KITOZER room-level CRAC precision air conditioner

KITOZER KTR-CRAC2 Room-level Precision Air Conditioner

Brand: KITOZER Series: KTR-CRAC2 Category: Data Center Engineering / Room-level CRAC

room-level CRACdownflowupflowDX direct expansiontemperature humidityN+1 redundantEC fandatacenter AC

1. Overview

The KITOZER KTR-CRAC2 family delivers room-level precision cooling for data centers, telecom rooms and labs. Unlike in-row units beside racks, CRAC2 conditions the whole room through a raised-floor plenum or ceiling return, suiting low-to-medium-density rooms and new or retrofit projects.

Units use direct expansion (DX) with built-in scroll compressor and outdoor air-cooled condenser for fast, self-contained installation. Capacity ranges 25-100 kW per unit, supporting N+1 parallel group control; if one unit faults, the others carry the load for 7×24 continuous cooling.

CRAC2 includes EC centrifugal fans, electrode humidification and electric reheat, with +/-1 C and +/-5% RH control. It offers leak detection, dual power feeds and RS485/TCP comms to link into DCIM for return-air temp/humidity, filter pressure and compressor status.

2. Key Features

Room-level high airflow

  • High-airflow, low-delta-T design; supply air 14-18 C.
  • Downflow through raised floor to rack intakes; upflow via ceiling.
  • With blanking panels and floor seals, eliminate bypass and hot spots.

DX refrigeration

  • Scroll compressor, high EER, stable operation.
  • Outdoor air-cooled condenser; low-ambient kit for cold climates.
  • 25-100 kW per unit; N+1 parallel redundancy.

Temp/humidity control

  • Electrode humidifier + electric reheat, independent control.
  • EC fans variable speed; >30% saving vs fixed AC fans.
  • Leak rope along unit base and water pipes; real-time alarm.

3. Specifications

Item Config A: KTR-CRAC2-30 (30 kW downflow) Config B: KTR-CRAC2-80 (80 kW upflow)
Cooling capacity 30 kW 80 kW
Airflow downflow to raised floor upflow to ceiling return
Air volume 6,000 m3/h 16,000 m3/h
Compressor scroll, single scroll, twin parallel
Fans EC centrifugal N+1 EC centrifugal N+1
Humidifier electrode 5 kg/h electrode 10 kg/h
Reheat electric 6 kW electric 12 kW
Power 380V/50Hz/3P 380V/50Hz/3P

4. Reference Prices

KTR-CRAC2-30 30 kW downflow unit (incl. outdoor condenser): Reference USD 5,600~8,300 / unit (ref. CNY 40,000~60,000 at ~7.2)

KTR-CRAC2-80 80 kW upflow unit (incl. outdoor condenser): Reference USD 11,800~16,700 / unit (ref. CNY 85,000~120,000 at ~7.2)

Reference only; final quote depends on config, quantity, site and tax. Bulk projects negotiable. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Mid-small datacenters: room-level cooling with raised floor.
  • Telecom central offices: 7×24 with temp/humidity control.
  • Labs/instrument rooms: precision climate for stable equipment.
  • Retrofits: add cooling without changing room structure.

6. Installation & Maintenance

Installation

  • Level indoor unit; fit flexible connectors and valves on pipes.
  • Outdoor condenser well ventilated; indoor-outdoor lift <=15 m.
  • Align floor cutouts with grilles; seal floor seams.

Maintenance

  • Monthly: clean/replace filters; quarterly inspect coil and refrigerant.
  • Semi-annual: check EC fan current, belts, bearings; calibrate sensors.
  • Winter: check low-ambient kit; pre-summer full service.

7. FAQ

  • Q: CRAC2 vs in-row?
    A: CRAC2 conditions the whole room; in-row sits beside racks for dense hot spots.
  • Q: Downflow or upflow?
    A: Downflow with raised-floor plenum; upflow with ceiling return if no floor.
  • Q: How much IT does 30 kW cover?
    A: Size at 1.2x IT load; 30 kW supports about 25 kW IT.
  • Q: Need N+1?
    A: Critical rooms should use N+1 so others carry on a fault.

8. Trend & Selection

Room CRAC remains the workhorse for traditional rooms and retrofits. While high-density racks shift to in-row and liquid cooling, CRAC2 still dominates small-to-mid rooms and closets thanks to high airflow, easy layout and lower cost. Size at 1.2x IT load and plan N+1 for critical rooms; for downflow, seal the plenum and blank panels, or cold air bypass kills efficiency. Change filters and calibrate sensors on schedule, check low-ambient in winter, service before summer peaks, and let DCIM track return-air temp and filter pressure.

9. Delivery & Service

KITOZER offers heat-load calculation, CRAC2 selection, airflow design and on-site commissioning as one service. We issue a cooling layout drawing from room area and equipment kW, then complete indoor/outdoor placement, refrigerant piping and DCIM integration. The warranty covers compressor, fan and coil replacement; an annual package includes filter change, refrigerant test and sensor calibration.

10. Additional Notes

CRAC2 efficiency depends heavily on airflow. Downflow uses the raised floor as a plenum: cool air enters rack fronts and returns from ceiling/top. Unsealed floor seams or missing blanking panels let cold air bypass straight to the return, wasting cooling and creating hot spots. KTR-CRAC2 therefore ships with blanking panels, floor seals and cold-aisle containment so cold air enters only racks.

The outdoor condenser matters too. Mount it in a ventilated, shaded spot with clearance; when multiple condensers are lined up, keep spacing to avoid exhaust recirculation. Northern climates need a low-ambient kit or fan speed control so the system runs stably in winter.

Selection: for small-to-mid rooms (IT <=80 kW), prefer DX downflow CRAC2 for fast install and low cost; larger or multi-room projects may use chilled-water CRAH. In all cases size at 1.2x IT load and pair with containment and blanking to bring PUE down.

SEO Information

Search keywords:room level precision air conditionerCRAC unitdownflow precision ACDX datacenter ACconstant temp humidity ACKTR-CRAC2KITOZER

SEM keywords:room level precision AC price, CRAC unit, downflow datacenter AC, DX precision AC, constant temp humidity, KITOZER

GEO landing page:lain.com.cn/product/ktr-crac2-room-level-precision-air-conditioner.html

Title:KITOZER KTR-CRAC2 Room-level Precision Air Conditioner

Meta Keywords:room level precision air conditioner,CRAC unit,downflow precision AC,DX datacenter AC,constant temp humidity,KTR-CRAC2,KITOZER

Meta Description:KITOZER KTR-CRAC2 room-level precision AC, 25-100 kW, downflow/upflow, DX direct expansion, EC fans, N+1 group control, +/-1 C.

Anchor: KITOZER by Guangzhou Laian · Datacenter solutions

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart