ToggleTechnical Design Proposal for 51-Point Network Host & Telephone/Network TV System
Design Institute: Guangzhou Lain Intelligent System Development Co., Ltd.
Brand Support: KITOZER
Version: V1.0
Date: August 2026
—
Table of Contents
- Company Profile
- Project Overview
- User Requirement Analysis
- Overall System Design Description
- System Equipment Quotation & Configuration List
- Detailed Technical Specifications of System Products
- Core Solution Advantages
- Common Technical Q&A
- Construction Schedule Plan
- Construction Organization Plan
- After-Sales Service System
- Operation & Maintenance Training Plan
- Similar Project References
- SEO Optimization System & Website Backend Configuration
- Contact Information
—
1. Company Profile
Guangzhou Lain Intelligent System Development Co., Ltd. (品牌: KITOZER), established in 2002, is a high-tech enterprise specializing in computer room construction, shielding engineering, low-voltage intelligent system integration, and the R&D and manufacturing of intelligent cabinets. With over two decades of deep industry expertise, the company has developed a full-chain service capability spanning solution design, product development, engineering implementation, and after-sales operation & maintenance. Our proprietary core brand KITOZER has been widely deployed across government, finance, education, healthcare, telecommunications, and industrial manufacturing sectors, earning extensive recognition and trust from clients nationwide.
Our business portfolio covers a comprehensive range of computer room supporting products, including micro-module cold-aisle cabinets, integrated data cabinets, outdoor weatherproof cabinets, shielding cabinets, shielding desks, and control consoles. We also deliver integrated solutions for shielding room construction, IDC data center construction, low-voltage integrated cabling, and environmental monitoring systems. As a manufacturer, we operate our own production base with a dedicated R&D design team, enabling flexible customization services tailored to the client’s on-site environment, business requirements, and budget scope. We provide multiple differentiated design proposals free of charge, ensuring high alignment with actual project needs.
In quality control, we have established a comprehensive quality management system. All products strictly comply with industry standards and internal control benchmarks, with defined operational procedures and inspection protocols at every manufacturing stage. Third-party testing institutions are engaged for routine sampling inspections to ensure consistent, reliable product performance. For after-sales support, we operate a 7×24 technical service system staffed with dedicated account managers and senior engineering teams, providing rapid response to client inquiries and fault reports. Our project-specific service model ensures full life-cycle technical support with dedicated personnel follow-through.
Leveraging more than twenty years of industry experience and technical accumulation, KITOZER consistently upholds the product philosophy of “Efficiency, Green Innovation, Safety, and Convenience,” committed to delivering high-reliability, cost-effective intelligent infrastructure solutions that empower digital transformation and information construction across industries.
—
2. Project Overview
2.1 Project Background
This project encompasses the low-voltage integrated system construction for a three-story building, covering three core subsystems: computer network, telephone voice, and cable television. The design follows the standard architecture specified in the Telephone Network & TV System Diagram, adopting a three-level star topology structure comprised of the “Incoming Line Core Layer – Floor Distribution Layer – Terminal Access Layer.” Through vertical backbone cable trays and horizontal cabling systems, comprehensive low-voltage signal coverage is achieved across the entire building, meeting routine requirements for office communications, network access, and television reception.
The project plans a total of 51 terminal points, equipped with 1 core network host serving as the network-wide data forwarding core. Each floor is fitted with an independent weak-current room and integrated distribution box. The outdoor incoming lines are laid via RC50 hot-dip galvanized steel conduits buried underground, with surge protective devices (SPD) at the entry point to meet lightning protection standards. The entire system complies with applicable national design codes and construction standards, balancing practicality, reliability, and scalability.
