Technical Design Proposal for the 40-Foot 5MWh/2.5MW Containerized Energy Storage System

Document Title: Technical Design Proposal for the 40-Foot 5MWh/2.5MW Containerized Energy Storage System

Prepared by: Guangzhou Lain Intelligent System Development Co., Ltd.

Brand: KITOZER

Version: V1.0

Date: August 2026

—

Table of Contents

  1. Company Profile
  2. Project Overview
  3. User Requirements Analysis
  4. Overall Design Description
  5. Product Configuration List
  6. Detailed Technical Parameters of Each System
  7. Core Advantages of the Solution
  8. Technical Q&A
  9. Project Construction Schedule
  10. Construction Organization Plan
  11. After-Sales Service System
  12. Personnel Training Plan
  13. Typical Engineering Cases
  14. SEO Optimization System & Website Backend Configuration
  15. Contact Information

—

1. Company Profile

Founded in 2002, Guangzhou Lain Intelligent System Development Co., Ltd. is a high-tech enterprise specializing in data center infrastructure, intelligent enclosure systems, and new-energy energy storage system R&D and manufacturing. Our core brand is KITOZER.

With over two decades of industry expertise, the company has developed advanced technologies in green, energy-efficient data center infrastructure and energy storage system integration. We deliver tailor-made solutions for diverse application scenarios and hold multiple product patents and industry qualifications. Our client base spans government agencies, industrial enterprises, telecommunications operators, and energy sector customers across China and international markets.

Main Products: Our comprehensive product portfolio includes modular cold-aisle containment systems, indoor integrated cabinets, outdoor intelligent enclosures, shielded rooms, containerized data centers, and containerized energy storage systems — covering the full spectrum of enclosure products and system integration solutions.

Manufacturing Capability: As a manufacturer, we offer flexible custom production with a complete service chain from solution design, manufacturing, and installation & commissioning to after-sales operation and maintenance. We uphold a commitment to quality as our core, distinctive design as our hallmark, and responsive after-sales support as our guarantee. Our project delivery model ensures on-time delivery and rapid service response.

Product Philosophy: The company adheres to the principles of “Safety, Efficiency, Innovation, and Pragmatism.” Leveraging years of accumulated technical expertise in enclosure structures, power distribution integration, environmental monitoring, and intelligent control, we have launched standardized and customizable containerized energy storage systems widely deployed in commercial and industrial (C&I) applications including peak-valley arbitrage, demand management, backup power, and renewable energy storage integration.

—

2. Project Overview

2.1 Project Background

Driven by carbon peak/neutrality goals and electricity market deregulation reforms, commercial and industrial users are facing multiple challenges: widening peak-valley electricity price differentials, high demand charges, and growing requirements for power supply reliability. Containerized energy storage systems have emerged as the mainstream form of user-side storage due to their factory prefabrication, rapid deployment, mobility and reusability, and proven safety and reliability.

This project addresses the user’s requirement for a 5MWh capacity / 2.5MW power application by employing a 40-foot standard high-cube container for high-density integration. The system integrates battery, power conversion, power distribution, monitoring, fire protection, and thermal management into a single, turnkey energy storage solution — meeting both cost-reduction/efficiency goals and power supply security objectives.

2.2 Construction Objectives

  • Rated capacity of 5MWh, rated power of 2.5MW, supporting 2 hours of full-power discharge
  • Establish a five-level safety protection architecture (cell → module → rack → system → enclosure), combining intrinsic safety with active protection
  • Support multiple operating modes: grid-connected peak-valley arbitrage, demand management, reactive power compensation, and off-grid backup
  • Factory prefabrication and integration for plug-and-play on-site deployment, significantly shortening construction lead time
  • Dual remote + local monitoring for unattended operation with convenient O&M

