Technical Design Proposal: 45kW Liquid-Cooled Server Rack

Product Model: KITOZER-LC-45kW-42U

Design Organization: Guangzhou Lain Intelligent System Development Co., Ltd.

Brand: KITOZER

Version: V2.0

Date: August 2026

—

Table of Contents

Chapter 1 Company Profile

1.1 Corporate Development History

1.2 Core Business and Product Lines

1.3 Qualifications and Honors

1.4 Manufacturing and R&D Capabilities

Chapter 2 Project Overview

2.1 Industry Background and Development Trends

2.2 Project Construction Objectives

2.3 Scope of Application

2.4 Design Basis and Applicable Standards

Chapter 3 User Requirement Analysis

3.1 Basic Functional Requirements

3.2 Performance Specification Requirements

3.3 Liquid Cooling System Specific Requirements

3.4 Structural and Installation Requirements

3.5 Operation, Maintenance, and Management Requirements

Chapter 4 Overall Design Description

4.1 Overall Design Principles

4.2 System Architecture

4.3 Internal Rack Layout Design

4.4 Liquid Cooling Pipeline Topology

4.5 Safety Redundancy and Reliability Design

Chapter 5 Quotation and Configuration List

5.1 Standard Configuration per Rack

5.2 Optional Value-Added Accessories

5.3 Bulk Project Quotation Notes

Chapter 6 Technical Parameters of System Products

6.1 Rack Main Frame System

6.2 Door and Locking System

6.3 Internal Mounting and Cable Management System

6.4 Manifold Liquid Distribution System

6.5 Packaging and Transport Materials

Chapter 7 Core Advantages of the Solution

7.1 High-Density Heat Dissipation Capability

7.2 Structural Mechanical Reliability

7.3 Liquid Cooling System Safety

7.4 Operational Maintenance Convenience

7.5 Customization and Adaptation Capability

7.6 Green and Low-Carbon Energy Efficiency

Chapter 8 Technical Q&A

8.1 Basic Rack Knowledge

8.2 Liquid Cooling System Technology

8.3 Installation and Construction

8.4 Operation and Maintenance

8.5 Selection and Customization

Chapter 9 Construction Schedule

9.1 Overall Project Cycle

9.2 Work Content and Timeline by Phase

9.3 Key Milestone Control and Deliverables

Chapter 10 Construction Organization Plan

10.1 Project Organizational Structure

10.2 Core Personnel Configuration and Responsibilities

10.3 On-Site Construction Standard Procedure

10.4 Full-Process Quality Control System

10.5 Safety Production Management

10.6 Civilized Construction and Site Management

Chapter 11 After-Sales Service System

11.1 Warranty Service Commitment

11.2 Multi-Level Fault Response Mechanism

11.3 On-Site Service Operation Standards

11.4 Spare Parts Supply Guarantee

11.5 Lifetime Value-Added Services

Chapter 12 Training Plan

12.1 Training Objectives and Audience

12.2 Tiered Training Content System

12.3 Diversified Training Methods and Arrangements

12.4 Training Assessment and Acceptance Criteria

12.5 Training Documentation Deliverables

Chapter 13 Project Case Studies

13.1 Leading AI Computing Center Liquid-Cooled Rack Cluster

13.2 Prestigious University HPC Center High-Density Liquid-Cooled Data Room

13.3 Major Internet Enterprise Edge Data Center

13.4 National Research Institute Liquid Cooling Test Platform

Chapter 14 Search Keywords and SEO Tags

14.1 Full-Category Keyword Matrix

14.2 Complete SEO Tag System

14.3 Internal Link Anchor Text Strategy

Chapter 15 Website Backend Configuration

15.1 Standard Backend Settings

15.2 Advanced Backend Settings

15.3 Search Optimization Settings

Appendix: Company Contact Information

—

Chapter 1: Company Profile

1.1 Corporate Development History

Founded in 2002, Guangzhou Lain Intelligent System Development Co., Ltd. is a national high-tech enterprise specializing in the research and manufacturing of data center infrastructure. With over two decades of deep engagement in the data center construction and intelligent rack sector, the company has grown from its early standard server racks and shielded racks to a comprehensive product portfolio encompassing micro-module cold aisle containment, integrated data racks, outdoor telecommunication cabinets, containerized data centers, and liquid-cooled data center infrastructure — building full life-cycle products and service capabilities for data center facilities.

Since its inception, the core brand KITOZER has remained committed to technology-driven innovation, closely tracking global data center technology trends. The company has successively launched several generations of rack products tailored to different computing power levels. Against the current backdrop of the explosive growth of AI large models and high-performance computing, and with server power density continuously climbing, the company strategically positioned itself early in the liquid cooling technology sector. A dedicated liquid cooling R&D team was established, overcoming core technical challenges including pipeline sealing, drip-free connections, uniform fluid distribution, and leak protection. This has resulted in a complete liquid-cooled rack product matrix covering 30kW, 45kW, 60kW, and 80kW power segments, complemented by full liquid cooling solutions including CDU (Coolant Distribution Units), outdoor cooling sources, and intelligent monitoring systems.

Through more than 20 years of market cultivation, KITOZER has evolved from a single rack manufacturer into a leading data center total solution provider in China. Our business covers all 31 provinces, municipalities, and autonomous regions nationwide, and extends to overseas markets including Southeast Asia, the Middle East, Africa, and Latin America. To date, we have served over 1,000 customers across government, finance, education, healthcare, internet, and scientific research sectors, completing thousands of data center construction projects — earning a solid reputation and significant brand influence within the industry.

1.2 Core Business and Product Lines

The company’s core business centers on data center infrastructure, organized into four major product series and two project service systems:

Rack Products Series: Comprehensive sheet-metal rack product line including standard network server racks, shielded racks, integrated intelligent racks, outdoor waterproof cabinets, wall-mounted cabinets, console consoles, and video walls — all supporting deep customization to suit diverse industry scenarios.

Micro-Module and Cold Aisle Series: Single-row micro-modules, double-row cold aisle containment systems, intelligent busways, and precision power distribution units enabling rapid deployment and elastic expansion for small and medium-sized data centers.

Liquid Cooling Infrastructure Series: Cold plate liquid-cooled racks, immersion liquid-cooled racks, CDU coolant distribution units, Manifold liquid distributors, outdoor precision air conditioners and cooling towers, and intelligent leak detection monitoring systems — covering complete liquid cooling heat dissipation solutions from single racks to cluster-level deployments.

Data Center Environment Monitoring Series: UPS uninterruptible power supplies, precision air conditioning, environment and power monitoring systems (DCIM), fire protection and security systems — providing comprehensive operational assurance.

Data Center Engineering Services: Integrated turnkey data center services from solution design, detailed design, on-site construction, system commissioning to final acceptance — covering all disciplines including decoration, power distribution, HVAC, fire protection, and monitoring.

Custom R&D Services: Dedicated R&D and production for non-standard racks, special environment data rooms, and customized liquid cooling solutions addressing specific customer requirements — with three sets of design proposals provided free of charge for client selection.

1.3 Qualifications and Honors

The company maintains strict compliance with regulations and prioritizes quality, holding multiple authoritative industry qualifications and certifications:

  • National High-Tech Enterprise Certification
  • ISO9001 Quality Management System Certification
  • ISO14001 Environmental Management System Certification
  • ISO45001 Occupational Health and Safety Management Certification
  • China Data Center Engineering Grade 1 Qualification
  • Electronic and Intelligent Engineering Professional Contracting Qualification
  • Dozens of utility model patents and appearance design patents
  • Products certified with national mandatory 3C, CE, and ROHS certifications
  • China Data Center Technology Innovation Excellence Award
  • National Data Center Equipment Industry Quality-Trusted Brand

1.4 Manufacturing and R&D Capabilities

The company’s manufacturing base is located in Panyu District, Guangzhou, featuring modern standard factory floors exceeding 10,000 square meters. Fully equipped with advanced sheet-metal fabrication and testing facilities — including CNC laser cutting machines, CNC press brakes, CNC turret punches, fully automatic electrostatic powder coating lines, argon arc welding stations, pressure testing benches, salt spray test chambers, and CMM coordinate measuring machines — we achieve full in-house production from raw materials to finished products, ensuring controllable capacity and quality.