2.2 Construction Scope
This project covers all areas of the building from the 1st to the 3rd floor, specifically including:
- Incoming Line System: Outdoor buried steel conduit installation, lightning/surge protection at entry, installation of the 1st-floor main integrated equipment cabinet, and core equipment deployment
- Vertical Backbone System: Installation of metal cable trays for weak-current systems and backbone cable installation for all three subsystems
- Floor Distribution System: Installation of integrated distribution boxes in floor weak-current rooms, deployment of floor distribution equipment, and cable termination
- Horizontal Terminal System: Concealed installation of terminal point conduits, horizontal cable installation, and terminal faceplate installation
- System Commissioning & Acceptance: Full-link testing, functional commissioning, completion acceptance, and handover training
2.3 Construction Objectives
- Functional Objectives: Achieve stable connectivity for all 51 terminal points; network points support gigabit to desktop; telephone points deliver clear, noise-free voice; TV points support high-definition digital signal transmission
- Performance Objectives: Full-link transmission performance meets corresponding grade standards without bottlenecks or noticeable attenuation; core equipment supports continuous 7×24 operation
- Reliability Objectives: Use national-standard quality materials and mature equipment; implement comprehensive lightning protection and grounding with physical protection capable of adapting to complex indoor and outdoor environments
- Scalability Objectives: Reserve ample redundancy in cable tray capacity, equipment ports, and backbone links to support future extension and system upgrades
- Compliance Objectives: Design, construction, and acceptance strictly adhere to national codes with neat cabling and clear labeling for convenient future maintenance
2.4 Design Basis
This proposal strictly complies with the following national codes, industry standards, and project drawing requirements:
| Standard | Description |
| ———- | ————- |
| GB 50311-2016 | Code for Engineering Design of Generic Cabling System |
| GB 50312-2016 | Code for Engineering Acceptance of Generic Cabling System |
| GB/T 50200-2018 | Code for Engineering Design of CATV Network |
| GB 50343-2012 | Technical Code for Protection of Building Electronic Information System Against Lightning |
| GB 50054-2011 | Code for Design of Low Voltage Electrical Installations |
| GB 51348-2019 | Standard for Electrical Design of Civil Buildings |
| GB 51158-2015 | Code for Engineering Design of Communication Line |
| — | Project-provided Telephone Network & TV System Diagram construction drawings |
| — | KITOZER corporate construction and product internal control standards |
—
3. User Requirement Analysis
3.1 Terminal Point Scale Requirements
The project comprises a total of 51 terminal points, distributed evenly by system type and floor as follows:
| Floor | Network Data Points | Telephone Voice Points | Cable TV Points | Floor Total |
| ——- | :—-: | :—-: | :—-: | :—-: |
| 1st Floor | 8 | 6 | 3 | 17 |
| 2nd Floor | 8 | 6 | 3 | 17 |
| 3rd Floor | 8 | 6 | 3 | 17 |
| Total | 24 | 18 | 9 | 51 |
3.2 Core Equipment Requirements
The project is configured with 1 enterprise-grade core network host (core switch), deployed within the network compartment of the 1st-floor main integrated equipment cabinet. This device handles data aggregation and forwarding for all 24 network points throughout the building. The switch must deliver stable forwarding performance, comprehensive Layer 2 management functions, and support for port mirroring, VLAN partitioning, storm control, and other features to meet office network management and security requirements.
3.3 System Architecture Requirements
According to the drawing requirements, the system adopts a layered star topology with a three-compartment cabinet structure:
- Three-Level Topology: 1st-floor incoming core layer → 2nd/3rd-floor distribution layer → room terminal access layer, providing clear hierarchy for easy management and fault diagnosis
- Three-Compartment Cabinet Design: The main equipment cabinet and floor distribution boxes each feature three independent compartments — TV, telephone, and network — providing physical isolation to prevent cross-system signal interference
- Shared Cable Tray: All three system cables share a 200×100 low-voltage metal cable tray, with zoned bundling and spacing maintained within the tray, balancing installation cost-efficiency with management convenience
3.4 Cabling and Conduit Requirements
- Backbone Cable Trays: Vertical backbone and horizontal branches both use 200mm×100mm galvanized metal cable trays with good mechanical strength and electromagnetic shielding performance
- Outdoor Incoming Lines: 1 cable for the TV system and 3 cables for the telephone/network systems — a total of 4 RC50 hot-dip galvanized steel conduits, buried at a depth of 0.8 meters with watertight sealing
- Horizontal Branch Conduits: Runs from cable trays to terminal points use JDG20 galvanized steel conduit, concealed installation to protect cables from external damage, in compliance with building decoration codes
3.5 Lightning Protection and Safety Requirements
Each of the three system incoming lines is fitted with a corresponding interface surge protective device (SPD) meeting Class D lightning protection standards, effectively suppressing lightning-induced overvoltages and surge currents to protect downstream equipment. Grounding resistance meets code requirements.