2.3 Design Basis and Standards

Standard No. Standard Name
— —
GB 51048 Design Standard for Electrochemical Energy Storage Power Stations
GB/T 36276 Lithium-ion Batteries for Electric Energy Storage
GB/T 34120 Technical Requirements for Power Conversion System of Energy Storage
GB/T 42288 Technical Requirements for Lithium-ion Battery Energy Storage Systems
GB 50054 Code for Design of Low Voltage Electrical Installations
GB 50057 Code for Design of Protection of Structures against Lightning
GB/T 1413 Series 1 Freight Containers — Classification, Dimensions and Ratings

—

3. User Requirements Analysis

3.1 Basic Functional Requirements

  • Grid-connected charge/discharge supporting constant power, constant current, and constant voltage modes
  • Rapid switching to off-grid mode during grid outage to supply critical loads
  • Automatic load peak tracking and maximum demand smoothing to reduce basic electricity charges
  • Four-quadrant operation with reactive power output capability for power factor correction
  • Dual local touchscreen and remote cloud monitoring and management

3.2 Performance Specification Requirements

Parameter Requirement
— —
System DC voltage level 1500V (reduces line losses, improves efficiency)
PCS overall efficiency ≥98.5%
System round-trip efficiency ≥88%
Grid current THD ≤3%
Battery cycle life ≥6000 cycles (1C, 25°C, 80% SOH)
Grid/off-grid switching time ≤20ms

3.3 Safety Protection Requirements

  • Multi-level electrical protection: fuses, circuit breakers, surge protection, insulation monitoring
  • Multi-level battery protection: over-voltage, under-voltage, over-current, over-temperature, short-circuit protection
  • Dedicated fire suppression system: early detection + clean agent extinguishing
  • Enclosure protection rating: IP65 for all-weather outdoor operation
  • Complete grounding and lightning protection system

3.4 Operation & Maintenance Management Requirements

  • Real-time monitoring of all equipment operating status with graded fault alarms
  • Automatic statistics of charge/discharge energy and electricity cost savings with operational reporting
  • Remote parameter configuration, firmware upgrade, and fault diagnosis capability
  • Multi-level user privilege management with auditable operation logs

3.5 Environmental Adaptability Requirements

Parameter Requirement
— —
Ambient operating temperature -20°C to +45°C
Corrosion protection C4 grade (suitable for coastal and industrial zones)
Seismic resistance Intensity 8
Wind resistance Grade 12
Protection Dust-proof, rain-proof, salt-spray resistant

—

4. Overall Design Description

4.1 Design Principles

Principle Description
— —
Safety First Multi-layer protection from cell to enclosure, comprehensive coverage of electrical, fire, and structural safety
Reliability Priority Core components from proven brands with design margins on critical parameters
High Efficiency 1500V high-voltage architecture + high-efficiency PCS + intelligent thermal management for minimal energy loss
Intelligent & Advanced EMS intelligent dispatch with multi-mode automatic switching and cloud-based O&M support
Economical & Practical Optimized space utilization, reduced initial investment and lifecycle cost
Scalable Supports multi-unit parallel expansion; can integrate PV and EV chargers to build microgrids

4.2 System Architecture

The system adopts a three-layer architecture:

  • Equipment Layer: Battery modules, PCS, power distribution cabinets, fire protection, thermal management, and sensors as underlying devices
  • Control Layer: BMS, PCS controller, fire alarm controller, thermal management controller, and environmental data acquisition unit
  • Management Layer: EMS energy management system, local touchscreen HMI, and remote cloud platform

External interfaces connect the system to the utility grid through the grid-connection point and to the user’s monitoring system via communication interfaces.

4.3 Container Internal Layout

The 40-foot standard high-cube container is divided into two fire-separated zones: the battery compartment and the electrical compartment.

Battery Compartment: Occupying approximately 70% of the interior space, it houses 12 battery racks arranged in double rows, each containing 30 modules, for a total of 360 modules. The compartment is equipped with air ducts, fire suppression nozzles, temperature/smoke detectors, and water immersion sensors.

Electrical Compartment: Located at the end of the container, it integrates the DC busbar cabinet, PCS, AC distribution cabinet, EMS control cabinet, fire alarm host, and auxiliary power distribution unit.

