 10°C
System design working pressure 1.0MPa
System test pressure 1.5MPa
Rated cooling capacity per cabinet 30kW
Peak cooling capacity per cabinet 35kW

4.5 Coolant Selection

Both primary and secondary sides of this system use 25% concentration ethylene glycol-water solution as the working fluid, offering the following characteristics:

Property Description
— —
Anti-freeze Performance Freezing point approximately −15°C, enabling safe system operation in low-temperature winter environments, preventing pipe and equipment freeze damage.
Corrosion Protection Dedicated corrosion inhibitors protect carbon steel, stainless steel, copper, aluminum, and other system wetted materials — extending system service life.
Scale Inhibition Dedicated scale inhibitors suppress calcium/magnesium scaling, maintaining stable heat exchange efficiency across piping and heat exchangers.
Safety & Environmental Ethylene glycol-water solution is chemically stable, non-toxic, harmless, and environmentally friendly; easy to clean up in the event of leakage.
Heat Transfer Performance Excellent thermal conductivity and specific heat capacity, delivering high-efficiency heat exchange.

—

Chapter 5 — Detailed Technical Specifications of System Products

5.1 Cabinet Structural System

5.1.1 42U Cold Plate Liquid Cooling Dedicated Cabinet

This cabinet is part of the KITOZER series, purpose-designed for cold plate liquid cooling scenarios. It features a high-strength cold-rolled steel frame integrating liquid cooling piping interfaces, power distribution interfaces, and monitoring components — compatible with standard 19-inch server mounting while balancing structural strength, thermal adaptability, and serviceability.

Structural & Dimensional Parameters

Parameter Specification
— —
Cabinet Height 2000mm (42U standard height)
Cabinet Width 600mm (standard 19-inch mounting width)
Cabinet Depth 1200mm (deep-cabinet design for liquid piping and server depth)
Usable Internal U-positions 42U, clearly marked, accuracy ±0.1U
Square-hole rail center distance 465mm (standard 19-inch mounting)
Front/Rear door opening angle ≥ 130°
Side door dimensions Full cabinet height, tool-free detachable design
Mounting depth adjustment Front/rear rails adjustable travel ≥ 100mm

Material & Finish Parameters

Parameter Specification
— —
Main frame material High-quality cold-rolled steel sheet, thickness ≥ 2.0mm
Door panel material High-quality cold-rolled steel sheet, thickness ≥ 1.5mm
Square-hole rail material High-strength galvanized steel, thickness ≥ 2.0mm, No. 12 steel standard
Surface finish Electrostatic powder coating, epoxy polyester powder
Coating thickness 60–80μm
Surface hardness ≥ 2H
Adhesion rating Class 0 (per GB/T 9286-1998)
Salt spray resistance ≥ 48 hours without corrosion (per GB/T 10125-2012)
Standard color RAL7035 light gray (custom colors available)
Mesh opening rate ≥ 65% front/rear doors — balance of ventilation and protection

Load-Bearing Parameters

Parameter Specification
— —
Static load capacity ≥ 1,500kg (uniformly distributed)
Dynamic load capacity ≥ 1,000kg
Cabinet top load capacity ≥ 200kg
Base load capacity ≥ 1,800kg
Per-rail (column) load capacity ≥ 500kg
Leveling foot adjustment range ±25mm

Structural Configuration

Component Description
— —
Front door Single-leaf perforated mesh door, three-point anti-theft lock
Rear door Double-leaf perforated mesh door, three-point anti-theft lock, dual-side maintenance access
Side doors Closed solid side panels (both sides), quick-release latches, tool-free removal
Top panel One-piece top, pre-drilled with 2× DN50 liquid piping openings, 4× cable entry holes, with rubber gaskets and fire-stop assemblies
Base panel Split-design base with liquid piping and cable openings, anti-slip shock-absorbing pads
Mounting rails 4× galvanized square-hole rails (front/rear), depth adjustable
Cable management Vertical cable managers on both sides with cable tie-down clips
Piping supports Dedicated liquid cooling pipe mounting brackets at cabinet rear for manifold and branch line fixation
Grounding kit 3×30mm grounding copper busbar with grounding bolts and stranded copper wire
Leveling base M16 heavy-duty leveling feet with anti-slip shock pads