3.6 Equipment Cabinet Requirements
- 1st-Floor Main Integrated Cabinet: Recommended size 400mm×600mm×150mm, wall-mounted at 1.5m from floor level
- 2nd/3rd-Floor Distribution Boxes: Recommended size 260mm×300mm×100mm, wall-mounted at 0.5m from floor level
- Material: All cabinets are fabricated from cold-rolled steel plate with electrostatic powder coating, featuring locks and grounding terminals
3.7 Operation & Maintenance Management Requirements
The system must incorporate a complete labeling scheme with unique identifiers on both ends of every cable, equipment ports, and faceplates. Complete link documentation is required. The system architecture must be straightforward and clearly structured, enabling routine inspection and basic fault handling by operation staff after simple training.
—
4. Overall System Design Description
4.1 Design Principles
4.1.1 Balance of Advancement and Maturity
The solution adopts current industry-mainstream, mature technologies. The network system uses Category 6 unshielded cabling standards supporting gigabit transmission with 10G upgrade compatibility. Core equipment is selected from enterprise-grade commercial switches with full functionality and stable operation, avoiding risks associated with unproven emerging technologies.
4.1.2 Priority on Reliability and Stability
The full transmission link utilizes national-standard quality cables and connectors, with high-reliability models selected for critical equipment. Cabling links incorporate redundancy design, and the lightning protection and grounding system is comprehensive, minimizing system failure probability and ensuring long-term stable operation.
4.1.3 Standardization and Compatibility
All product interfaces, performance parameters, and dimensions comply with national and industry standards, ensuring interoperability across different brands. The cabling system adopts a universal modular structure, facilitating future maintenance, replacement, and expansion.
4.1.4 Cost-Effectiveness and Practicality
While meeting functional and performance requirements, the system architecture and product selection are optimized to avoid over-specification. The solution closely matches actual project usage needs with practical functionality and simple operation, maximizing investment returns.
4.1.5 Scalability and Flexibility
Cable tray capacity reserves more than 30% spare space, core equipment reserves spare ports, and backbone links reserve redundant pairs. The system supports future point expansion, system upgrades, and business adjustments without major modifications to the existing architecture.
4.2 Overall Topology Architecture
The system adopts a three-level star topology where all three subsystems share conduit and cable tray infrastructure while maintaining physical separation, independent operation, and unified management.
4.2.1 Incoming Line Core Layer (1st-Floor Main Equipment Room)
Serving as the hub of the entire low-voltage system, outdoor carrier cables are introduced through RC50 buried steel conduits into the 1st-floor main integrated equipment cabinet:
| System | Signal Path |
| ——– | ————- |
| Network System | Incoming line passes through network SPD → connects to core network host → distributed to 2nd & 3rd floor distribution boxes via vertical Category 6 backbone cables |
| Telephone System | Incoming line passes through telephone SPD → terminates at 110-type main distribution frame → connected to floor terminal blocks via Category 3 large-pair backbone cables |
| TV System | Incoming line passes through TV SPD → connects to 1×4 main splitter (one port reserved) → the other three ports connect to floor tap-offs via coaxial cables |
4.2.2 Floor Distribution Layer (2nd & 3rd Floor Weak-Current Rooms)
Each floor’s weak-current room houses a three-compartment integrated distribution box that receives vertical backbone signals and distributes them to all terminal points on that floor:
| Compartment | Function |
| ————- | ———- |
| Network Section | Vertical backbone cable terminated, connected to horizontal cables via patch cords, distributed to 8 network points on the floor |
| Telephone Section | Large-pair backbone cable terminated at floor 110 terminal block, cross-connected to horizontal voice cables, distributed to 6 telephone points on the floor |
| TV Section | Backbone coaxial cable connected to 1×3 floor tap-off, distributed to 3 TV points on the floor |
4.2.3 Terminal Access Layer
Type 86 terminal faceplates are installed in each room and office area. Horizontal cables are routed from cable trays through JDG conduits to terminal faceplates, where modules are terminated for terminal device connectivity.