The container end features Class-A fire-rated double doors. Side walls are fitted with emergency escape windows and ventilation louvers. The floor base is equipped with waterproof cable glands for cable entry.

4.4 Technology Route Selection

Subsystem Selected Technology Key Advantages
— — —
Battery Lithium iron phosphate (LFP) cells, 1500V DC system High safety, long cycle life, superior cost-effectiveness
Power Conversion Centralized 2.5MW PCS, three-level topology High efficiency, mature control, easy maintenance
Thermal Management Industrial precision air conditioning + balanced airflow duct cooling Cell temperature differential ≤5°C, high reliability, no leakage risk
Fire Suppression Triple detection (smoke + heat + combustible gas) + perfluorohexanone (Novec 1230) piped extinguishing system Clean, residue-free, specifically suited for lithium battery fires

4.5 Operating Modes

Mode Description
— —
Peak-Valley Arbitrage Charge during off-peak hours, discharge during peak hours with automatic tariff schedule execution
Demand Management Real-time load tracking, automatic discharge to shave peaks when threshold exceeded
Backup Power Automatic transfer to off-grid mode upon grid failure, constant voltage/frequency supply
Reactive Power Compensation STATCOM mode for power factor improvement
Demand Response Receives grid dispatch commands for peak shaving and frequency regulation
Manual Maintenance Step-by-step manual operation during inspection and commissioning

—

5. Product Configuration List

5.1 Battery Energy Storage DC System

No. Equipment Specifications Unit Qty Remarks
— — — — — —
1 LFP energy storage battery module 51.2V/280Ah, 16S1P, 14.336kWh pcs 360 30 in series/rack, 12 racks total
2 Rack-level battery cluster management unit (BCU) 30-series management, voltage/current/temperature acquisition, active balancing set 12 1 per rack
3 Battery array management system (BAMS) 12-cluster management, SOC/SOH estimation, coordinated with EMS/fire protection set 1 System-level BMS
4 Vertical battery mounting rack Cold-rolled steel, powder-coated, 10 tiers, insulated support, load capacity ≥3.5 tons set 12 Double-row arrangement
5 DC cluster-level fuse 1500V DC, 315A, high breaking capacity pcs 12 1 on positive terminal of each cluster
6 DC manual isolating switch 1500V DC, 400A, with visible disconnection point pcs 12 For maintenance isolation
7 DC busbar cabinet 12-in 1-out, main circuit breaker, insulation monitoring, voltage/current acquisition set 1 DC main busbar

5.2 Power Conversion System & AC/DC Distribution System

No. Equipment Specifications Unit Qty Remarks
— — — — — —
1 Centralized energy storage PCS 2.5MW, DC 1000~1700V, AC 400V, grid-connected/off-grid dual mode set 1 Three-level topology
2 AC main incoming circuit breaker 4P, 4000A, intelligent trip unit, shunt trip + auxiliary contacts pcs 1 AC main protection
3 Grid-connected AC contactor AC 400V, 4000A, with auxiliary contacts pcs 1 Grid-connection interlock
4 AC surge protective device 3P+N, Type 1 lightning protection, 100kA set 1 Lightning surge protection
5 Bi-directional smart energy meter Three-phase four-wire, 0.5S class, RS485 communication pcs 1 Charge/discharge metering
6 Auxiliary distribution transformer 10kVA, 400V/220V, single-phase isolation pcs 1 Auxiliary equipment power
7 Miniature circuit breakers 1P/2P, 10A/16A/32A, C-curve pcs 20 Branch circuit protection

5.3 Energy Management & Environmental Monitoring System

No. Equipment Specifications Unit Qty Remarks
— — — — — —
1 Energy storage EMS controller Industrial embedded, charge/discharge scheduling, multi-system coordination set 1 System brain
2 Industrial touchscreen HMI 15-inch, capacitive touch, flush-mount pcs 1 Local human-machine interface
3 Environmental monitoring acquisition unit Multi-signal input, RS485 communication, DC 24V pcs 1 Environmental data aggregation
4 Temperature/humidity sensors -20~80°C, 0~100%RH, RS485 pcs 6 4 in battery compartment, 2 in electrical compartment
5 Water immersion sensors Electrode type, digital output, IP67 pcs 4 Four corners of compartment floor
6 Door magnetic switches Magnetic induction, digital output pcs 2 1 per door
7 4G remote communication module Full-network compatible, external antenna set 1 Cloud connectivity
8 Industrial Ethernet switch 8-port gigabit, DIN-rail mount, DC 24V pcs 1 Internal network

5.4 Energy Storage Dedicated Fire Suppression System

No. Equipment Specifications Unit Qty Remarks
— — — — — —
1 Perfluorohexanone (Novec 1230) piped extinguishing system 50kg per cylinder, piped network + nozzle full coverage set 2 Battery compartment zoned suppression
2 Fire alarm controller Addressable loop type, multi-zone, relay outputs pcs 1 Fire protection master control
3 Photoelectric smoke detectors DC 24V, addressable type pcs 12 Evenly distributed on compartment ceiling
4 Heat detectors Fixed temperature 70°C, addressable type pcs 12 Paired with smoke detectors
5 Combustible gas detectors Detects H₂/CO, RS485 + digital output pcs 6 Battery compartment floor area
6 Audible-visual alarm DC 24V, ≥110dB pcs 2 1 inside, 1 outside container
7 Emergency start/stop buttons With protective cover, manual trigger pcs 2 Both sides outside container
8 Mechanical pressure relief vents Opens at 0.1MPa, 300×300mm pcs 2 Balances compartment pressure

5.5 Thermal Management & Ventilation System

No. Equipment Specifications Unit Qty Remarks
— — — — — —
1 Industrial precision air conditioner Cooling capacity 12kW, heating/cooling combined, RS485 communication pcs 4 2 in battery compartment, 2 in electrical compartment
2 Axial exhaust fans Airflow 5000m³/h, static pressure 150Pa, IP54 pcs 4 Emergency ventilation
3 Intake louvers Aluminum alloy, insect mesh + dust filter media pcs 4 Side wall air intake
4 Motorized fire dampers 70°C fusible link closure, fire alarm interlock pcs 4 Ventilation circuit isolation
5 Airflow distribution ducting Galvanized steel, custom design, adjustable air outlets set 2 Battery compartment temperature equalization
6 Auxiliary electric heaters 2kW, PTC type, dual over-temperature protection pcs 4 Low-temperature heating

5.6 40-Foot Container Enclosure System

No. Equipment Specifications Unit Qty Remarks
— — — — — —
1 40-foot standard high-cube container External 12192×2438×2896mm, rock-wool insulation, IP65 pcs 1 Primary load-bearing structure
2 Class-A fire-rated double door 1800×2100mm, door closer + escape lock + observation window set 1 End main entrance
3 Emergency escape windows 600×800mm, tempered glass, breakable from inside pcs 2 Symmetrical on side walls
4 Anti-slip load-bearing floor 3mm checkered steel plate, anti-corrosion, uniformly distributed load ≥10kN/m² set 1 Equipment support
5 Outdoor weather-resistant anti-corrosion coating Epoxy zinc-rich primer + polyurethane topcoat, salt spray ≥1000h set 1 C4 grade corrosion protection
6 Safety warning and signage system Nameplates, warnings, circuit labels, operating instructions set 1 O&M identification