Production Management: The company implements lean production models with a strict quality management system, executing a “three-inspection system” (self-inspection, mutual inspection, and specialized inspection). Every process has defined operating standards and inspection requirements. Finished products undergo complete inspections covering appearance, dimensions, performance, sealing, and pressure resistance before shipment, ensuring zero-defect delivery.

R&D Capability: The company has assembled a professional R&D team of senior structural engineers, fluid engineers, and electrical engineers — core members each with over a decade of industry experience in data center equipment. Continuously tracking cutting-edge industry technologies, the company invests more than 8% of annual revenue in R&D innovation, iterating product performance and launching new products to meet evolving market demands. For the liquid cooling sector, the company has established a dedicated liquid cooling laboratory capable of conducting pipeline flow resistance testing, heat exchange efficiency testing, seal life testing, and leak simulation testing — providing solid technical support for product reliability.

—

Chapter 2: Project Overview

2.1 Industry Background and Development Trends

With the rapid advancement of artificial intelligence, big data, cloud computing, and high-performance computing technologies, data centers — as the core digital economy infrastructure — are experiencing explosive growth in computing demand. Concurrently, the power density of individual servers continues to climb. Traditional general-purpose servers typically consume 300–500W per unit, with rack-level density commonly at 5–10kW. However, current AI training servers and high-performance computing servers have already surpassed 3kW per unit, some reaching 5–8kW, driving single-rack power requirements to 30kW, 45kW, and beyond.

Traditional air-cooling heat dissipation relies on air convection to carry away heat. Constrained by physical limitations — air specific heat capacity, fan static pressure, and rack ventilation rates — the maximum cooling capacity per rack is approximately 15–20kW. Moreover, under high loads, fan noise and energy consumption rise significantly while local hot-spot issues become prominent, making air cooling inadequate for next-generation high-density computing equipment. In this context, liquid cooling technology — leveraging the significant advantages of high liquid specific heat capacity, superior heat exchange efficiency, low noise, and excellent energy efficiency — has become the mainstream technical approach for high-density data center heat dissipation.

Cold plate liquid cooling, as the most mature and widely deployed liquid cooling solution, installs cold plates on server core chips. Coolant flows through the cold plates to absorb heat, then circulates through in-rack manifolds and external cooling source systems. This achieves single-rack cooling capacities exceeding 45kW with ease, while preserving the rack-mount server deployment form factor. With excellent compatibility with existing data center infrastructure and low retrofit costs, it is the preferred choice for high-density heat dissipation in modern computing centers.

2.2 Project Construction Objectives

This proposal is designed for single-rack 45kW power density application scenarios, developing a dedicated 45kW liquid-cooled server rack. The objectives are to deliver a product with reliable structure, efficient heat dissipation, convenient operation, and safe stable performance. Specific objectives include:

  • Cooling Capacity Target: Stably supports 45kW heat dissipation load per rack, meeting the cooling needs of mainstream high-density liquid-cooled servers; server core chip temperatures maintained within reasonable ranges with no local overheating.
  • Structural Safety and Reliability: Rack frame provides sufficient load-bearing capacity and structural strength; liquid cooling system is reliably sealed with zero leak risk; overall performance meets requirements for long-term stable data center operation.
  • Efficient and Convenient Maintenance: Standardized modular design; servers support rapid hot-swap maintenance; pipeline connections are simple to operate; daily inspection and fault troubleshooting are convenient — reducing operational complexity and cost.
  • Standard Compatibility: 19-inch standard rack dimensions, compatible with mainstream rack-mount liquid-cooled servers, seamlessly integrating with existing cold aisle systems, raised floors, and power distribution infrastructure.
  • Scalable and Customizable: Supports customized adjustments for different port quantities, interface specifications, and additional functions — adapting to different server brands and project-specific requirements.

2.3 Scope of Application

The 45kW liquid-cooled server rack is applicable to, but not limited to, the following scenarios:

  • AI artificial intelligence computing centers and large model training clusters
  • High-performance computing (HPC) centers at universities and research institutes
  • High-density computing nodes and edge data centers for internet enterprises
  • Quantitative trading computing rooms in financial and securities industries
  • Government and enterprise classified high-density data rooms (available with shielding structure options)
  • Liquid cooling technology testing and validation platforms

The product is compatible with cold plate liquid-cooled servers and supports multiple common coolant media including ethylene glycol water solutions, deionized water, mineral oil, and fluorinated fluids. It adapts to various external cooling source systems such as closed-circuit cooling towers, chillers, and dry coolers.

2.4 Design Basis and Applicable Standards

This proposal strictly adheres to relevant national and industry standards and specifications for design, primarily including:

  • GB 50174-2017 (Code for Design of Data Centers)
  • GB 50462-2016 (Code for Construction and Acceptance of Electronic Information System Room Engineering)
  • GB/T 2887-2011 (Technical Requirements for Computer Room Racks)
  • GB/T 30094-2013 (Industrial Enclosures — General Technical Requirements)
  • T/CCSA 377-2021 (Technical Specifications for Liquid-Cooled Data Centers)
  • T/CDCC 22-2022 (Technical Requirements for Data Center Liquid Cooling Systems)
  • GB 4208-2017 (Degrees of Protection Provided by Enclosures — IP Code)
  • GB/T 14976-2012 (Seamless Stainless Steel Pipes for Fluid Transport)
  • GB 50260-2013 (Code for Seismic Design of Electrical Installations)
  • GB/T 10125-2012 (Corrosion Tests in Artificial Atmospheres — Salt Spray Tests)
  • GB 4943.1-2022 (Information Technology Equipment — Safety — Part 1: General Requirements)
  • GB 50054-2011 (Code for Design of Low Voltage Electrical Installations)

—

Chapter 3: User Requirement Analysis

3.1 Basic Functional Requirements

  • Rack Mounting: Provision of standard 42U rack mounting space per 19-inch international standard, compatible with mainstream rack-mount liquid-cooled servers; supplied with sufficient rack screws and mounting accessories.
  • Cable Management: Vertical cable managers on the rear with adequate cable routing space and tie points; layered segregation of power and signal cables to prevent cable clutter from affecting heat dissipation and maintenance.
  • Physical Protection: Front and rear doors equipped with reliable mechanical locks for enclosed cabinet management ensuring equipment physical security; basic dust and foreign object protection adapted to data center operating environments.
  • Supplementary Ventilation: Perforated mesh front and rear doors with adequate ventilation rates to support cooling of residual fan-cooled server components, while enabling visual inspection of internal equipment status.
  • Equipment Load Support: Fixed shelves and sliding rails for switches, storage devices, and auxiliary equipment to accommodate diverse equipment installations within the rack.

3.2 Performance Specification Requirements

  • Cooling Performance: Maximum cold plate cooling load of 45kW per rack; with supply water temperature at 25°C and flow rate of 120L/min, outlet temperature rise shall not exceed 5°C, meeting server cooling requirements.
  • Load-Bearing Capacity: Static uniformly distributed load capacity ≥1600kg; dynamic load capacity ≥1000kg; capable of supporting a fully populated high-density liquid-cooled server load.
  • Pressure Rating: Liquid cooling system rated working pressure ≥1.6MPa; test pressure ≥2.4MPa; safety factor of 3× or greater.
  • Sealing Performance: Leakage rates for all pipeline connection points, welds, and quick couplings meeting high industry standards; no visible leakage during normal operation; drip-free coolant disconnection during quick coupling insertion/removal.
  • Environmental Adaptability: Rack operates stably in data center environments at 5°C–40°C temperature and 30%–80% relative humidity; metal components exhibit good corrosion resistance; non-metal components are flame-retardant.

