Table of Contents
ToggleKITOZER Level-3 Classified Data Center Environment Monitoring System
Brand: KITOZER Series: KTR-DC Category: Environmental Monitoring > Data Center Environmental Monitoring
1. Overview
Under the Cybersecurity Law, Data Security Law and classified-protection regulations, data-center power & environment monitoring is a mandatory physical-security control. The KITOZER KTR-DC system uses a four-layer architecture — perception, acquisition, platform and application — to continuously monitor temperature/humidity, smoke, water leak, UPS, power distribution, CRAC units and access control with multi-channel alarming.
The KTR-DH-J1900 edge host (ARM dual-core 1 GHz, 8x RS485, 12x DI, 4x DO, 4G Cat.1) is the core; it supports domestic Kylin OS. The platform is pure B/S, accessible from any browser, with companion iOS/Android/HarmonyOS apps. Delivery is remote-commissioned, eliminating on-site cabling work and rapidly meeting Level-2 and Level-3 physical-environment compliance.
2. Key Features
Industrial-grade acquisition
- ARM dual-core Cortex-A7 1 GHz, 256 MB RAM, 8 GB eMMC, whole-unit power <=5 W.
- 8x RS485 (2 reassignable to RS232), 12x DI, 4x DO; 2 kV diff / 4 kV common-mode surge.
- Operating temperature -20 to +70 °C; 4G nationwide with offline buffering.
Plug-and-play sensors
- Temp/humidity: -20 to 80 °C, ±0.3 °C; 0-100% RH, ±3%, with local display.
- Photoelectric smoke: >=85 dB audible alarm, dry-contact output.
- Location leak module: 5 probes/module, response <3 s, DIN-rail mount.
Smart alarm & platform
- Four-tier alarm classification with siren, SMS, voice, app push and platform popup.
- B/S platform with 2D configuration, e-map, custom reports and cross-device trend curves.
- Scheduled self-test with SMS push; logs retained >=1 year for compliance audit.
3. Typical Configuration (110 m² Level-3 room)
| Device | Model | Qty | Key specs |
|---|---|---|---|
| Environment host | KTR-DH-J1900 | 1 | ARM A7 1 GHz, 8x RS485, 4G Cat.1 |
| Temp/humidity sensor | KTR-TH-01 | 6 | ±0.3 °C / ±3% RH, RS485 |
| Photoelectric smoke | KTR-SM-01 | 4 | >=85 dB, dry contact |
| Leak module | KTR-WL-01 | 2 | 5 probes/module, <3 s |
| Location leak cable | KTR-WC-10M | 2 | 10 m/set, 6 mm |
| SMS/voice module | KTR-SMS-4G | 1 | 4G, three carriers |
| Siren/strobe | KTR-AL-108 | 2 | >=108 dB, DC 12 V |
| SCADA software | KTR-DC-SCADA | 1 | B/S, Kylin compatible |
4. Reference Price
KTR-DH-J1900 host (incl. 4G, 8x RS485): RMB 6,600 / unit
Front-end sensor kit (6 TH + 4 smoke + 2 leak): RMB 4,800 / lot
KTR-DC-SCADA B/S platform (incl. remote deployment): RMB 5,000 / set
Complete 110 m² Level-3 package (incl. remote commissioning): RMB 25,000-35,000 / site
Reference prices only; final quotation applies. Based on exchange rate as of October 2026 (1 USD = 7.2 CNY), the complete-site equivalent is roughly USD 3,500-4,900. Price covers factory test, pre-installed software, remote parameter setup, system integration and 7-day remote support; excludes on-site cabling and sensor mounting.
5. Applications
- Level-2 / Level-3 classified rooms for government, finance, healthcare, education and energy.
- IDCs / modular data centers / cold-zone environment monitoring.
- 4G/5G base stations and aggregation rooms.
- Industrial sites and low-voltage substations.
6. Installation & Maintenance
Deployment
- Host 1U rack or DIN-rail in distribution box; AC 100-240 V wide-range input.
- RS485 bus daisy-chain, <=32 nodes/segment, 120 Ω terminator, shield grounded at one end.
- TH sensors placed in hot/cold aisles; leak cable below CRAC units, pipes and PDUs.
Commissioning & O&M
- Remote guidance for network bring-up, platform deployment, sensor addressing and threshold setup.
- Test four alarm channels, reports, self-test and app push; 7-day remote follow-up.
- Quarterly inspection of logs, battery voltage and 4G signal; annual sensor cleaning/calibration.
7. Compliance & integration notes
The KTR-DC platform is aligned with GB/T 22239 (Classified Protection Baseline), GB 50174 (Data Center Design) and YD/T 1363 telecom environment-monitoring norms. It delivers the physical-environment evidence required by assessors: continuous trend logs, threshold alarms with full time-stamps, operator/role permissions and exportable audit reports. The host speaks Modbus-RTU on RS485, so third-party sensors (UPS, precision cooling, PDUs, leak controllers) can be layered on without a gateway; the B/S server additionally publishes MQTT/HTTP northbound APIs for integration into DCIM or O&M clouds. Because the host supports domestic Kylin OS and the platform runs on Windows or Linux, the package fits both imported and self-controlled IT estates — a typical requirement for Level-3 environments. Remote commissioning keeps implementation lean: no on-site crew is required, and most sites are brought fully online within two working days once network and power are available.
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER)
Tel / WeChat: +86 13922289957 / +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com