5.7 Cables, Conduits & Auxiliary Materials

No. Equipment Specifications Unit Qty Remarks
— — — — — —
1 Intra-cluster power cables 120mm² silicone rubber cable, 1500V DC m 600 Module interconnection
2 DC main cables 240mm² flame-retardant armored, 1500V DC m 200 Cluster to busbar cabinet/PCS
3 AC grid-connection cables 4×240+1×120mm², 0.6/1kV flame-retardant m 100 PCS to grid-connection point
4 Communication shielded cables RVSP 2×1.5mm², twisted pair shielded m 800 Signal communication
5 Auxiliary power cables RVV 3×2.5, 2×1.5mm² m 500 Auxiliary equipment power
6 Hot-dip galvanized conduit DN20/25/50, with fittings m 400 Cable protection
7 Waterproof cable glands PG9/16/21/42, metal, IP67 pcs 80 Container cable entry sealing
8 Copper cable lugs OT/UT type, 1.5~240mm², tin-plated pcs 600 Cable termination
9 Busbar connection assembly T2 copper, tin-plated, with insulating supports set 1 Main circuit busbar

5.8 Mounting, Fixing & Grounding Accessories

No. Equipment Specifications Unit Qty Remarks
— — — — — —
1 Fixing bolt kits M8~M16, galvanized expansion + hex socket set 300 Equipment mounting
2 Flame-retardant nylon cable ties 4×200/8×300/10×400, weather-resistant black pack 20 Cable bundling
3 Insulation protection materials Electrical tape, heat-shrink tubing, insulating barriers batch 2 Insulation protection
4 Equipment identification plates Acrylic, engraved name and number pcs 100 O&M identification
5 Main grounding flat bar 40×4mm, hot-dip galvanized m 50 Ring grounding busbar
6 Protective grounding cables BVR 16/6mm², yellow-green m 200 Equipment equipotential grounding
7 LED interior lighting 20W panel light, door-activated switch set 4 Compartment lighting
8 Maintenance power outlets 10A 5-hole waterproof, AC 220V pcs 4 Temporary power for maintenance

—

6. Detailed Technical Parameters of Each System

6.1 Battery Energy Storage DC System

6.1.1 Lithium Iron Phosphate Energy Storage Battery Module

Cell Parameters:

Parameter Specification
— —
Cathode material Lithium iron phosphate (olivine structure), thermal stability ≥700°C
Anode material Synthetic graphite, high lithium intercalation capacity, stable cycling
Separator PP/PE composite microporous membrane, 130°C shutdown protection
Electrolyte Carbonate system + flame-retardant additives
Cell nominal voltage 3.2V
Cell rated capacity 280Ah
Cell energy density ≥165Wh/kg
Cycle life ≥6000 cycles (1C charge/discharge, 25°C, 80% residual capacity)

Module Electrical Parameters:

Parameter Specification
— —
Series/parallel configuration 16S1P
Nominal voltage 51.2V
Rated capacity 280Ah
Rated energy 14.336kWh
Operating voltage range 43.2V ~ 57.6V
Max continuous charge/discharge current 1C (280A)
Peak discharge current 1.5C / 30s
DC internal resistance ≤8mΩ
Insulation resistance ≥100MΩ (at DC 1000V)

Mechanical & Environmental:

Parameter Specification
— —
Enclosure Cold-rolled steel plate, powder-coated, IP20
Dimensions Approx. 700×450×180mm
Weight Approx. 110kg
Operating temperature Charging: -10°C~55°C; Discharging: -20°C~60°C
Storage temperature -40°C~60°C
Altitude ≤2000m (derated above this altitude)

Safety Features:

  • Passes nail penetration, crush, overcharge, short-circuit, and hot-box safety tests
  • Built-in voltage and temperature acquisition wiring harness with real-time BMS monitoring
  • Flame-retardant enclosure and structural design to delay thermal propagation

6.1.2 Battery Cluster Management Unit (BCU)

Parameter Specification
— —
Series management capacity Max 32 series (30 series in this configuration)
Voltage acquisition accuracy ±5mV
Temperature acquisition 16 NTC channels, accuracy ±0.5°C
Current acquisition Hall sensor, range ±500A, accuracy ±0.5% FS
Insulation monitoring 0~10MΩ, accuracy ±10%
SOC estimation Coulomb counting + OCV correction, steady-state accuracy ≤±3%
Balancing function Active balancing, balancing current ≥5A
Protection logic Three-level protection: alarm → current limiting → shutdown
Communication interfaces 2× CAN, 1× RS485
Power supply DC 9~36V wide range, power consumption ≤10W
Operating temperature -40°C~85°C
Mounting DIN-rail, mounted at top of battery rack