4.3 Conduit and Cable Tray System Design
4.3.1 Low-Voltage Metal Cable Tray
| Parameter | Specification |
| ———– | ————— |
| Specification | 200mm (W) × 100mm (H) trough-type galvanized metal cable tray |
| Routing Path | Vertically through the weak-current shaft connecting floors 1–3; horizontally within ceiling voids on each floor corridor |
| Capacity Calculation | Tray cross-sectional area: 20,000mm²; usable area at 40% fill rate: 8,000mm²; combined vertical + horizontal cable occupation of three systems: < 1,000mm², leaving ample expansion space |
| Installation Requirements | Support bracket spacing ≤2m; vertical deviation ≤3mm/m; horizontal deviation ≤2mm/m; cross-bonding grounding at tray connections |
4.3.2 Outdoor Incoming Steel Conduits
| Parameter | Specification |
| ———– | ————— |
| Specification | RC50 hot-dip galvanized welded steel conduit, wall thickness ≥3.5mm |
| Quantity | 4 conduits total — 1 for TV system, 3 for telephone/network systems |
| Installation | Buried at 0.8m depth outdoors; protective sleeve added when crossing roadways; watertight sealing at both ends; conduit ends polished smooth without burrs to prevent cable damage |
| Grounding | Both ends of each conduit reliably connected to equipotential grounding terminals |
4.3.3 Horizontal Conduits
| Parameter | Specification |
| ———– | ————— |
| Specification | JDG20 setscrew-type galvanized steel conduit, wall thickness ≥1.2mm |
| Installation Method | Concealed installation within walls, floor slabs, or ceilings; junction boxes installed at bends; intermediate boxes added where conduit runs exceed code limits |
| Cable Pulling Requirements | Maximum 2 Category 6 cables or 1 coaxial cable per conduit; bending radius meets cable bend requirements |
4.4 Lightning Protection and Grounding System Design
4.4.1 Protection Level
In accordance with GB 50343-2012, this project’s low-voltage system is designed to Class D protection level with signal surge protective devices installed at incoming lines. Rated discharge current: 5kA; maximum discharge current: 10kA.
4.4.2 Configuration Scheme
| System | SPD Configuration |
| ——– | ——————- |
| Network System | 1 × RJ45 interface gigabit network SPD |
| Telephone System | 1 × RJ11 interface telephone signal SPD |
| TV System | 1 × F-type interface coaxial signal SPD |
4.4.3 Grounding Requirements
- All SPD grounding terminals shall be connected to the building’s low-voltage equipotential terminal using stranded copper wire of not less than 4mm² cross-section
- All metal cable trays, steel conduits, and equipment cabinets shall be equipotentially bonded; grounding resistance ≤4Ω
- Grounding conductors shall be short and direct, without coiling, ensuring unobstructed surge discharge paths
—
5. System Equipment Quotation & Configuration List
5.1 Core Network System Configuration
| No. | Item Description | Specification/Model | Unit | Qty | Brand | Remarks |
| :—: | —————– | ——————— | :—-: | :—: | ——- | ——— |
| 1 | Core Network Host (Gigabit Switch) | 24-port gigabit Ethernet rack-mount switch | Unit | 1 | KITOZER | Deployed in 1F main cabinet; network-wide core aggregation; full line-rate forwarding |
| 2 | Category 6 Unshielded Patch Panel | 19″ 24-port modular Cat6 patch panel | Unit | 1 | KITOZER | Installed in main cabinet; terminates all horizontal & backbone network cables |
| 3 | 1U Cable Management Bar | 19″ metal cable manager | Unit | 1 | KITOZER | Companion to patch panel for organized jumpers |