3.3 Liquid Cooling System Specific Requirements

  • Manifold Configuration: Each rack houses one set of Manifold liquid distribution units comprising 2 vertical distribution columns, installed on the left and right sides of the rack rear respectively; each column features 9 distribution ports, totaling 18 liquid distribution outputs per rack, accommodating connections for 9 dual-loop liquid-cooled servers.
  • Quick Connection: Server-side distribution hoses utilize drip-free quick couplings supporting one-hand operation and rapid insertion/removal; server replacement requires no line draining, with zero coolant drip during connection/disconnection, and no impact on other servers’ normal operation.
  • Leak Protection: Rack base features a stainless steel drip pan covering the entire liquid cooling pipeline area, capturing potential condensation water or minor leakage; drip pan includes drain outlet and leak sensor mounting provisions.
  • Pipeline Integration: Supports floor-level supply/return pipeline access from beneath the rack base, or overhead routing options, adapting to different data center pipeline layouts.
  • Flow Uniformity: Flow deviation across all ports on distribution columns shall not exceed ±10%, ensuring uniform coolant distribution to every server without thermal shortfall to any unit.

3.4 Structural and Installation Requirements

  • Overall Dimensions: Rack external dimensions are 600mm width × 1400mm depth × 2200mm height, compatible with standard 600mm-wide rack data center layouts and mixed deployment alongside conventional air-cooled racks.
  • Bayed Installation: Multiple racks can be installed side-by-side with uniform seams and neat appearance; compatible with cold aisle containment systems.
  • On-Site Assembly: Racks ship fully assembled with accessories individually packaged; on-site work requires only positioning, main pipeline connection, and power wiring before commissioning — simple installation procedure with high deployment efficiency.
  • Grounding Requirements: Rack features a comprehensive grounding system; front/rear vertical rails, side panels, and doors all have reliable electrical continuity and grounding terminals, meeting data center equipotential grounding requirements.
  • Transport Adaptation: Packaged dimensions compatible with standard containers and truck transport; adequate transport protection withstands long-distance transit without damage.

3.5 Operation, Maintenance, and Management Requirements

  • Serviceability: Routine maintenance requires no special tools; consumable components quickly replaceable; front and rear doors open at wide angles for full internal access enabling convenient operator work.
  • Visual Status Indication: Pipeline connection status, valve states, and equipment operation status directly visible without disassembling structural components.
  • Fault Localization: System faults such as leakage quickly traceable to the exact point, reducing troubleshooting time; supports installation of leak detection sensors for automatic alarm integration with environment monitoring systems.
  • Scalability: Subsequent upgrades may add PDU, intelligent monitoring modules, fire suppression modules, and related accessories; supports port quantity upgrades adaptable to even higher density server deployments.
  • Complete Documentation: Delivery includes complete product manuals, operation and maintenance guides, test reports, certificates of conformity, and other technical documentation for routine management use.

—

Chapter 4: Overall Design Description

4.1 Overall Design Principles

This proposal adheres to the following core principles throughout the design process:

  • Reliability-First Principle: Stability of core data center equipment is the top priority. All designs prioritize reliability with sufficient safety margins on structural components and multiple sealing protections on the liquid cooling system, eliminating single points of failure that could impact operations.
  • Standardization and Compatibility: Strict adherence to 19-inch rack standards, pipeline interface standards, and electrical grounding standards ensures excellent compatibility with mainstream servers and data center infrastructure, reducing customer deployment and integration costs.
  • Maintenance-Friendly: Full consideration of maintenance personnel’s daily operational scenarios; optimized structural layout and connection methods reduce the number of maintenance steps, lower operating difficulty, improve maintenance efficiency, and minimize human error risk.
  • Modular Design: Core components adopt modular design — manifolds, cable managers, locks, and shelves are all independent modules individually removable and replaceable for convenient future maintenance and upgrades.
  • Safety Redundancy: Multiple protective redundancies targeted at risks such as liquid cooling leakage and structural overload — e.g., drip pan + leak detection dual protection; reinforced plate thickness + stiffening ribs dual load-bearing assurance.
  • Green and Low-Carbon: Optimized pipeline flow resistance reduces pump energy consumption; enhanced heat transfer efficiency lowers cooling source energy usage; contributes to data center PUE reduction, supporting green data center construction aligned with dual-carbon objectives.

4.2 System Architecture

The 45kW liquid-cooled server rack comprises five major subsystems working in coordination to deliver load support, heat dissipation, management, and protection for high-density liquid-cooled servers:

  • Mechanical Load Subsystem: Rack main frame, front/rear doors, side panels, and base assembly provide the physical load foundation, offering installation support and physical protection for all internal equipment and components.
  • Liquid Cooling Distribution Subsystem: Vertical distribution columns, distribution hoses, quick couplings, and drip pan form the core cooling pathway, delivering coolant transport and distribution between external cooling sources and server cold plates.
  • Mounting Accessories Subsystem: Rack rails, PDU mounting brackets, fixed shelves, sliding rails, and rack screws provide installation and fixation for servers, network equipment, and power distribution devices.
  • Cable Management Subsystem: Vertical cable managers, cable rings, and tie points organize power cables, network cabling, and signal wiring in an orderly manner.
  • Safety Protection Subsystem: Mechanical locks, grounding system, drip pan, and leak detection provisions protect against physical, electrical, and liquid cooling safety risks.

4.3 Internal Rack Layout Design

The rack depth direction is divided into three functional zones from front to rear, achieving rational segregation of cold/hot zones, pipelines, and cabling:

Front Operation Zone: Located in the front half of the rack (~800mm depth), this is the server installation area. Standard 19-inch mounting rails are positioned here with servers facing forward, enabling front access for power on/off, status viewing, and drive hot-swap operations.

Rear Pipeline Zone: Located on the left and right sides of the rack rear, each side houses one vertical distribution column spanning the full 42U height. Distribution ports face inward for convenient connection to server rear liquid cooling interfaces. The pipeline zone and server area reserve sufficient operating space for hose connection and maintenance.

Center Cable Management Zone: Located at the rear center position, vertical cable managers route server power cables, network cables, and wiring — achieving physical separation of cabling from liquid cooling pipelines to prevent entanglement and facilitate independent maintenance.

The rack base accommodates the drip pan installation, fully covering the rear pipeline zone to catch potential drips. The rack top is pre-drilled for pipeline and cable routing to support overhead utility access.

4.4 Liquid Cooling Pipeline Topology

The rack liquid cooling system adopts a “dual vertical column parallel” topology, designed as follows:

Main Loop: Coolant supplied by the external cooling source enters the left distribution column (supply riser) from the bottom left of the rack. Through individual branch lines, coolant flows into server cold plates. The heat-absorbed coolant exits servers into the right distribution column (return riser) and exits from the bottom right back to the external cooling source, completing the full circulation loop.

Distribution Branches: Each distribution column vertically positions 9 distribution ports corresponding to servers at different U positions. Each port connects one distribution hose to the corresponding server interface. All branches are connected in parallel, ensuring consistent supply water temperature at each server.

Flow Balancing: Distribution column main pipe diameters are significantly larger than branch pipe diameters, incorporating tapered flow channel designs. This ensures uniform flow across ports at different heights, with flow deviation controlled within ±10%, preventing thermal shortfall for upper or lower servers.

Venting and Pressure Measurement: Both distribution columns include vent valve ports and pressure test ports at the top for air evacuation during system charging and for operational pressure monitoring, facilitating routine maintenance and fault diagnosis.

Valve Configuration: Optional shutoff valves on main supply and return ports enable individual rack isolation for maintenance without interrupting cluster operation.

4.5 Safety Redundancy and Reliability Design

  • Structural Strength Redundancy: Main vertical rails use 2.0mm cold-rolled steel plate roll-formed construction, 0.5mm thicker than standard racks; load-bearing beams employ stiffening rib reinforcement with static load capacity rated at 30%+ margin, preventing structural deformation under prolonged full-load conditions.
  • Pipeline Pressure Redundancy: Liquid cooling system rated working pressure of 1.6MPa with design burst pressure of ≥4.8MPa (3× safety factor); all welds undergo 2.4MPa hydrostatic pressure hold testing with zero leakage.
  • Sealing Redundancy: Pipeline connections employ dual-sealing “welding + thread seal” structure; quick couplings feature bidirectional self-sealing with both ends closing simultaneously upon connection/disconnection — even accidental coupling separation does not cause significant leakage.
  • Leak Protection Redundancy: Triple protection system of “drip-free couplings + bottom drip pan + leak detection alarm”: normal insertion/removal is drip-free, minor leakage is captured by the drip pan, and environmental monitoring alarms trigger immediately upon reaching alert thresholds — comprehensive multi-dimensional leak risk prevention.
  • Electrical Safety Redundancy: Rack overall grounding resistance ≤0.1Ω with equipotential bonding across all metal components; mounting brackets are insulated to prevent potential differences between different devices.

—

Chapter 5: Quotation and Configuration List

5.1 Standard Configuration per Rack

No. Component Specification Unit Qty Remarks
—– ———– ————— —— —– ———
1 Rack Main Frame 42U, 600×1400×2200mm, high-quality cold-rolled steel, electrostatic powder coating, static load ≥1600kg Set 1 Includes front/rear mounting rails, base, top cover
2 Single-door Perforated Front Door 600×2200mm, hex mesh perforation, ventilation rate ≥70%, cold-rolled steel frame Leaf 1 With recessed handle and hinges
3 Double-door Perforated Rear Door 1400×2200mm, split double doors, hex mesh perforation, ventilation rate ≥70% Set 1 Includes two leaves, hinges and handles
4 Mechanical Lock Set Dedicated anti-theft rack locks, common key, anti-pry latch Set 2 1 for front door, 1 linked for rear
5 Rear Vertical Cable Manager Full 42U height, flame-retardant ABS + metal bracket, layered cable rings Pcs 2 Left and right, one each
6 Rear Rail PDU Bracket Compatible with 19-inch rails, cold-rolled steel, powder coated Set 2 For vertical PDU mounting
7 Rear Column VCDU/PDU Bracket Heavy-gauge steel plate, load ≥50kg per set Set 2 For liquid distribution units and PDU
8 Rack Mounting Screw Kit M6 standard, screws, nuts, flat & spring washers, carbon steel color zinc plated Set 40 For equipment mounting
9 Rack-Mount Fixed Shelf 19-inch standard, depth matched to 1400mm rack, load ≥50kg Pc 1 For auxiliary equipment
10 Server Sliding Rails 19-inch three-section ball-bearing rails, full extension, load ≥30kg/pair Pair 2 For drawer-style equipment
11 Manifold Distribution Column 304 stainless steel, vertical mount, 9 distribution ports per column, rated 1.6MPa Pcs 2 One supply, one return, left & right
12 Server Distribution Hose Coolant-resistant rubber + braided reinforcement, length 1.5m, rated 1.6MPa Pcs 18 One per port
13 Drip-Free Quick Couplings 304 stainless steel body, FKM seals, bidirectional self-sealing, drip-free insertion/removal Set 18 Each set includes male and female ends
14 Stainless Steel Drip Pan 304 stainless steel, one-piece deep drawn, matches rack base, with drain outlet Pc 1 Installed at rack bottom
15 Complete Packaging Materials Honeycomb cardboard box + EPE foam edge protectors + strapping bands, moisture and dust resistant Set 1 Includes packaging for all accessories

5.2 Optional Value-Added Accessories

No. Accessory Specification Unit Qty Remarks
—– ———– ————— —— —– ———
1 Intelligent Leak Detection Sensor Location-based leak detection cable, with controller, supports environment monitoring alarm Set 1 Installed in drip pan
2 Rack-Mount Intelligent PDU 16A/32A, 8/12 outlets, current & voltage monitoring, remote management Pcs 2 Configurable power and outlet count
3 Rack Temp/Humidity Sensor High-precision digital display, RS485 communication, environment monitoring integration Pcs 2 1 front, 1 rear
4 Baying Connection Kit Cold-rolled steel, zinc plated, for rack side-by-side joining Set 4 4 sets per rack bayed
5 Removable Side Panels Cold-rolled steel, powder coated, color-matched to rack Pcs 2 Left and right
6 Main Line Shutoff Valves 304 stainless steel, threaded connection, 1.6MPa Pcs 2 Supply and return ports
7 Flow Sensors Electronic flow meter, monitors main line flow, data upload capable Pcs 2 Supply and return
8 Extended Distribution Hoses Length options 2m/3m, same standard hose material Pcs As needed For special installation distances

5.3 Bulk Project Quotation Notes

  • The above pricing is for single-unit standard configuration reference; bulk procurement qualifies for tiered volume discounts. Final pricing subject to official quotation.
  • Optional accessories may be added or removed per project requirements, with corresponding price adjustments.
  • Quotation includes production, testing, and packaging costs; excludes transportation, on-site installation, and taxes — these may be separately quoted as required.
  • Non-standard customized products are quoted individually based on customization complexity and material costs.
  • Integrated liquid-cooled data room turnkey projects (including cooling sources, pipelines, monitoring, construction, etc.) are available as package quotations.

—

Chapter 6: Technical Parameters of System Products

6.1 Rack Main Frame System

Parameter Specification
———– —————
Rack Standard 19-inch international standard, EIA-310-E compliant
Mounting Space 42U
External Dimensions (W×D×H) 600×1400×2200mm
Main Column Material High-quality cold-rolled steel plate, 2.0mm thickness, roll-formed
Frame Structure Welded frame, four-column load-bearing structure
Surface Treatment Environmental electrostatic powder coating, scratch-resistant
Coating Thickness 60–120μm
Color Black (RAL 9004) standard; custom colors available
Static Load Capacity ≥1600kg uniformly distributed
Dynamic Load Capacity ≥1000kg
Front/Rear Mounting Rails Galvanized steel, 2.0mm thickness, U-channel profile, height adjustable
Mounting Thread Specification M6 threaded, square hole design compatible with cage nuts
Grounding Resistance ≤0.1Ω
Protection Rating IP20 (IP54 for optional sealing kit)
Operating Temperature −5°C to +55°C
Storage Temperature −20°C to +70°C
Relative Humidity 30%–80% (non-condensing)
Product Standards Compliance GB/T 2887-2011, GB/T 30094-2013, GB 50174-2017

6.2 Door and Locking System

Parameter Specification
———– —————
Front Door Type Single-leaf, perforated mesh, flush mounted
Front Door Dimensions 600×2200mm
Front Door Ventilation Rate ≥70% (hexagonal mesh, 2.0mm openings)
Rear Door Type Double-leaf, split opening, perforated mesh
Rear Door Dimensions 1400×2200mm (total)
Rear Door Ventilation Rate ≥70%
Door Frame Material Cold-rolled steel plate, 1.5mm thickness
Door Panel Material Cold-rolled steel plate, 1.2mm thickness (perforated area)
Door Opening Angle Front ≥110°, Rear ≥170°
Hinge Type Heavy-duty industrial hinges, removable design
Handle Type Recessed handle, spring-loaded
Lock Type Dedicated anti-theft lock with key locking
Lock Features Anti-pry latch, tamper-resistant
Key System Common key (same key for all doors); different key option available
Surface Treatment Electrostatic powder coating, color-matched to frame
Optional Protective Features Tempered glass front door (for visual inspection); mesh door with air filter

6.3 Internal Mounting and Cable Management System

Parameter Specification
———– —————
Mounting Rail Profile U-channel, 19-inch standard width (482.6mm)
Mounting Rail Thickness 2.0mm, galvanized steel
U-position Precision ±0.4mm
Square Hole Specification 9.5×9.5mm, M6 compatible
Cage Nut Type M6 carbon steel, color zinc plated (45# steel)
Screw Specification M6×16mm, flange head
Thread Form Metric standard, fine pitch
Adjustable Depth Range 25mm
Fixed Shelf Load Rating ≥50kg uniformly distributed
Sliding Rail Load Rating ≥30kg per pair, full extension
Sliding Rail Type Three-section ball-bearing slides
Vertical Cable Manager Dimensions 80×50mm cross-section, full 42U height
Cable Manager Structure Flame-retardant ABS brackets + metal support rails
Cable Tie Points ≥1 per 1U per side
Cable Ring Material Flame-retardant engineering plastic, cold-resistant ≥ −30°C
PDU Mounting Position Rear vertical rails, front and rear configurations supported
PDU Bracket Load ≥50kg
Grounding Points Front door, rear door, side panels, base — dedicated grounding terminals

6.4 Manifold Liquid Distribution System

Parameter Specification
———– —————
Manifold Type Vertical single-column distribution, supply and return paired
Manifold Quantity per Rack 2 columns (1 supply + 1 return)
Distribution Ports per Column 9 ports
Total Distribution Ports per Rack 18 ports
Port Spacing 2U interval (88.9mm center-to-center)
Port Type Threaded connection, G3/8″ or G1/2″ standard (selectable)
Main Pipe Diameter DN32 (option: DN40)
Branch Pipe Diameter DN10–DN12
Manifold Material 304 stainless steel
Sealing Material FKM (fluororubber) — ethylene propylene (EPDM) option
Rated Working Pressure 1.6MPa
Test Pressure 2.4MPa
Burst Pressure ≥4.8MPa
Connection Type Welded (main structure) + threaded (branch connections)
Flow Uniformity Port-to-port deviation ≤±10%
Supply Water Temperature Range 15°C–35°C (recommended 18°C–30°C)
Recommended Flow Rate 120L/min at 45kW heat load
Max Flow Rate 160L/min
Compatible Coolants Ethylene glycol water solution (≤35%), deionized water, mineral oil, fluorinated fluids
Pipe Material 304 stainless steel seamless
Pressure Test Standard 100% factory hydrostatic test at 2.4MPa
Exterior Finish Brushed or sanitary polished, oxidation-resistant
Vent/Pressure Ports Top-mounted, both columns

6.5 Packaging and Transport Materials

Parameter Specification
———– —————
Packaging Type Full-enclosure honeycomb paper carton
Carton Dimensions 660×1460×2260mm (internal)
Edge Protection EPE expanded polyethylene foam corner guards, 50mm thickness
Corner Guard Specification 20×20×20cm right-angle brackets, density ≥25kg/m³
Anti-Moisture PE moisture barrier film, double-layer
Strapping PET plastic strapping bands, 16mm width
Strapping Quantity 4 bands (2 longitudinal + 2 transverse)
Identification Marks Warning labels: fragile, upright, stacking limit
Loading Support Palletized base, GIG standard pallet (1200×1000mm) or custom
Transport Vibration Resistance 3G vibration testing, 500km simulated road transport
Stacking Capacity 3 racks high (empty cabinet packaging)
Container Compatibility Standard 20ft/40ft containers — 6 racks per 20ft (estimate)
Protection Standard Meet ISTA 3E international transport testing requirements
Waterproof Protection Full polyethylene film wrapping, moisture-absorbing desiccant added

—

Chapter 7: Core Advantages of the Solution

7.1 High-Density Heat Dissipation Capability

The 45kW liquid-cooled server rack delivers a 3×+ cooling capacity advantage over traditional air-cooled racks (which typically cap at ~15-20kW). Leveraging the high specific heat capacity of liquid coolant, the system efficiently removes heat from server CPU/GPU cold plates, maintaining chip temperatures within optimal operating ranges even during sustained full-load operation. The dual-column Manifold design with precision flow balancing ensures every server in the rack receives uniform coolant distribution — eliminating the localized hot spots that plague air-cooled environments and enabling data centers to maximize compute density per square meter of floor space.

7.2 Structural Mechanical Reliability

The rack frame is engineered with 2.0mm cold-rolled steel — 0.5mm thicker than industry-standard racks — delivering a static load capacity of ≥1600kg with 30%+ safety margin. Full welding at all frame joints provides superior rigidity and dimensional stability over the operational lifetime. Every rack undergoes rigorous factory testing including load validation, dimensional accuracy inspection, and grounding continuity checks — ensuring structural performance that stands up to the demands of high-density, mission-critical deployments.

7.3 Liquid Cooling System Safety

Safety is engineered into every aspect of the liquid cooling pathway. All wetted components utilize 304 stainless steel and FKM sealing materials with dual-sealing connection structures, rated at 1.6MPa working pressure with a 3× burst safety factor. The triple-layer leak protection system — drip-free quick couplings, stainless steel drip pan, and leak detection alarm provisions — provides comprehensive defense against cooling system failures. Every manifold undergoes 100% factory hydrostatic pressure testing at 2.4MPa, guaranteeing leak-free performance from day one.

7.4 Operational Maintenance Convenience

Designed with maintainers in mind, the rack features tool-free access to all serviceable components. Front and rear doors open at wide angles (≥110° front, ≥170° rear) providing full internal access. The quick-coupling system enables server hot-swap in under 60 seconds without draining pipelines or affecting neighboring servers. Standardized modular components — manifolds, cable managers, brackets — are individually replaceable without specialized tools, dramatically reducing mean time to repair (MTTR) and total cost of ownership.

7.5 Customization and Adaptation Capability

As a manufacturer with in-house R&D and production, we support deep customization to match specific project requirements. Whether adjusting port configurations, interface specifications, rack dimensions, color schemes, or integrating additional features (shielding, specialized cooling, intelligent monitoring), our team delivers tailored solutions efficiently. Custom non-standard rack and liquid cooling configurations are developed through our dedicated engineering team, with three design proposals provided free of charge for evaluation.

7.6 Green and Low-Carbon Energy Efficiency

The 45kW liquid-cooled rack contributes to data center sustainability goals on multiple fronts. The efficient liquid cooling pathway eliminates the need for high-power cooling fans within the rack, reducing server auxiliary energy consumption by up to 40%. Optimized pipeline flow resistance minimizes pump energy requirements at the CDU level. By enabling higher per-rack compute density, the solution reduces facility footprint requirements per kW of IT load, contributing to significant PUE reductions — supporting data center operators in meeting carbon neutrality and sustainability compliance requirements.

—

Chapter 8: Technical Q&A

8.1 Basic Rack Knowledge

Q1: What is the load capacity of this rack?

A: The rack has a static uniformly distributed load capacity of ≥1600kg and a dynamic load capacity of ≥1000kg, supporting fully populated high-density liquid-cooled server configurations.

Q2: Is this rack compatible with standard 19-inch servers?

A: Yes, the rack fully complies with the 19-inch international standard (EIA-310-E), compatible with all mainstream rack-mount servers, switches, and storage devices.

Q3: What is the frame material and surface treatment?

A: The frame is manufactured from high-quality cold-rolled steel with 2.0mm main column thickness, finished with environmental electrostatic powder coating providing excellent corrosion and scratch resistance.

Q4: Can the rack be customized?

A: Yes, we support extensive customization including dimensions, colors, port configurations, additional functions (shielding, monitoring, specialized accessories), and branding options.

8.2 Liquid Cooling System Technical Questions

Q1: What cooling capacity does each rack support?

A: Each rack supports a maximum cooling load of 45kW cold plate heat dissipation. Recommended conditions: supply water temperature 25°C, flow rate 120L/min, temperature rise ≤5°C.

Q2: What is the working pressure rating?

A: The rated working pressure is 1.6MPa with a test pressure of 2.4MPa and a burst pressure of ≥4.8MPa, providing a 3× safety factor.

Q3: What coolants are compatible?

A: Compatible coolants include ethylene glycol water solutions (up to 35% concentration), deionized water, mineral oil, and fluorinated fluids.

Q4: How is flow uniformity ensured across different U positions?

A: The manifold uses larger main pipe diameters relative to branch lines with tapered internal flow channels, ensuring flow deviation of ±10% or less across all 18 ports.

Q5: What happens if a quick coupling is disconnected?

A: The quick couplings feature bidirectional self-sealing design — both male and female sides seal simultaneously upon disconnection, preventing coolant leakage and enabling tool-free server maintenance without draining.

Q6: Can this rack work with different external cooling sources?

A: Yes, the rack is compatible with various external cooling sources including closed-circuit cooling towers, chillers, dry coolers, and CDUs.

8.3 Installation and Construction Questions

Q1: How long does installation take?

A: Racks ship fully assembled. On-site installation requires positioning, connecting main supply/return pipelines, and power wiring — typically completed within 4 hours per rack by qualified technicians.