6.1.3 Battery Array Management System (BAMS)

Parameter Specification
— —
Cluster management capacity Max 24 clusters (12 clusters in this configuration)
Core functions Full-system data aggregation, system-level SOC/SOH estimation, charge/discharge power control, graded fault handling, thermal runaway early warning, coordinated fire protection and thermal management
Protection functions System over/under-voltage, total over-current, insulation fault, excessive temperature differential
Communication interfaces CAN, RS485, Ethernet; supports Modbus, IEC 104 protocols
Data storage Local storage ≥1 year of operational and fault records
Power supply DC 24V±10%, power consumption ≤30W
Operating temperature -20°C~70°C
Mounting Rack-mount, integrated in control cabinet
MTBF ≥100,000 hours

6.1.4 Vertical Battery Mounting Rack

Parameter Specification
— —
Material Q235 high-quality structural steel, integrally welded + bolted
Structure 10 tiers, 3 modules per tier, 30 modules per rack
Load capacity ≥3500kg per rack, safety factor ≥1.5
Insulation High-strength insulated base plate on each tier, module-to-rack insulation ≥100MΩ
Anti-fall Limit stop bars and hold-down clamps on each tier
Cable routing Segregated power/signal cable troughs with fixing points
Surface treatment Pickling + phosphating + electrostatic powder coating, C4 corrosion protection
Dimensions Approx. 750×800×2200mm (W×D×H)

6.1.5 DC Cluster-Level Fuse

Parameter Specification
— —
Rated voltage 1500V DC
Rated current 315A
Breaking capacity ≥50kA
Characteristic gPV general-purpose photovoltaic fuse characteristic
Base material High-temperature flame-retardant, V0 grade
Connection Bolted compression
Operating temperature -40°C~125°C
Standards GB/T 13539, IEC 60269
Function Cluster-level short-circuit protection, isolates faulty cluster to prevent propagation

6.1.6 DC Manual Isolating Switch

Parameter Specification
— —
Rated voltage 1500V DC
Rated current 400A
Poles 1P
Breaking capacity Capable of load-breaking
Operation Manual handle, visible disconnection point, lockable
Mechanical life ≥10,000 operations
Protection rating IP20 (inside cabinet)
Function Maintenance isolation for personnel safety

6.1.7 DC Busbar Cabinet

Parameter Specification
— —
Rated voltage 1500V DC
Circuits 12 inputs, 1 output
Main circuit breaker 4000A DC molded-case, overload and short-circuit protection
Insulation monitoring Continuous online monitoring of ground insulation resistance, alarm on anomaly
Instrumentation High-precision voltage and current sensors, power and energy calculation
Surge protection Built-in Type 2 DC surge protective device
Enclosure Cold-rolled steel 2.0mm, electrostatic powder coating, IP20
Display Cabinet door touchscreen showing voltage, current, insulation, and branch status
Accessories Lighting, maintenance outlet, terminal blocks
Dimensions Approx. 800×600×2200mm (W×D×H)
Mounting Floor-standing, fixed installation

—

6.2 Power Conversion System & AC/DC Distribution System

6.2.1 Centralized Energy Storage PCS

Main Circuit Parameters:

Parameter Specification
— —
Rated power 2.5MW
DC side Voltage 1000~1700V, max current 1670A
AC side Voltage 400V±15%, frequency 50Hz±0.5Hz, current 3608A
Power factor -0.95~+0.95 continuously adjustable
Current THD ≤3% (at rated power)

Performance Specifications:

Parameter Specification
— —
Maximum efficiency ≥98.5%
European efficiency ≥98.0%
Dynamic response ≤10ms
Grid/off-grid switching ≤20ms
Noise ≤75dB @ 1m

Functional Features:

  • Grid-connected mode: Constant power, constant current, constant voltage charging, reactive power compensation, primary frequency regulation, low voltage ride-through
  • Off-grid mode: V/f control, unbalanced load capability, non-linear load support
  • Black start: Independent voltage establishment without grid
  • Anti-islanding protection: Active + passive detection with rapid grid disconnection
  • Protection functions: DC over/under-voltage, reverse polarity, insulation fault; AC over/under-voltage, over/under-frequency, short-circuit, ground fault; equipment over-temperature, overload, and fan fault protection

Control & Communication:

Parameter Specification
— —
Topology Three-level NPC topology
Control DSP + FPGA all-digital control
Interfaces RS485, CAN, Ethernet, fiber optic
Protocols Modbus, IEC 61850, etc.
HMI 10-inch color touchscreen for local parameter setting and status monitoring

Mechanical & Environmental:

Parameter Specification
— —
Cooling Forced air cooling with intelligent variable-speed fans
Structure Cabinet modular design, pluggable power units
Protection rating IP20
Operating temperature -20°C~50°C
Storage temperature -40°C~70°C
Humidity 5%~95% non-condensing
Dimensions Approx. 1200×1000×2200mm
Weight Approx. 2500kg
Certification standards GB/T 34120, GB/T 19964, IEC 62116 — meets grid-connection requirements

6.2.2 AC Main Incoming Circuit Breaker

Parameter Specification
— —
Type Air circuit breaker (ACB)
Rated voltage AC 400V
Rated current 4000A
Poles 4P
Breaking capacity Rated short-circuit breaking capacity ≥65kA
Trip unit Intelligent electronic trip unit: long delay + short delay + instantaneous + ground fault
Accessories Shunt trip coil, auxiliary contacts, alarm contacts
Operation Motor-operated stored-energy closing, manual opening, remote opening capability
Mounting Fixed type
Standards GB 14048.2, IEC 60947-2

6.2.3 Grid-Connected AC Contactor

Parameter Specification
— —
Rated voltage AC 400V
Rated current 4000A
Poles 3P
Coil voltage AC 220V
Auxiliary contacts 4 NO + 4 NC
Mechanical life ≥1,000,000 operations
Electrical life ≥100,000 operations
Function Grid-connection circuit switching, coordinated with anti-islanding protection

6.2.4 AC Surge Protective Device

Parameter Specification
— —
Type Type 1 power SPD
Voltage AC 380/400V
Poles 3P+N
Nominal discharge current (In) 100kA (8/20μs)
Max discharge current (Imax) 200kA
Voltage protection level (Up) ≤2.5kV
Response time ≤25ns
Failure indication Red/green window indicator with remote signaling contact
Disconnection Thermal + overcurrent trip, automatic disconnection on fault
Mounting DIN-rail
Standards GB 18802.1, IEC 61643-11

6.2.5 Bi-Directional Smart Energy Meter

Parameter Specification
— —
Type Three-phase four-wire multifunction energy meter
Accuracy Active energy: Class 0.5S; Reactive energy: Class 2
Rated voltage 3×220/380V
Rated current 1.5(6)A, with current transformers
Frequency 50Hz
Metering functions Forward/reverse active energy, four-quadrant reactive energy, demand, multi-tariff time-of-use metering
Measurement Voltage, current, power, power factor, frequency, harmonics
Communication RS485 interface, supports DL/T645 and Modbus protocols
Display LCD cyclic display
Pulse output Active/reactive energy pulses for verification
Power supply AC 85~265V wide range
Power consumption ≤2W
Mounting DIN-rail

6.2.6 Auxiliary Distribution Transformer

Parameter Specification
— —
Capacity 10kVA
Phases Single-phase
Input AC 400V
Output AC 220V
Insulation class Class F
Efficiency ≥95%
Cooling Natural air cooling
Protection rating IP20
Windings All-copper windings
Function Provides isolated power to auxiliary equipment, improves anti-interference capability