| 4 | Category 6 Network Patch Cord | 1m unshielded factory-terminated patch cord | Pc | 24 | KITOZER | Used for patching between panel and switch |
| 5 | Category 6 Unshielded Twisted Pair | 4-pair 8-core 23AWG OFC copper | m | 1200 | KITOZER | Horizontal + vertical backbone network cable, incl. redundancy & installation allowance |
| 6 | Category 6 Network Module | RJ45 90° IDC type, unshielded | Pc | 24 | KITOZER | One per network terminal point |
| 7 | Network Signal Surge Protector | RJ45 gigabit SPD | Pc | 1 | KITOZER | Network incoming lightning protection, Class D |
5.2 Telephone Voice System Configuration
| No. | Item Description | Specification/Model | Unit | Qty | Brand | Remarks |
| :—: | —————– | ——————— | :—-: | :—: | ——- | ——— |
| 1 | Main Voice Distribution Frame | 100-pair 110-type rack-mount distribution frame | Unit | 1 | KITOZER | Installed in 1F main cabinet; carrier incoming termination |
| 2 | Floor Voice Terminal Blocks | 50-pair 110-type wall-mount terminal blocks | Unit | 2 | KITOZER | One per floor for 2F & 3F; floor telephone cable termination & distribution |
| 3 | Category 3 Large-Pair Cable | 25-pair indoor voice backbone cable | m | 60 | KITOZER | 1F–3F vertical backbone voice transmission |
| 4 | Category 6 Unshielded Twisted Pair | 4-pair 8-core national-standard OFC copper | m | 900 | KITOZER | Horizontal telephone point cabling, voice-transmission compatible |
| 5 | Telephone Voice Module | RJ11 Cat3 voice module | Pc | 18 | KITOZER | One per telephone terminal point |
| 6 | Telephone Patch Cord | 1m RJ11 factory-terminated | Pc | 18 | KITOZER | Cross-connect between frame and terminal blocks |
| 7 | Telephone Signal Surge Protector | RJ11 signal SPD | Pc | 1 | KITOZER | Telephone incoming lightning protection |
5.3 Cable TV System Configuration
| No. | Item Description | Specification/Model | Unit | Qty | Brand | Remarks |
| :—: | —————– | ——————— | :—-: | :—: | ——- | ——— |
| 1 | Main Signal Splitter | 1-in 4-out broadband CATV splitter | Unit | 1 | KITOZER | 1F main cabinet; trunk signal distribution to all floors |
| 2 | Floor Tap-Off | 1-in 3-out floor TV tap-off | Unit | 3 | KITOZER | One per floor; distributes to floor TV points |
| 3 | Coaxial Cable | SYWV75-5 physical foam dielectric | m | 540 | KITOZER | Vertical backbone + horizontal TV cable, incl. allowance |
| 4 | Cable TV Terminal Faceplate | 86-type single-port TV faceplate | Pc | 9 | KITOZER | One per TV terminal point |
| 5 | F-Type Compression Connector | 75-5 zinc alloy, nickel-plated | Pc | 30 | KITOZER | Cable end termination, incl. spares |
| 6 | TV Signal Surge Protector | F-type coaxial SPD | Pc | 1 | KITOZER | TV incoming lightning protection |
5.4 Conduit and Cable Tray System Configuration
| No. | Item Description | Specification/Model | Unit | Qty | Brand | Remarks |
| :—: | —————– | ——————— | :—-: | :—: | ——- | ——— |
| 1 | Low-Voltage Metal Cable Tray | 200×100mm galvanized trough type | m | 75 | KITOZER | Incl. 15m vertical backbone + 60m horizontal branches |
| 2 | RC50 Hot-Dip Galvanized Steel Conduit | DN50, wall thickness 3.5mm | m | 40 | National Standard | 4 outdoor incoming conduits × 10m each, burial depth 0.8m |
| 3 | JDG20 Galvanized Conduit | DN20 setscrew type, wall 1.2mm | m | 153 | National Standard | Horizontal branch conduits, avg. 3m per point × 51 points |
| 4 | Cable Tray Accessories | Elbows, tees, couplers, end caps | Lot | 1 | KITOZER | Companion fitting for 200×100 tray |