Q2: Does installation require special tools?

A: No, standard tools are sufficient for rack installation. All liquid cooling connections use threaded fittings with standard wrenches.

Q3: Can racks be installed adjacent to air-cooled racks?

A: Yes, the 600mm width standard dimension enables mixed deployment alongside conventional air-cooled racks within the same row.

Q4: Can this rack support overhead pipeline routing?

A: Yes, the rack top includes pre-configured openings for pipeline and cable routing, supporting both floor-level and overhead pipeline installation modes.

8.4 Operation and Maintenance Questions

Q1: What routine maintenance is required?

A: Routine maintenance includes visual inspection of pipeline connections for leakage, checking manifold pressure readings, and verifying coolant quality parameters. Recommended inspection frequency: monthly.

Q2: How is server hot-swap performed?

A: Disconnect the supply and return hoses via quick couplings (automatic sealing), slide the server out on rails, perform replacement, reconnect hoses — the procedure takes approximately one minute.

Q3: What leak protection measures are in place?

A: The rack features triple protection: drip-free quick couplings for connection safety, a stainless steel drip pan under all pipeline areas, and provisions for leak detection sensors that integrate with environment monitoring systems.

Q4: Is remote monitoring supported?

A: Yes, optional sensors including leak detection, temperature/humidity, and flow monitoring can be integrated with standard environment monitoring systems (DCIM) via RS485/BACnet/Modbus protocols.

8.5 Selection and Customization Questions

Q1: How many servers can each rack accommodate?

A: Each rack accommodates up to 9 dual-loop liquid-cooled servers (18 server liquid cooling connections) with 42U of 19-inch mounting space for servers and networking equipment.

Q2: What port configurations are available?

A: Standard configuration offers 18 distribution ports (9 supply + 9 return). Alternative configurations with different port quantities and interface specifications (G1/4″, G3/8″, G1/2″) are available.

Q3: Can the rack be adapted for higher power densities?

A: Yes, KITOZER offers liquid-cooled rack solutions spanning 30kW, 45kW, 60kW, and 80kW configurations for varying density requirements. Please contact our engineering team for specific requirements.

Q4: What is the ordering lead time?

A: Standard configuration: 15–20 working days. Custom configurations: 25–35 working days depending on complexity. Bulk orders may be expedited based on production capacity.

—

Chapter 9: Construction Schedule

9.1 Overall Project Cycle

The typical project implementation period for 45kW liquid-cooled rack deployment is 30–45 calendar days from order confirmation to site acceptance, broken down as follows:

Phase Duration Description
——- ———- ————-
Pre-Production Preparation 3–5 days Design confirmation, drawing review, production planning
Manufacturing & Testing 15–20 days Production, quality inspection, factory testing
Logistics & Delivery 5–10 days Packaging, transport arrangement, site delivery
On-Site Installation & Commissioning 5–8 days Positioning, pipeline connection, system commissioning
Acceptance & Handover 2–3 days Joint inspection, documentation handover, training

Note: Timeline may vary based on project size, site conditions, and customization requirements.

9.2 Work Content and Timeline by Phase

Phase 1: Pre-Production (Days 1–5)

  • Final design confirmation and technical clarification
  • Approval of shop drawings and production documentation
  • Production scheduling and material procurement
  • Quality control plan development

Phase 2: Manufacturing (Days 6–25)

  • Sheet metal fabrication: cutting, bending, welding
  • Surface treatment: degreasing, phosphating, powder coating
  • Assembly: frame assembly, door installation, attachment fitting
  • Liquid cooling manifold fabrication and testing
  • Full-function factory testing per quality standards

Phase 3: Logistics (Days 26–35)

  • Protective packaging per transport standards
  • Loading and transport arrangement
  • Site delivery and incoming inspection
  • Damage inspection verification

Phase 4: Installation & Commissioning (Days 36–43)

  • Rack positioning and alignment
  • Leveling and anchoring
  • Main supply/return pipeline connection
  • System flushing and air evacuation
  • Pressure testing and leak inspection
  • Cooling circulation testing and flow verification

Phase 5: Acceptance (Days 44–46)

  • Joint inspection with client team
  • Full-function performance validation
  • Documentation handover
  • On-site training session
  • Sign-off and project completion

9.3 Key Milestone Control and Deliverables

Milestone Confirmation Method Deliverables
———– ——————— ————–
Design Confirmation Customer approval signature Shop drawings, technical specifications
Material Inspection Incoming Q.C. records Material certifications, test reports
Production Completion Factory acceptance inspection Factory test reports, inspection records
Pre-Shipment Inspection Joint or remote inspection available Complete inspection reports, photo records
Site Delivery Delivery receipt verification Delivery notes, packing lists
Installation Completion On-site commissioning Commissioning reports, test data
System Acceptance Joint acceptance inspection Acceptance certificates, complete documentation package
Project Handover Final coordination meeting Warranty certificates, operation manuals, training records

—

Chapter 10: Construction Organization Plan

10.1 Project Organizational Structure

A dedicated project team is established for each project, structured as:

  • Project Director: Overall project leadership, resource allocation, client interface
  • Project Manager: Day-to-day project execution, schedule control, quality assurance
  • Design Engineer: Technical drawing, design modifications, technical support
  • Quality Inspector: Quality control process management, inspections and testing
  • Installation Team Leader: On-site installation management, technician coordination
  • Commissioning Engineer: System testing, adjustment, and optimization
  • Safety Officer: Safety compliance, hazard identification, safety training
  • Logistics Coordinator: Transport arrangement, on-site delivery, storage management

10.2 Core Personnel Configuration and Responsibilities

Position Qualification Key Responsibilities
———- ————— ———————-
Project Manager 10+ years in data center infrastructure projects Schedule management, coordination, quality assurance, client reporting
Senior Design Engineer 8+ years, mechanical/fluid engineering background Technical design review, customization drawings, system optimization
Manufacturing Supervisor 10+ years in sheet metal fabrication Production quality, delivery timelines, manufacturing process control
Q.C. Inspector 5+ years, certified quality inspector In-process inspection, final inspection, test documentation
Installation Lead 8+ years, certified installer On-site installation management, installation quality verification
Commissioning Engineer 5+ years, liquid cooling system specialist System charging, testing, performance validation, troubleshooting
Safety Officer Certified safety management professional Site safety compliance, hazard assessment, incident prevention

10.3 On-Site Construction Standard Procedure

  1. Pre-Arrival Site Survey: Confirm site conditions, access routes, equipment hoisting requirements, and utility connection points
  2. Equipment Arrival Inspection: Joint inspection of packaging integrity, item-by-item verification against packing lists, damage documentation
  3. Site Safety Induction: Safety briefing for all installation personnel, site safety rules, and hazard identification
  4. Positioning and Layout: Final positioning per floor plan, alignment and leveling verification
  5. Mechanical Installation: Rack positioning, baying connections, anchoring per seismic requirements
  6. Pipeline Connection: Main supply/return pipeline connection, torque verification, connection inspection
  7. Electrical Connection: Power wiring, grounding system installation, electrical safety verification
  8. System Flushing: Pipeline cleaning, air evacuation, system charging with coolant
  9. Pressure Testing: Hydrostatic pressure test at specified test pressure, leak inspection of all connection points
  10. System Commissioning: Flow rate verification, temperature performance testing, system parameter adjustment
  11. Performance Validation: Full-load cooling capacity verification, flow uniformity measurement
  12. Site Cleanup and Handover: Site cleanup, waste removal, documentation handover to client

10.4 Full-Process Quality Control System

  • Incoming Materials: All raw materials enter with certification inspection; incoming Q.C. records maintained for full traceability
  • Manufacturing Process: “Three-inspection” system (self, mutual, dedicated inspections) at each production stage
  • Pre-Delivery Testing: 100% factory testing including dimensional inspection, pressure testing, sealing verification, load testing, and grounding continuity
  • One-Product-One-Certificate: Every product carries unique traceability code linking to complete quality records
  • On-Site Verification: Installation quality verified against acceptance checklist; joint commissioning tests with client representatives
  • Defect Management: Non-conformance reporting and corrective action procedures; zero-defect delivery objective
  • Documentation Control: Complete quality documentation package delivered with each project

