KITOZER
KITOZER

48V DC Power System Design: KITOZER Telecom Rectifier Cabinet with Battery Backup

Telecom DC Power System: 48V Rectifier Cabinet Design and Sizing

Telecom base stations, fiber access nodes, and edge sites require reliable 48V DC power. The KITOZER KZ-PS48120 integrated power cabinet combines a 48V/120A rectifier system with battery backup in a single wall or floor-mount enclosure. This application note covers system sizing, configuration, and deployment best practices.

System Architecture

The KZ-PS48120 system consists of:

  • AC input distribution (32A breaker, surge protection)
  • Rectifier modules (4× 30A hot-swap modules, N+1 redundancy)
  • DC output distribution (8× 10A fused outputs)
  • Battery management (2× battery strings, 100Ah each)
  • Monitoring unit (RS485/Ethernet, web interface)
  • Environmental sensors (temperature, door contact)

Technical Specifications

Parameter Value
System Voltage -48V DC (nominal)
Max Output Current 120A
Rectifier Modules 4× 30A hot-swap, 93% efficiency
AC Input 220VAC ±20%, 50/60Hz
Bytesry Charging 2-stage: bulk 54.0V, float 53.5V
Battery Capacity 2× 100Ah (24V) or 4× 100Ah (12V)
Backup Time (at 50A load) ~2 hours (2×100Ah)
Enclosure IP55 wall mount, 600×800×350mm
Dimensions 600(H)×800(W)×350(D) mm
Weight 85kg (without batteries)
Reference Price $2,800 – $3,500 USD

Sizing Calculation Example

For a base station with 40A average load:

Step 1: Required rectifier capacity = 40A load + battery charging (10A) = 50A. Select 2×30A modules (N+1 redundancy).

Step 2: Battery capacity for 4-hour backup at 40A: 40A × 4h = 160Ah. Select 2×100Ah strings in parallel (200Ah effective with derating).

Step 3: Cabinet size must accommodate 4× 12V 100Ah batteries. KZ-PS48120-W fits 4 batteries in the lower compartment.

Deployment Scenarios

  • 5G base station (RRU + BBU, 30-50A)
  • Fiber access point (OLT + splitters, 15-25A)
  • Security camera backbone (PoE switch + NVR, 10-20A)
  • Remote telecom hut (24/7 operation, UPS + generator interface)

Monitoring and Remote Management

The built-in monitoring unit supports Modbus RTU (RS485) and SNMP over Ethernet. Real-time monitoring includes: AC voltage/current, DC voltage/current per string, battery voltage/temperature, charger status, and door alarms. Alarm notifications via email, SMS, or webhook.

SEO Tags

Core: 48V DC power system, telecom rectifier, battery backup cabinet, power distribution

Long-tail: 48V 120A rectifier cabinet, telecom power supply with battery, outdoor power cabinet, KITOZER DC power system

Brand: KZ-PS48120, KITOZER power cabinet, telecom rectifier

Meta Title: 48V DC Telecom Power System | KITOZER KZ-PS48120 Rectifier Cabinet

Meta Description: KITOZER 48V/120A telecom rectifier cabinet with N+1 redundancy and battery backup. Complete system design guide, sizing calculation and pricing for base stations.

Contact

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER)
Phone/WeChat: +86 13922289957 / +86 18520668845
WhatsApp: +86 19068534140
Web: www.lain.com.cn | www.gdlain.com
Address: Chaotian Park, Zhongrun Industrial Zone, Shilou, Panyu, Guangzhou, China

Shopping Cart