| 5 | Cable Tray Support Brackets | L-type galvanized trapeze arms | Set | 38 | KITOZER | One set per 2m of tray, incl. expansion anchors |
5.5 Equipment Cabinets and Terminal Faceplate Configuration
| No. | Item Description | Specification/Model | Unit | Qty | Brand | Remarks |
| :—: | —————– | ——————— | :—-: | :—: | ——- | ——— |
| 1 | Main Integrated Equipment Cabinet | 400×600×150mm, 3-compartment, wall-mount | Unit | 1 | KITOZER | 1F weak-current room; installed 1.5m above floor |
| 2 | Floor Integrated Distribution Box | 260×300×100mm, 3-compartment, wall-mount | Unit | 2 | KITOZER | One per floor for 2F & 3F; installed 0.5m above floor |
| 3 | Dual-Port Information Faceplate | 86-type, network + telephone | Pc | 18 | KITOZER | For combined network/telephone points |
| 4 | Single-Port Network Faceplate | 86-type, single RJ45 | Pc | 6 | KITOZER | For dedicated network points |
| 5 | Flush-Mount Back Box | 86-type, PVC flame-retardant | Pc | 51 | National Standard | One per terminal point |
5.6 Installation Accessories and Miscellaneous
| No. | Item Description | Specification/Model | Unit | Qty | Brand | Remarks |
| :—: | —————– | ——————— | :—-: | :—: | ——- | ——— |
| 1 | Category 6 RJ45 Connectors | Three-prong gold-plated, 100 pcs/box | Box | 1 | KITOZER | Cable termination & spares |
| 2 | Cable Ties, Screws, Expansion Anchors | National standard common specification | Lot | 1 | National Standard | System-wide installation & fastening |
| 3 | Cable Identification Labels | Waterproof self-adhesive | Sheet | 5 | National Standard | Cable & port numbering identification |
—
6. Detailed Technical Specifications of System Products
6.1 Core Network System Product Specifications
6.1.1 Core Network Host (24-Port Gigabit Ethernet Switch)
I. Hardware Specifications
| Parameter | Specification |
| ———– | ————— |
| Port Configuration | 24 × 10/100/1000BASE-T auto-negotiation Ethernet ports, supporting Auto MDI/MDIX with 10M/100M/1000M device compatibility |
| Switching Capacity | ≥48Gbps, all ports with wire-speed non-blocking forwarding |
| Packet Forwarding Rate | ≥35.7Mpps, supporting high-volume concurrent data transmission |
| MAC Address Table | 8K MAC address capacity, auto-learning, auto-aging with configurable aging time |
| Buffer Capacity | 256KB shared buffer per port for burst traffic handling |
| Power Input | AC 100–240V 50/60Hz wide-voltage input, tolerant of grid fluctuations |
| Power Consumption | ≤18W, energy-efficient and environmentally friendly |
| Cooling Method | Fanless natural convection cooling, silent operation suitable for office environments |
| Physical Dimensions | Standard 19″ rack-mount, 1U height, 440mm×200mm×44mm |
| Chassis Material | 1.0mm cold-rolled steel, electrostatic powder coating, corrosion-resistant & EMI-shielded |
| Mounting | Rack-mount or wall-mount with included mounting brackets |
II. Layer 2 Functional Specifications
| Function | Specification |
| ———- | ————— |
| VLAN | IEEE 802.1Q VLAN, up to 4K VLANs; supports port-based and protocol-based VLANs for broadcast domain segmentation |
| Spanning Tree | STP/RSTP/MSTP support for loop prevention and enhanced network reliability |
| Link Aggregation | Static aggregation and LACP dynamic aggregation, up to 8 aggregation groups × 8 ports each |
| Port Mirroring | 1:1 and N:1 mirroring; ingress, egress, and bidirectional traffic mirroring for monitoring and troubleshooting |
| Rate Limiting | Port-based ingress/egress rate limiting, minimum granularity 64Kbps |