10.5 Safety Production Management

  • Safety Policy: Compliance with all applicable occupational health and safety regulations
  • Protective Equipment: Mandatory personal protective equipment (PPE) for all site personnel
  • Electrical Safety: Lockout/tagout procedures for all electrical work; GFCI protection for power tools
  • Lifting Operations: Certified rigging equipment and operators for heavy equipment movement
  • Hazard Communication: Material Safety Data Sheets (MSDS) for all coolants and chemicals; proper handling training
  • Emergency Response: Site-specific emergency response plan; first-aid trained personnel on site
  • Incident Reporting: Mandatory incident reporting with corrective action implementation
  • Safety Training: Pre-work safety orientation; task-specific safety briefings

10.6 Civilized Construction and Site Management Requirements

  • Site Appearance: Clean, organized work areas; equipment and materials stored in designated zones
  • Environmental Protection: Dust control measures; containment for any coolant spillage; proper waste disposal
  • Noise Control: Low-noise equipment selection; noisy operations scheduled within permitted hours
  • Site Access Control: Authorized personnel only; visitor sign-in procedures
  • Daily Housekeeping: End-of-day site cleanup; daily waste removal
  • Neighbor Considerations: Coordination with facility management on operational scheduling to minimize disruption

—

Chapter 11: After-Sales Service System

11.1 Warranty Service Commitment

  • Standard Warranty: 24 months from the date of installation acceptance
  • Warranty Coverage: All manufacturing defects in materials and workmanship
  • Extended Warranty: Additional 12-month extension available for purchase (36 months total)
  • Lifetime Support: Lifetime technical support and spare parts availability commitment
  • Response Commitment: Service response guaranteed within specified timelines from fault notification
  • Product Liability: Indemnification for direct damages caused by product manufacturing defects during warranty period

11.2 Multi-Level Fault Response Mechanism

Fault Level Definition Response Time On-Site Arrival
————- ———— ————— —————–
Level 1 — Critical Complete system outage, cooling interruption affecting production ≤30 minutes remote response Within 24 hours
Level 2 — Major Significant performance degradation, single rack failure ≤2 hours remote response Within 48 hours
Level 3 — General Minor fault, non-critical component failure, performance slightly below spec ≤4 hours remote response Within 72 hours
Level 4 — Consultative Technical consultation, preventive maintenance guidance ≤8 hours remote response By appointment

Response times apply to regions within 500km of Guangzhou; remote areas subject to transportation logistics and will be coordinated with the customer.

11.3 On-Site Service Operation Standards

  1. Service Scheduling: We coordinate a service time window with the customer; arrival confirmed 24 hours in advance
  2. Arrival Protocol: Technician arrives in uniform with identification; completes check-in procedures at customer site
  3. Fault Diagnosis: Systematic fault identification with customer’s operations team participation
  4. Service Execution: Repair or replacement procedures performed per service standards
  5. Testing & Verification: Post-service functional testing to confirm resolution
  6. Documentation: Service report provided — including fault description, root cause analysis, actions taken, and recommendations
  7. Customer Sign-off: Service completion confirmed by customer representative before departure

11.4 Spare Parts Supply Guarantee

  • Spare Parts Inventory: Critical components — manifolds, quick couplings, hoses, drip pans — maintained in permanent stock
  • Stock Availability: Same-day dispatch for in-stock parts (working days)
  • Long-Term Availability: Spare parts guaranteed for minimum 10 years after product discontinuation
  • Exchange Service: Swap-out service for major components — replacement shipped before defective unit returns (advanced exchange)
  • Overseas Customers: A minimum 2% spare parts ratio recommended for purchased equipment; wholesale supply of consumables available

11.5 Lifetime Value-Added Services

  • Product Upgrades: Technical solution suggestions and implementation for performance or feature upgrades
  • Software Updates: Free updates for associated monitoring and management software
  • Periodic Inspections: Free remote technical inspection of product performance parameters at agreed intervals
  • Technical Consultation: Lifetime access to our engineering team for system optimization and expansion planning
  • Training Updates: Periodic operation and maintenance training sessions for refresher or personnel changes
  • Engineering Support: Dedicated support, including online remote video service and email consultation service

—

Chapter 12: Training Plan

12.1 Training Objectives and Audience

Training Objectives:

  • Enable participants to fully understand the 45kW liquid-cooled server rack product structure and working principles
  • Develop operator proficiency in daily equipment operations, inspection, and maintenance procedures
  • Establish troubleshooting skills for common faults and emergency response handling capabilities
  • Ensure a safe and efficient working environment for liquid cooling system operations

Target Audience:

Category Training Focus Prerequisites
———- ————— —————
Facility Operations Staff Basic operations, daily inspection, routine maintenance Familiar with data center equipment basics
Maintenance Technicians Advanced maintenance, fault diagnosis, component replacement 2+ years hands-on data center experience
Engineering/Management Staff System design principles, capacity planning, expansion strategy Data center infrastructure knowledge
Safety/Compliance Officers Safety procedures, coolant handling, emergency response Safety management awareness

12.2 Tiered Training Content System

Level 1 — Basic Training (4 hours):

  • Product introduction and system architecture overview
  • Equipment nomenclature and component identification
  • Daily inspection procedures and checklists
  • Safety basics for liquid cooling environments
  • Basic operations: door opening, server access, visual inspections

Level 2 — Technical Training (8 hours):

  • Liquid cooling system principles and fluid dynamics basics
  • Manifold system operation and flow management
  • Server connection/disconnection procedures with quick couplings
  • System pressure management and monitoring
  • Common fault identification, diagnosis, and troubleshooting
  • Coolant quality management and replacement procedures

Level 3 — Advanced Engineering Training (12 hours):

  • Full system design principles and performance calculations
  • Capacity planning and system expansion methodology
  • Integration with CDU systems and external cooling sources
  • Troubleshooting complex multi-system failures
  • System optimization and efficiency enhancement techniques
  • Emergency response planning and execution

12.3 Diversified Training Methods and Arrangements

Training Method Description Duration Suitable for
—————- ————- ———- ————–
Classroom Instruction Structured theory sessions with visual aids As scheduled All levels
Hands-On Workshop Practical equipment operation exercises at our facility 1–2 days Level 1–2
On-Site Training Training conducted at customer installation site Per project Level 1–2
Remote Webinar Online interactive sessions via video conferencing 2 hours/session All levels
Video Tutorials Self-paced instructional videos On demand Level 1–2
Documentation Comprehensive written manuals and quick reference cards Self-study All levels

Training Schedule: Training can be delivered prior to system acceptance, during commissioning, or at scheduled intervals post-delivery. On-site training during project commissioning is included with every project.

12.4 Training Assessment and Acceptance Criteria

Training Level Assessment Method Passing Criteria
—————- ——————- ——————
Level 1 — Basic Multiple-choice written test ≥80% score
Level 2 — Technical Written test + practical operation assessment ≥80% written + successful practical demonstration
Level 3 — Advanced Technical presentation + troubleshooting exercise ≥85% written + demonstrated fault resolution

All passing participants receive a KITOZER Certified Operator Certificate.

Failed participants may retake the assessment once at no charge.

12.5 Training Documentation Deliverables

Item Description Format Quantity
—— ————- ——– ———-
Product Manual Complete product description and technical parameters Printed + PDF 2 sets
Operation Guide Step-by-step daily operating procedures Printed + PDF 2 sets
Maintenance Manual Preventive maintenance schedules and procedures Printed + PDF 2 sets
Troubleshooting Guide Common faults, diagnosis, and resolution Printed + PDF 2 sets
Training Presentation Full training slide deck from sessions Digital 1 set
Training Videos Demonstrations of key operational procedures Digital 1 set
Quick Reference Card Laminated summary of key operating parameters Printed 5 cards
Safety Manual Safety procedures and coolant handling guide Printed + PDF 2 sets

—

Chapter 13: Project Case Studies

13.1 Leading AI Computing Center Liquid-Cooled Rack Cluster

Project Overview: Supply and installation of high-density liquid-cooled rack infrastructure for a major AI computing center in China supporting large language model training workloads.

