ToggleKITOZER KTR-PSB2 Wall-mounted 3-Phase 40KA SPD
Brand: KITOZER Series: KTR-PSB2 Category: Power Distribution / Surge Protection
SPD3-phase surge protector40KAwall mountpower surge protectionKTR-PSB2
1. Overview
KITOZER KTR-PSB2 is a wall-mounted 3-phase surge protective device (SPD) installed on the feeder side of the data-center distribution panel, protecting all downstream electronics from lightning surges and switching transients. A lightning strike on the external supply or nearby ground grid injects tens of thousands of volts of transient overvoltage along the power line — lasting microseconds but high enough to destroy switch power supplies, motherboard chips and UPS rectifiers. The SPD clamps L-PE voltage to a level the equipment can survive (residual voltage) and diverts surge current to earth.
KTR-PSB2 is a wall-mounted integrated unit containing 3P+N+PE modules: nominal discharge current In 20 kA (8/20μs), max Imax 40 kA. Full 5-wire protection (L1/L2/L3/N/PE), one MOV per phase, and a spark gap between N and PE. Each module has a status window: green = OK, red = replace. A remote dry contact reports SPD failure to the DCIM host. Wall-mount next to the panel, or DIN-rail inside the panel.
Compared with rack-mounted SPDs, the wall version fits panels without spare rail slots, or when adding a standalone stage of protection outside the panel. KTR-PSB2 has an integrated disconnector (Uc 385 V): when an MOV fails short, it disconnects from the line to prevent fire. Response time ≤25 ns, voltage protection level Up ≤1.5 kV. Suits TT/TN-S/TN-C-S systems, 50/60 Hz.
2. Key Features
3-phase 40 kA full protection
- 3P+N+PE 5-wire.
- In 20 kA / Imax 40 kA (8/20μs).
- Up ≤1.5 kV.
Status + remote alarm
- Green/red window at a glance.
- Dry contact to DCIM.
- Field-replaceable modules.
Safe disconnector
- Auto-disconnect on MOV short.
- Fire prevention.
- Uc 385 V continuous.
Wall / DIN dual mount
- Wall or 35 mm rail.
- ≤25 ns response.
3. Specifications
| Item | KTR-PSB2 |
|---|---|
| Poles | 3P+N+PE |
| Max continuous Uc | 385 V AC |
| Nominal In | 20 kA (8/20μs) |
| Max Imax | 40 kA (8/20μs) |
| Voltage protection Up | ≤1.5 kV |
| Response time | ≤25 ns |
| Earthing | TT / TN-S / TN-C-S |
| Remote alarm | 1 dry contact (250V/0.5A) |
| Mount | Wall / 35 mm rail |
| Operating temp | -40~85℃ |
| Size | ~90×80×65 mm/module |
4. Reference Prices
KTR-PSB2 wall 3-phase 40 kA SPD (3P+N, remote contact): Reference USD 63~111 / unit (ref. CNY 450~800 at ~7.2)
KTR-PSB2 complete (SPD + upstream breaker + terminals + wall box): Reference USD 97~167 / set (ref. CNY 700~1,200 at ~7.2)
Reference only; priced by poles, kA rating and enclosure. Ground bus and cable not included. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Main distribution panel primary protection.
- UPS input secondary surge protection.
- Row/PDU feeder protection.
- Overhead feed and rooftop equipment.
- Telecom shelters and outdoor cabinets.
6. Installation & Maintenance
Installation
- De-energize; choose feeder side of panel.
- Wall-box or DIN-rail mount.
- Series upstream backup breaker per coordination study.
- Line L1/L2/L3/N to feed; PE to ground bus.
- Ground lead short and fat (≥6 mm²).
- Wire dry contact to DCIM DI port.
- Energize; confirm green window.
- Record residual voltage on surge test.
Maintenance
- Check indicator window monthly.
- Red window → replace module immediately.
- Review remote alarms after thunderstorms.
- Test earth resistance annually.
- Replace modules every 5 years.
7. FAQ
- Q: Is 40 kA enough for a data hall?
A: For a secondary feeder-side SPD, In 20 kA/Imax 40 kA is adequate. Building main needs 100 kA Class I; row/UPS tertiary uses 10 kA Class III. Multi-stage coordination is best. - Q: Why the upstream breaker?
A: MOVs fail short over time; without a backup breaker this causes a line-to-earth short and fire. The breaker trips to isolate the failed SPD. - Q: Longer ground lead better?
A: No — shorter is better, ≤0.5 m, ≥6 mm². Long leads add inductance and raise residual voltage during surges. - Q: Green window means never stressed?
A: Green means still functional, but it has absorbed surges and degraded. In lightning-prone regions, proactively replace every 3~5 years.
8. Trend & Selection
Power protection moves from single-point to multi-stage coordination — main panel Class I, UPS Class II, row cabinet Class III, with decreasing kA and residual voltage. Select: 40 kA wall unit at feeder; mandatory upstream breaker; short fat ground; remote contact to DCIM; indicator in inspection route; check after storms. The SPD is the data hall’s lightning sentinel — it absorbs the surge so the downstream equipment survives.
9. Delivery & Service
KITOZER supplies wall 3-phase SPDs per the power single-line diagram, with backup breakers, terminals and wall enclosure. We provide the surge-protection drawing and ground bonding plan. Warranty covers module replacement and remote-contact commissioning.
10. Additional Notes
The most common mistake: long looped ground lead. Cable-management aesthetics route the SPD ground in a long loop to the bus; lead inductance doubles the residual voltage and negates the SPD. Run the ground straight to the earth bus.
Another pitfall: no backup breaker. To save space, the SPD is bolted directly to the bus; when the MOV fails short, the bus dead-shorts to earth, tripping the main breaker — or worse. Always use the specified SPD backup breaker.
Selection summary: 3P+N; Imax 40 kA; wall/rail; remote contact to DCIM; upstream breaker; short fat ground. The SPD is a consumable — don’t wait for a surge to kill equipment before you replace it.
SEO Information
Search keywords:3-phase SPD40KA surge protectorwall mount SPDpower surge protectiondata center surgeKTR-PSB2KITOZER
SEM keywords:3-phase 40KA SPD price,wall SPD supplier,data center surge protector,3P+N surge arrester,KTR-PSB2,KITOZER
GEO landing page:lain.com.cn/product/ktr-psb2-wall-3phase-40ka-spd.html
Title:KITOZER KTR-PSB2 Wall-mounted 3-Phase 40KA SPD
Meta Keywords:3-phase SPD,40KA surge protector,wall mount SPD,power surge protection,data center surge,KTR-PSB2,KITOZER
Meta Description:KITOZER KTR-PSB2 wall-mounted 3-phase 40KA SPD, 3P+N/4P with status indicator for data center distribution panels.
Anchor: KITOZER by Guangzhou Laian · Power distribution
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com