| Storm Control | Broadcast, multicast, and unknown unicast storm suppression with configurable thresholds |
| Jumbo Frame | Up to 9K bytes for enhanced large-file transfer efficiency |
| Cable Diagnostics | VCT virtual cable testing for short-circuit, open-circuit, pair mis-wiring, and fault distance diagnosis |
III. Management and Maintenance
| Feature | Specification |
| ——— | ————— |
| Management Methods | Web GUI management, Console CLI, Telnet/SSH remote management |
| Configuration Management | Configuration file backup/restore, firmware online upgrade |
| Monitoring | Port traffic statistics, port status, system temperature, CPU usage monitoring |
| Logging | System logs, operation logs, alarm logs, syslog server reporting |
| SNMP | SNMP v1/v2c/v3 support, compatible with mainstream network management platforms |
IV. Environmental and Reliability
| Parameter | Specification |
| ———– | ————— |
| Operating Temperature | 0°C to 45°C |
| Storage Temperature | −10°C to 70°C |
| Operating Humidity | 10% to 90%, non-condensing |
| Protection Rating | IP30, suitable for indoor cabinet/equipment box installation |
| MTBF | ≥100,000 hours |
| Compliance | CE, FCC, RoHS; compliant with national EMC standards |
6.1.2 24-Port Category 6 Unshielded Patch Panel
| Parameter | Specification |
| ———– | ————— |
| Product Type | 19″ rack-mount modular Cat6 patch panel, 1U height |
| Performance Grade | Compliant with TIA/EIA 568-C.2, ISO/IEC 11801, GB/T 18015 Category 6 standards; supports 250MHz bandwidth |
| Port Quantity | 24 RJ45 ports with dust covers |
| Contact Material | Phosphor bronze base, gold plating ≥50μinch, three-prong contact design; ≥750 mating cycles; contact resistance ≤20mΩ |
| IDC Terminals | Phosphor bronze tin-plated, suitable for 22–26AWG solid/stranded conductors; ≥200 termination cycles; insulation resistance ≥1000MΩ |
| Wiring Identification | Clear T568A/T568B wiring sequence indicators printed on both port front and rear IDC blocks |
| Frame Material | 1.5mm cold-rolled steel frame, black electrostatic powder coating, rust-resistant and durable |
| Cable Management | Integrated rear cable management rings for tidy cable bundling |
| Labeling System | Replaceable paper labels with transparent protective covers for port identification |
| Transmission Performance | Insertion loss: ≤1.6dB @250MHz; Return loss: ≥20.1dB @250MHz; NEXT: ≥39.1dB @250MHz; ACR: ≥18dB @250MHz; ELFEXT: ≥23.2dB @250MHz |
| Dimensions | 482.6mm × 44.45mm × 100mm |
| Operating Temperature | −10°C to 60°C |
| Certification | UL, ETL; RoHS compliant |
6.1.3 1U Metal Cable Management Bar
| Parameter | Specification |
| ———– | ————— |
| Specification | 19″ standard rack-mount, 1U height |
| Structure | 12-ring dual-sided cable management with front and rear cable routing space |
| Material | 1.2mm cold-rolled steel, black electrostatic powder coating |
| Function | Organizes patch cords and cables, maintains neat cabinet/box wiring, reduces cable bending stress, improves airflow |
| Mounting | Standard rack screws; installed alongside patch panels and switches |
| Dimensions | 482.6mm × 44.45mm × 80mm |
6.1.4 1m Category 6 Unshielded Network Patch Cord
| Parameter | Specification |
| ———– | ————— |
| Product Type | Category 6 unshielded factory-terminated RJ45–RJ45 patch cord |
| Cable Specification | 24AWG stranded OFC conductors, 4-pair 8-core, HDPE insulation, PVC jacket |
| Connector | Three-prong gold-plated contacts, plating ≥50μinch, strain-relief boot, ≥1000 mating cycles |