Scale: 96 units of 45kW liquid-cooled racks (KITOZER-LC-45kW-42U)

Deployment: 4 rows × 24 racks, integrated with cold aisle containment and CDU cooling infrastructure

Project Features:

  • Full high-density GPU server deployment — AI training clusters
  • Sustained full-load operation with 96 racks × 45kW continuous heat dissipation
  • Integration with chilled water cooling system and closed-circuit cooling towers
  • Intelligent environment monitoring with centralized management platform

Key Outcomes:

  • PUE ≤ 1.15 achieved at full load
  • Server inlet temperatures maintained within ±1°C across all racks
  • Zero leakage incidents since commissioning
  • Deployment completed 15 days ahead of schedule

13.2 Prestigious University HPC Center High-Density Liquid-Cooled Data Room

Project Overview: High-performance computing center expansion at “Project 985” university, accommodating next-generation HPC servers for scientific research applications.

Scale: 32 units of 45kW liquid-cooled racks + 8 units of 60kW liquid-cooled racks

Deployment: Mixed-density deployment with micro-module cold aisle containment

Project Features:

  • HPC cluster supporting weather simulation, life sciences, and materials research
  • Integration with existing facility cooling infrastructure via CDU systems
  • Seismic-engineered mounting per GB 50260-2013 requirements
  • Comprehensive monitoring integrated with existing building management system

Key Outcomes:

  • Research computing capacity increased 3.2× within existing facility footprint
  • Equipment noise levels reduced by approximately 20dB vs. air-cooled configuration
  • Faculty and student researchers trained on system operation through hands-on sessions
  • Zero liquid cooling safety incidents over two years of operation

13.3 Major Internet Enterprise Edge Data Center

Project Overview: Edge data center deployment for a leading Chinese internet company, supporting high-density edge computing workloads in metropolitan nodes.

Scale: 24 units of 45kW liquid-cooled racks per site × 5 sites

Deployment: Distributed edge nodes across multiple cities

Project Features:

  • High-density edge computing nodes — AI inference and content delivery
  • Rapid deployment capability: complete site installation in 10 days per location
  • Remote monitoring and management integration with centralized operations platform
  • Containerized cooling infrastructure for decentralized deployment

Key Outcomes:

  • Edge inference latency reduced by 40% vs. centralized architecture
  • Standardized deployment model enables repeatable rapid expansion
  • Remote operation achieved with minimal on-site staffing requirements
  • Cross-site consistency in cooling performance and operational parameters

13.4 National Research Institute Liquid Cooling Test Platform

Project Overview: Dedicated liquid cooling test platform for a national research institute, providing controlled environment for liquid cooling technology validation and evaluation.

Scale: 10 units of 45kW liquid-cooled racks with flexible test instrumentation

Deployment: Modular test configuration with quick-reconfiguration capability

Project Features:

  • Multiple coolant media testing capability: ethylene glycol solutions, deionized water, fluorinated fluids
  • Precision instrumentation for flow, temperature, and pressure measurement
  • Configurable manifold system supporting various server cold plate layouts
  • Data acquisition integration for research analysis

Key Outcomes:

  • Successfully validated multiple liquid cooling technology approaches
  • Completed server cold plate performance benchmarking for next-gen processors
  • Detailed flow distribution and thermal performance data published in research papers
  • Platform continues to serve as national-level liquid cooling certification test facility

—

Chapter 14: Search Keywords and SEO Optimization Tags

14.1 Full-Category Search Keyword Matrix

Product Core Keywords:

  • Liquid-cooled server rack
  • 45kW liquid cooling rack
  • High-density server cabinet
  • Cold plate liquid cooling
  • Data center liquid cooling system

Application Keywords:

  • AI data center cooling
  • HPC liquid cooling solution
  • GPU server rack cooling
  • High-performance computing cabinet
  • Liquid-cooled data center infrastructure

Solution Keywords:

  • Turnkey liquid cooling data center
  • CDU coolant distribution system
  • Manifold liquid distribution rack
  • Containerized liquid cooling solution
  • Custom liquid cooling rack manufacturer

Trade Keywords:

  • Server rack manufacturer China
  • Liquid cooling rack project-confirmed
  • Data center cooling equipment supplier
  • Rack OEM ODM manufacturer
  • Infrastructure export supplier

Full-Text Keywords:

  • 42U liquid cooling cabinet
  • Rack with drip-free quick coupling
  • 1.6MPa cooling rack manifold
  • 304 stainless steel liquid distributor
  • 45kW heat dissipation cabinet

14.2 Complete SEO Tag System

Title Tag:

KITOZER 45kW Liquid-Cooled Server Rack | High-Density Data Center Cooling Cabinet Manufacturer — Guangzhou KITOZER (gdlain.com)

Meta Description:

Discover the KITOZER-LC-45kW-42U liquid-cooled server rack — 45kW cold plate cooling capacity, 42U 19-inch standard, 304 stainless manifold, drip-free quick couplings. Project-confirmed from China’s leading data center rack manufacturer with global export experience. Turnkey liquid cooling solutions available.

Meta Keywords:

liquid cooled server rack, 45kW rack, data center liquid cooling, high density server cabinet, cooling rack manufacturer

14.3 Internal Link Anchor Text Strategy

Anchor Text Target Page
————- ————-
Liquid-cooled server rack Product detail page
45kW cooling capacity Technical specifications page
Manifold CDU system Liquid cooling system page
Data center cooling solution Solution overview page
Rack manufacturer China About us / factory page
High-density data center Application case studies page
Liquid cooling infrastructure Infrastructure solutions page
Custom server racks Customization service page

—

Chapter 15: Website Backend Configuration

15.1 Standard Backend Settings

The official website (https://gdlain.com) is configured with the following standard settings to optimize user experience and international lead generation:

  • Site Language: English (primary)
  • Site Currency: USD (US Dollar) as primary display, CNY available
  • Time Zone: GMT+8 (China Standard Time)
  • Contact Display: Full contact information on all pages including phone, WhatsApp, email, and address
  • Product Showcase: Filterable product catalog by category, power rating, and application
  • File Downloads: Technical specifications, brochures, and certifications in PDF format
  • Inquiry System: Multi-field inquiry form with product selection and specification inputs
  • Responsive Design: Fully mobile-responsive layout for all devices

15.2 Advanced Backend Settings

  • Multi-Language Support: Framework in place for additional languages (Spanish, Russian, Arabic) for regional market expansion
  • CRM Integration: Lead capture and management system integrated with backend
  • Live Chat: Real-time customer service chat application integrated for international time zones
  • Analytics: Full web analytics implementation for traffic analysis and conversion tracking
  • Content Management: Weekly content publication on applications, case studies, and technical insights
  • Performance Optimization: CDN acceleration for global content delivery, especially for markets in USA, Europe, Southeast Asia, Middle East, and Africa

15.3 Search Optimization Settings

  • XML Sitemap: Dynamically generated, auto-submitted to Google Search Console and Bing Webmaster Tools
  • Structured Data: Schema.org markup for Products, Organization, and Breadcrumbs
  • HTTPS Security: Full-site SSL encryption
  • Page Speed: Optimized image compression, lazy loading, and caching for fast international access
  • Mobile Optimization: Mobile-first indexing compliance
  • Local SEO: Google Business Profile for “Guangzhou Lain Intelligent System Development Co., Ltd.” and location-specific pages for international market targeting

—

Appendix: Company Contact Information

Company Name: Guangzhou Lain Intelligent System Development Co., Ltd.

Brand: KITOZER

Address: Huashan Road 5, Shilou Town, Panyu District, Guangzhou, Guangdong, China

Tel / WhatsApp / WeChat: +86 13538869979 / +86 13538869979

Website: https://gdlain.com

Business Hours: Monday–Saturday, 9:00–18:00 (GMT+8)

For overseas project inquiries, technical specifications, and partnership opportunities, we welcome direct contact. Our international sales team responds to all inquiries within 24 hours.

Shopping Cart