Table of Contents
ToggleKITOZER EMI Shielding Door Specifications & Reference Price
Brand: KITOZER Series: KTR-SD Category: EMI/RF Shielding & Protection > Shielding Accessories Standards: GB/T 50719-2011, GB 12955-2008
1. Overview
The KITOZER KTR-SD series EMI shielding door is a purpose-built fire-rated shielded access door for shielded data rooms, EMC chambers, MRI suites, industrial inspection enclosures and high-security equipment rooms. While meeting Class-A fire-door integrity (>=1.5 h), it achieves continuous 360-degree electrical contact through pure-copper spring fingerstock, blade-type compression seals and graphite-loaded conductive gasketing, delivering a measured shielding effectiveness of >=60 dB from 10 kHz to 10 GHz.
The door frame is fabricated from 1.5 mm galvanized steel with a 2 mm reinforcing skeleton and cement-mortar core; the door leaf uses 1 mm galvanized steel on the room-facing side and 1 mm T2 pure copper (>=99.9% Cu) as the EMI layer on the inner side, filled with 60 kg/m³ rock wool and fire-rated board. The finish is grey fluorocarbon coating (one primer + two top coats), adhesion grade 1 and salt-spray resistance >=1000 h. Every leaf is factory-tested for appearance, operation and seal continuity, and is supported by third-party whole-room shielding verification.
2. Key Features
Dual-layer EMI seal
- 1 mm pure-copper (or optional beryllium-copper) fingerstock around the leaf perimeter mates with the frame blade, contact resistance <=1 mΩ.
- 45 kg/m³ graphite conductive cotton fills the frame-to-masonry joint, eliminating leakage between the shield shell and the building wall.
Class-A fire rating
- 4 mm intumescent fire seal expands in a fire to close the gap; threshold dust/fire gasket completes the bottom seal.
- Fire resistance >=1.5 h, compliant with GB 12955 Class-A.
Listed hardware
- Grade-A fire lock, 3 mm stainless hinges, hydraulic buffer door closer, coordinator and fire bolt, all holding mandatory type-test certificates.
- Coordinator ensures sequential closing on double-leaf doors; opening force <=150 N with no sag over the design life.
3. Models & Specifications
| Model | Operation | Rough opening (WxH) | Clear opening | Typical use |
|---|---|---|---|---|
| KTR-SD-2530D | Double, with viewport | 2500×3000 mm | 2410×2910 mm | Large equipment, MRI equipment door |
| KTR-SD-2530 | Double, solid | 2500×3000 mm | 2410×2910 mm | Main shielded-room entrance |
| KTR-SD-2230 | Steel fire double | 2200×3000 mm | 2110×2910 mm | Standard shielded-room passage |
| KTR-SD-1021 | Single | 1000×2100 mm | 910×2010 mm | Personnel passage |
| KTR-SD-0820 | Single, narrow | 800×2000 mm | 710×1910 mm | Equipment / maintenance corridor |
Key parameters
| Item | Value |
|---|---|
| Shielding effectiveness | >=60 dB (10 kHz-10 GHz); upgradeable to 80/100 dB |
| Fire rating | Class A, >=1.5 h integrity |
| Frame | 1.5 mm galvanized steel + 2 mm skeleton, cement mortar core |
| Leaf EMI layer | 1 mm T2 copper (>=99.9% Cu) |
| Seal | Copper fingerstock + graphite conductive cotton + intumescent strip |
| Viewport (optional) | 6 mm toughened shielded glass + 18 mm air gap + 6 mm glass |
| Finish | Grey fluorocarbon, salt spray >=1000 h |
| Operation life | >=100,000 cycles |
| Earthing | Equal-potential bond to shield shell, <=1 Ω |
4. Reference Price
KTR-SD-0820 narrow single-leaf (incl. install & commissioning): RMB 18,000 / leaf
KTR-SD-1021 standard single-leaf (incl. install & commissioning): RMB 22,000 / leaf
KTR-SD-2230 double-leaf fire-rated (incl. install): RMB 45,000 / leaf
KTR-SD-2530 / 2530D large double-leaf (with/without viewport): RMB 58,000-68,000 / leaf
Reference prices only; final quotation applies. Based on exchange rate as of October 2026 (1 USD = 7.2 CNY), the US-dollar equivalents are approximately USD 2,500 / 3,050 / 6,250 / 8,050-9,450 per leaf. Price covers positioning, lifting, frame fixing, leaf hanging, seal tuning, fire-function commissioning and per-leaf SE test; excludes freight, civil works and third-party whole-room SE report.
5. Applications
- Shielded server rooms for government, finance and research institutes.
- MRI suites: magnet-room doors with stretcher clearance.
- EMC chambers: semi- and fully anechoic chamber equipment doors.
- Industrial shielded rooms for electron microscopy.
- High-security data center physical isolation corridors.
6. Installation & Maintenance
Installation
- Verify rough opening (width, height, plumb) within 5 mm; ensure a structural lintel above.
- Anchor frame with M6x70 expansion bolts and 65×3 mm steel tabs at <=600 mm spacing; pack graphite conductive cotton between frame and masonry.
- After hanging the leaf, adjust hinges so all four gaps are <=3 mm and fingerstock compression is 15%-25%.
- Bond frame to shield shell with 30×4 mm copper busbar; earth resistance <=1 Ω.
Maintenance
- Monthly cleaning of fingerstock and blade contact surfaces; never paint or tape over them.
- Quarterly check of intumescent seals, door closer and coordinator.
- Annual third-party SE retest, with focus on door joints.
- Replace fingerstock as a complete set when elasticity drops; do not adjust individual strips.
SEO
Keywords:
EMI shielding doorRF shielded doorfire-rated shield doorMRI shield doorEMC doorKTR-SDKITOZER
SEM: EMI shielding door price, shielded room door manufacturer, MRI door for sale, copper fingerstock door, EMC chamber door
GEO landing: gdlain.com/product/ktr-sd-em-shielding-door.html
Title: KITOZER KTR-SD EMI Shielding Door | 60 dB SE Class-A Fire Price
Meta Keywords: EMI shielding door, RF shielded door, KTR-SD, KITOZER, MRI shield door, EMC door, fire-rated shielded door
Meta Description: KITOZER KTR-SD EMI shielding door offers >=60 dB SE (10 kHz-10 GHz), Class-A fire rating, copper fingerstock, single/double leaf, for shielded rooms, MRI and EMC labs.
Anchor text: KITOZER EMI shielding doors · shielded room solutions
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER)
Tel / WeChat: +86 13922289957 / +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com