Table of Contents
ToggleKITOZER Outdoor Intelligent Integrated Cabinet Installation & Protection Guide
Model: KTR-OC Series | IP55 (IP65 optional) | Operating temperature -40 °C to +55 °C
Product Overview
The KITOZER KTR-OC outdoor intelligent integrated cabinet is a purpose-built enclosure for 5G base stations, power distribution automation, traffic monitoring, surveillance, edge computing and outdoor energy storage. Factory prefabricated and modular, it only needs a concrete foundation, cabinet placement and simple wiring on site, cutting build time by over 80% and total cost by over 50% compared with a traditional equipment room.
The cabinet uses an isolated dual-cabin design: equipment cabin and battery cabin are temperature-controlled and wired independently, so battery heat and IT heat do not interfere. The shell is 2.0 mm cold-rolled steel with hot-dip zinc undercoat plus outdoor polyester powder topcoat, rated for 1000 h salt spray. Coastal and chemical-plant sites can be upgraded to IP65 and C4/C5 corrosion protection.
Protection & Environmental Adaptation
| Threat | Design response |
|---|---|
| Rain / dust | IP55 standard, IP65 optional; EPDM foam gasket, raised base, bottom-entry cable glands |
| Heat / cold | -40 to +55 °C operation; PTC heating below -10 °C; VFD AC for high-temperature cooling |
| Salt spray / corrosion | ≥80 µm zinc + ≥60 µm polyester powder; 1000 h salt spray; C4/C5 optional |
| Typhoon / seismic | Withstands 35 m/s (Grade 12) wind; seismic grade 8; channel-steel base ≥1500 kg |
| Lightning | C+D surge protection, 40 kA on power, 5 kA on signal; grounding ≤4 Ω |
| Theft / vandalism | Three-point anti-theft lock (GA/T 73 grade B); door + vibration + PIR alarms |
Hybrid Thermal Management
KTR-OC combines VFD air conditioner, air-to-air heat exchanger, smart fan and PTC heater, automatically switching based on internal load and ambient temperature. Total-cabinet PUE ≤1.2.
- VFD AC: 2000 / 3000 / 5000 W cooling, APF ≥3.2, equipment cabin ±0.5 °C;
- Heat exchanger: all-aluminum counter-flow, ≥65% efficiency, 500/1000/1500 W;
- Smart fans: 4× PWM axial fans with G4 filter, emergency mode on AC failure;
- PTC heater: 200/500/1000 W, starts at 5 °C, 85 °C thermal cutout, open-flame free.
FSU Monitoring
An embedded FSU (ARM Cortex-A7 quad-core) offers 8× AI, 16× DI, 8× DO, 2× GbE and built-in 4G (5G/LoRa/NB-IoT optional). It speaks Modbus RTU/TCP, MQTT, HTTP, SNMP and IEC 104. It samples T/H (±0.3 °C / ±2% RH), water leak (0.5 mm trigger), smoke, V/A (0.5 class), door and vibration across 200+ points, with ≥30 days local storage.
Specifications
| Item | Value |
|---|---|
| Standard sizes | 1200 W × 800 D × 2000 H / 900 W × 900 D × 2100 H mm (multiple tiers) |
| Max custom size | 2500 W × 1200 D × 2500 H mm |
| Configuration | Dual cabin (equipment + battery) / triple cabin |
| Sheet thickness | Frame 2.0 mm, door 1.5 mm, base 3.0 mm channel steel |
| Ingress protection | IP55 (IP65 optional) |
| Operating temperature | -40 °C to +55 °C |
| Wind resistance | Grade 12 typhoon (35 m/s) |
| Seismic | Grade 8 (GB 50260-2013) |
| Input | AC 220 V±20% / optional DC -48 V / AC 380 V three-phase |
| Output circuits | 8× 10 A + 4× 16 A standard, expandable to 24 |
| Cooling | AC + heat exchanger + fan + PTC hybrid |
| Whole-cabinet PUE | ≤1.2 |
| Fire | Combined smoke+heat detector, optional S-type aerosol suppression |
| Remote comms | 4G global / Ethernet, 5G optional |
Reference Configuration & Price
| Model | Typical scope | Reference price (incl. tax & freight) |
|---|---|---|
| KTR-OC-S1-F15 | Single cabin / 1.5 kW fan cooling / basic distribution / FSU | ¥18,000 – ¥25,000 |
| KTR-OC-S2-H20 | Dual cabin / 2.0 kW heat-exchanger / battery bay / 4G FSU | ¥32,000 – ¥45,000 |
| KTR-OC-S2-A30 | Dual cabin / 3.0 kW VFD AC / battery bay / access + CCTV | ¥48,000 – ¥65,000 |
| KTR-OC-S3-A50 | Triple cabin / 5.0 kW AC / aerosol fire / C4 anti-corrosion | ¥75,000 – ¥100,000 |
In USD, roughly US$2,500 – US$13,900. Based on exchange rate as of October 2026 (1 USD ≈ 7.2 CNY). Prices are for reference only; actual quotation may vary by cooling method, battery configuration, surge-protection level, corrosion class and optional CCTV/fire options.
Installation & Site Notes
Site selection: Choose elevated, well-drained ground; top of foundation must be ≥300 mm above historical flood level. Soil bearing ≥100 kPa. Keep ≥800 mm front clearance for door opening and ≥500 mm side clearance.
Foundation: C20 concrete, 200–300 mm high, embedded 4-M16 anchor bolts and grounding flat steel. Cure ≥7 days before placing the cabinet.
Placement: Use a pallet truck or lifting strap — never drag. Level the cabinet to ≤1.5‰ verticality, then lock with washers and double nuts.
Wiring: All cables enter through bottom glands; strong and weak wires run in separate conduits. Bond the grounding busbar to site earth with ≥16 mm² copper, ≤4 Ω.
Commissioning: Test insulation (≥10 MΩ), grounding, AC on/off, heat-exchanger set-point, FSU uplink, smoke/aerosol linkage and remote door-unlock in sequence.
Maintenance Cycle
Monthly: inspect door gaskets, locks and fan filters. Quarterly: measure grounding resistance, clean the AC condenser, check battery terminal voltage. Annual: inspect the anti-corrosion coating, lubricate locks and hinges, calibrate FSU sensors, and weigh the aerosol suppression unit to confirm shelf life. The FSU continuously monitors 200+ points and pushes alarms to local sounder, SMS, platform pop-up and WeChat-style push within 5 seconds; over 90% of routine operations (parameter change, firmware upgrade, remote reboot, thermal mode switch) can be done without a site visit.
KTR-OC cabinets are certified to YD/T 1537, YD/T 5186 and IEC 61969-1, with C4/C5 anti-corrosion variants for coastal and chemical-plant sites. Optional extras include H.265+ CCTV, an aerosol suppression unit, 5G module, photovoltaic input and a pole/wall-mounting kit.
[Render location: KTR-OC dual-cabin exterior / equipment cabin interior / FSU UI / concrete foundation install]