Protection & Compatibility Parameters

Parameter Specification
— —
Protection rating IP41 (complete cabinet)
EMC compliance Per GB/T 17626 series
Installation compatibility All standard 19-inch rack-mount equipment
Cabinet baying compatibility Seamless multi-cabinet baying with joining brackets
Seismic performance Per GB 50260-2013, designed for Seismic Intensity 8
Fire performance All materials meet B1 flame-retardant rating

5.1.2 Cabinet Load-Bearing Leveling Base

Heavy-duty leveling base purpose-designed for liquid cooling cabinets, enhancing overall load capacity and stability while enabling precise on-site leveling.

Parameter Specification
— —
Material Q235 carbon steel welded construction, powder-coated anti-corrosion finish
Dimensions 600mm × 1200mm, fully matching cabinet footprint
Structural profile No. 10 channel steel main frame, 5mm steel plate base
Leveling feet M16 heavy-duty galvanized feet (4 units)
Adjustment range ±25mm
Static load capacity per base ≥ 2,000kg
Surface treatment Electrostatic powder coating, anti-rust anti-corrosion
Mounting method Bolted connection to cabinet base
Grounding design Grounding terminal provided for equipotential bonding
Anti-slip design Rubber anti-slip pads under feet for slip resistance and vibration damping

5.1.3 Cabinet Grounding Assembly

Dedicated cabinet grounding system meeting computer room equipotential bonding requirements and ensuring electrical safety.

Parameter Specification
— —
Grounding busbar material T2 copper, tin-plated surface
Busbar specification 30mm × 3mm, length 1900mm
Conductivity ≥ 98% IACS
Grounding wire 6mm² multi-strand yellow/green bicolor copper core, length 2m
Grounding bolts M8 stainless steel with flat and spring washers
Terminal connections Copper lug crimp connection
Mounting position Vertically on rear rails of cabinet
Grounding resistance ≤ 1Ω
Corrosion resistance Tin plating thickness ≥ 5μm, long-term oxidation-free

5.2 Liquid Cooling Core Heat Exchange Units

5.2.1 Rack-Level Coolant Distribution Unit (CDU)

The KITOZER series rack-mount CDU is the core heat exchange device of the cold plate liquid cooling system. Installed at the cabinet base, it achieves primary/secondary coolant isolation and heat exchange. This CDU delivers 35kW rated cooling capacity, perfectly matched to the 30kW liquid cooling cabinet, with a compact 3U rack-mount design offering high integration and comprehensive functionality.

Basic Performance Parameters

Parameter Specification
— —
Rated cooling capacity 35kW (at primary supply 30°C / secondary return 45°C)
Applicable heat load range 10–35kW
Heat exchange efficiency ≥ 95%
Rated working pressure 1.0MPa
Test pressure 1.5MPa
Design service life ≥ 15 years
Mounting form 19-inch standard rack-mount
Mounting height 3U
Mounting position Bottom U-position of cabinet

Plate Heat Exchanger Parameters

Parameter Specification
— —
Heat exchanger type Brazed plate heat exchanger
Plate material 316L food-grade stainless steel
Brazing material Pure copper
Plate quantity 40 plates
Heat exchange area ≥ 2.5m²
Heat transfer coefficient ≥ 3,000 W/(m²·K)
Max working pressure 1.6MPa
Max working temperature 120°C
Connection size Primary DN20 female thread, secondary DN20 female thread
Pressure drop Primary ≤ 50kPa, secondary ≤ 60kPa
Media compatibility Ethylene glycol-water solution, pure water, and common coolants
Sealing form Fully brazed, gasket-free — zero leak risk

Secondary-Side Circulation Pump Parameters

Parameter Specification
— —
Pump type Magnetic drive centrifugal pump, shaft-seal-free, zero-leakage design
Quantity 1 unit (redundant dual-pump option available)
Rated flow 8m³/h
Rated head 12m
Rated power 0.37kW
Supply voltage 220V AC, 50Hz
Insulation class Class F
Protection rating IP55
Pump housing material 304 stainless steel
Impeller material Engineering plastic PPS
Bearing material Silicon carbide, wear- and corrosion-resistant
Sealing form Static seal only, no dynamic seal points — leakage completely eliminated
Control mode 0–10V variable frequency speed control, automatic flow adjustment by load
Noise level ≤ 55dB(A)
Design life ≥ 50,000 hours

Precision Filter Parameters

Parameter Specification
— —
Filter type Y-type precision filter
Installation position Secondary-side supply line
Filtration rating 5μm
Housing material 304 stainless steel
Filter element material Polypropylene melt-blown cartridge
Connection size DN20 female thread
Rated pressure 1.6MPa
Working temperature 0–80°C
Differential pressure indicator Standard equipment — automatic warning at filter blockage
Replacement method Bypass valve included, online cartridge replacement without shutdown

Pressure Stabilization Expansion Tank Parameters

Parameter Specification
— —
Tank type Diaphragm expansion tank
Nominal volume 12L
Pre-charge pressure 0.2MPa (factory preset, field adjustable)
Max working pressure 1.0MPa
Working temperature −10°C to 90°C
Tank material Carbon steel Q235-B, powder-coated anti-corrosion
Diaphragm material EPDM (ethylene-propylene-diene monomer), coolant-resistant
Connection size G1/2 female thread
Function Compensates coolant thermal expansion/contraction, stabilizes system pressure

Valve Assembly Parameters

Component Specification
— —
Primary supply/return ball valves 2 units, 304 stainless steel, DN20, with position indicator
Secondary supply/return ball valves 2 units, 304 stainless steel, DN20, with position indicator
Automatic air vent 1 unit, 304 stainless steel, G1/2 connection, automatic air purge
Safety valve 1 unit, opening pressure 0.8MPa, overpressure automatic relief
Drain valve 1 unit, 304 stainless steel ball valve, DN15, for routine blowdown
Check valve 1 unit, secondary return end, prevents reverse flow
Valve seal material PTFE (polytetrafluoroethylene), temperature- and corrosion-resistant
Valve cycle life ≥ 10,000 open/close cycles without leakage

Sensor Configuration Parameters

Component Specification
— —
Secondary supply temperature sensor PT100 platinum RTD, Class A accuracy, 304 stainless steel housing
Secondary return temperature sensor PT100 platinum RTD, Class A accuracy, 304 stainless steel housing
Secondary supply pressure sensor Range 0–1.0MPa, accuracy ±0.2% FS, 4–20mA output
Secondary return pressure sensor Range 0–1.0MPa, accuracy ±0.2% FS, 4–20mA output
Flow sensor Turbine-type, range 0.5–10m³/h, accuracy ±1%
Leak sensor Locating leak detection cable at CDU base, immediate alarm on leak

Control Unit Parameters

Parameter Specification
— —
Controller ARM architecture embedded industrial-grade controller
Display 4.3-inch color touchscreen, resolution 480×272
Display content Supply/return temperature, pressure, flow, operating status, fault information
Control functions Variable-frequency pump control, automatic temperature regulation, automatic fault alarm, valve linkage control
Communication interfaces RS485 (Modbus-RTU protocol), Ethernet (TCP/IP protocol)
Alarm modes Local audible/visual alarm, remote system alarm
Data storage ≥ 30 days historical data logging
Supply voltage 220V AC, 50Hz
Operating temperature 0–50°C
Storage temperature −20°C to 70°C
Immunity Compliant with EMC industrial-grade standards

Physical & Material Parameters

Parameter Specification
— —
External dimensions 482.6mm (W) × 132mm (H) × 600mm (D)
Unit weight Approx. 45kg
Frame material 1.5mm cold-rolled steel, electrostatic powder coating
Internal piping material 304 stainless steel
Surface color RAL7035 light gray
Mounting method Standard rack-mount, with L-type mounting brackets
Protection rating IP31

5.2.2 CPU Dedicated Liquid Cooling Cold Plate

The KITOZER series micro-channel liquid cooling cold plate is purpose-designed for server CPU heat dissipation. Featuring a red copper base with precision micro-channel manufacturing, it delivers high heat exchange efficiency and low flow resistance, compatible with mainstream x86 architecture CPU socket specifications.