6.2.7 Auxiliary Circuit Miniature Circuit Breakers

Parameter Specification
— —
Type Miniature circuit breaker (MCB)
Voltage AC 230/400V
Current ratings 10A, 16A, 32A
Poles 1P, 2P
Trip characteristic C-curve
Breaking capacity 6kA
Mechanical life ≥20,000 operations
Mounting DIN-rail
Standards GB 10963, IEC 60898
Application Branch circuit protection for thermal management, fire protection, monitoring, lighting, and outlets

—

6.3 Energy Management & Environmental Monitoring System

6.3.1 Energy Storage EMS Controller

Hardware Platform:

Parameter Specification
— —
Processor Industrial-grade ARM multi-core, clock frequency ≥1.5GHz
Memory DDR4 ≥2GB
Storage eMMC ≥32GB, SD card expansion supported
Power supply DC 24V±15%, power consumption ≤20W
Operating temperature -40°C~85°C
Mounting DIN-rail / rack-mount
MTBF ≥100,000 hours

Interface Configuration:

Interface Specification
— —
Ethernet 4× Gigabit ports
Serial ports 4× RS485/232 (configurable)
Digital inputs 8× DI, dry contacts
Relay outputs 4× DO
4G Built-in full-network cellular module
GPS/BeiDou Optional time synchronization and positioning

Core Functions:

Function Description
— —
Data acquisition & monitoring Unified collection of all data from BMS, PCS, energy meter, thermal management, fire protection, and environmental sensors; real-time display and historical storage
Charge/discharge scheduling Built-in peak-valley arbitrage, demand management, backup power, and demand response strategies with automatic scheduled execution; custom strategy programming supported
Multi-system coordination Coordinates BMS power limiting, PCS power output, thermal management start/stop, and fire protection interlock
Alarm management Three-level alarms (advisory, major, critical); multiple notification channels including local audible-visual, SMS, APP, and email; full alarm history traceability
Statistical analysis Automatic daily/monthly/annual reporting; charge/discharge energy, electricity cost savings, depth of discharge, and cycle count statistics
Access control Multi-level privileges for administrator, operator, and guest; operation log recording
Remote O&M Remote parameter configuration, firmware upgrade, and fault diagnosis

Software & Protocols:

Item Specification
— —
Operating system Embedded Linux
Northbound protocols MQTT, HTTP, Modbus TCP, IEC 104
Southbound protocols Modbus RTU, CAN, proprietary protocols

6.3.2 Industrial Touchscreen HMI

Parameter Specification
— —
Screen size 15 inches
Type TFT true-color capacitive touch
Resolution 1024×768
Color depth 16.7 million colors
Brightness 300 cd/m²
Processor Industrial-grade ARM
Memory 512MB DDR3 + 512MB Flash
Interfaces 2× RS485, 1× Ethernet, 1× USB
Power supply DC 24V, power consumption ≤15W
Operating temperature -20°C~70°C
Protection rating Front panel IP65
Mounting Flush-mount in cabinet door
Functions Local status display, parameter setting, manual control, fault inquiry

6.3.3 Environmental Monitoring Acquisition Unit

Parameter Specification
— —
Processor 32-bit ARM
Analog inputs 8× 4-20mA / 0-10V, 12-bit ADC
Digital inputs 16× DI
Relay outputs 8× DO
Communication 2× RS485, 1× Ethernet
Protocol Modbus RTU/TCP
Power supply DC 24V, power consumption ≤10W
Operating temperature -40°C~85°C
Mounting DIN-rail
Function Aggregates temperature, humidity, water immersion, door status and other environmental signals for upload to EMS

6.3.4 In-Cabinet Temperature/Humidity Sensors

Parameter Specification
— —
Temperature range -20°C~+80°C
Temperature accuracy ±0.5°C @ 25°C
Humidity range 0%~100% RH
Humidity accuracy ±3% RH @ 25°C
Output RS485 digital, Modbus protocol
Power supply DC 12~24V
Power consumption ≤1W
Response time Temperature ≤10s; Humidity ≤15s
Enclosure ABS, IP30
Mounting Wall-mount / ceiling-mount