| Performance Standard | TIA/EIA 568-C.2 Category 6; supports 250MHz bandwidth and gigabit Ethernet |
| Electrical Performance | Insertion loss: ≤0.4dB @250MHz; Return loss: ≥22dB @250MHz; NEXT: ≥42dB @250MHz |
| Flame Rating | VW-1 jacket, flame-retardant |
| Length | 1m; custom lengths available upon request |
| Color | Blue (network-dedicated, for system identification) |
6.1.5 Category 6 Unshielded Twisted Pair
| Parameter | Specification |
| ———– | ————— |
| Model | UTP CAT6 4×2×0.57mm Category 6 unshielded twisted pair |
| Conductor | Solid high-purity oxygen-free copper (OFC), 23AWG, diameter 0.57±0.02mm, purity ≥99.99%, superior conductivity, minimal signal attenuation |
| Insulation | Physical foam HDPE insulation per conductor; color-coded pairs per standard spectrum: White/Blue–Blue, White/Orange–Orange, White/Green–Green, White/Brown–Brown |
| Cross Separator | Built-in PE cross web separator maintaining pair geometry, reducing pair deformation under external pressure, effectively lowering crosstalk for high-frequency performance |
| Twist Design | Four pairs utilize different precision twist rates to optimize crosstalk and return loss performance |
| Outer Jacket | PVC, grey, flame-retardant grade CM/CMR; abrasion-resistant, anti-aging, flexible for installation |
| Transmission Performance (20°C) | Bandwidth: 250MHz; supports 10/100/1000Mbps Ethernet; 10G capable at short distances; DC resistance: ≤9.38Ω/100m; resistance unbalance: ≤3%; mutual capacitance: ≤5.6nF/100m; characteristic impedance: 100±15Ω @1–250MHz; attenuation: ≤22.5dB/100m @250MHz; NEXT: ≥39.1dB/100m @250MHz; ACR: ≥17.0dB @250MHz; ELFEXT: ≥23.2dB @250MHz; RL: ≥20.1dB @250MHz |
| Mechanical Properties | Min. bending radius: ≥8× cable diameter during installation, ≥4× after installation; max. tensile strength: ≤100N; operating temperature: −20°C to 60°C; installation temperature: above 0°C |
| Standards & Certification | TIA/EIA 568-C.2, ISO/IEC 11801, GB/T 18015; UL, ETL certified; RoHS compliant |
| Packaging | 305m/box, cardboard packaging with moisture barrier |
6.1.6 Category 6 Unshielded Network Module
| Parameter | Specification |
| ———– | ————— |
| Product Type | RJ45 Category 6 unshielded information module, 90° IDC termination |
| Performance Grade | TIA/EIA 568-C.2 Category 6; 250MHz bandwidth; gigabit transmission support |
| Interface Type | Standard 8P8C RJ45 jack, compatible with RJ11 telephone plugs |
| Contact Material | Phosphor bronze base, gold plating ≥50μinch, three-prong contact; reliable connectivity with high durability |
| IDC Terminals | Phosphor bronze, tin-plated; suitable for 22–26AWG solid conductors; ≥200 re-termination cycles |
| Wiring Label | Clear T568A/T568B color codes printed on module body |
| Housing Material | High-strength flame-retardant ABS engineering plastic, UL94-V0 rating, heat-resistant and impact-resistant |
| Mounting | Snap-in design compatible with standard 86-type faceplates, floor boxes, and patch panels |
| Electrical Performance | Contact resistance: ≤20mΩ; insulation resistance: ≥1000MΩ; dielectric strength: AC 1000V/1min no breakdown; insertion loss: ≤0.4dB @250MHz; return loss: ≥20dB @250MHz; NEXT: ≥39dB @250MHz |
| Service Life | ≥750 mating cycles |
| Operating Temperature | −10°C to 60°C |
| Certification | RoHS compliant; tested per Ministry of Industry and Information Technology standards |
(Note: Remaining sections —— Chapter 7 through Chapter 15 — will be provided in the subsequent document volume.)