ToggleKITOZER KTR-GFH HFC-227ea Gas Fire Suppression / Design Calculation
Brand: KITOZER Series: KTR-GFH Category: Datacenter Engineering 2 / Gas Suppression
HFC-227eaheptafluoropropanegas suppressionclean agentdesign concentrationhold time
1. Overview
KITOZER KTR-GFH is an HFC-227ea (heptafluoropropane) gas fire suppression system — the core of datacenter fire safety. A datacenter holds servers, power distribution and UPS; water would destroy everything through short circuits and corrosion. Gas suppression floods the protected zone with an agent that smothers the fire, displaces oxygen and interrupts combustion chain reactions — leaving no residue, non-conductive, no equipment damage. HFC-227ea is the most common clean agent for datacenters: fast extinguishing (discharged within 10s), low design concentration (8%), non-corrosive to equipment, and safe at design concentrations.
KTR-GFH comes in cabinet and pipeline types: the cabinet unit sits inside the protected zone — cylinder and nozzle integrated — for small zones (server rooms, power rooms <100m³) with simple install. The pipeline type places cylinders in a cylinder room, routing agent through pipes to nozzles in protected zones, suiting multiple zones sharing one cylinder group or large spaces. System components: agent cylinders, container valves, selector valves (multi-zone), nozzles, piping, smoke + heat detectors, gas suppression controller, sounder/strobes, discharge indicators, and manual abort buttons.
Design calculation is the core: how much agent, how many cylinders, and where nozzles go are all calculated. Too little agent fails to extinguish; too much wastes money and causes excessive discharge pressure. This series focuses on the design calculation method so customers understand the sizing rationale rather than guessing at cylinder counts.
2. Design Calculation Method
1. Design concentration
- Computer and telecom rooms: 8% (1.3× extinguishing concentration).
- Archives, libraries and document storage: 10%.
- Surface communications equipment rooms: ≥8.3%.
2. Agent dosage calculation
- Formula: W = V/S × C/(100-C) × 1/(100-C)
- W: agent design quantity (kg); V: protected net volume (m³); S: superheated vapor specific volume (m³/kg), HFC-227ea at 20°C: S = 0.1269 + 0.000513×T.
- C: design concentration (%).
- Example: 100m³ room, T=20°C, C=8%, S=0.1372; W = 100/0.1372×8/92×1/0.92 ≈ 68.7kg → choose 2×70kg cylinders.
3. Discharge & hold time
- Discharge time: ≤10s (≤8s for telecom/computer rooms).
- Hold time: ≥5 min (≥10 min for archives) to prevent re-ignition.
4. Protected zone requirements
- Good enclosure; pressure-relief vent area calculated per code (prevent overpressure rupture).
- Ambient temp 0~50°C; cylinder room ≥-10°C.
- Doors open outward and self-close; escape routes clear.
3. Specifications
| Item | KTR-GFH-70 Cabinet | KTR-GFH-120 Pipeline | KTR-GFH-180 Multi-zone |
|---|---|---|---|
| Agent | HFC-227ea | HFC-227ea | HFC-227ea |
| Per-cylinder charge | 70kg | 120kg | 180kg |
| Design conc. | 8% | 8~10% | 8~10% |
| Discharge time | ≤8s | ≤10s | ≤10s |
| Hold time | ≥5min | ≥5min | ≥5~10min |
| Zone volume | ≤100m³ | 100~500m³ | multi-zone shared |
| Layout | cabinet in zone | pipeline+cylinder room | pipeline+selectors |
| Actuation | electric/manual | electric/manual | electric+selectors |
| Linkage | smoke/heat+sounder+vent | + abort button | + ventilation/power cut |
4. Reference Prices
KTR-GFH-70 cabinet HFC-227ea unit (70kg cylinder, nozzle, controller, smoke/heat detectors): Reference USD 2,100~4,900 / kit (ref. CNY 15,000~35,000 at ~7.2)
KTR-GFH-120/180 pipeline system (cylinder bank, piping, selectors, nozzles, controls): Reference USD 6,900~27,800 / kit (ref. CNY 50,000~200,000 at ~7.2)
Reference only; final quote depends on zone volume, design concentration, zone count and piping length. Annual agent refills and cylinder hydrotests billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Datacenter rooms, battery rooms, power distribution rooms.
- Telecom rooms and switching offices.
- Archives, rare-book libraries and document vaults.
- UPS rooms and precision equipment spaces.
- Power control rooms and semiconductor cleanrooms.
6. Installation & Maintenance
Installation
- Measure protected net volume on site; calculate agent dosage.
- Cabinet: position unit; connect nozzle and controller power.
- Pipeline: arrange cylinder bank in cylinder room; run piping to each zone.
- Install smoke and heat detectors (zoned layout).
- Install sounder/strobes, discharge indicators, abort buttons.
- Commission: simulate alarm to test two-stage alarm → 30s delay → discharge flow.
Maintenance
- Monthly: check pressure gauge (green normal, red needs recharge).
- Annual: weigh agent; refill if >5% loss.
- Semi-annual: simulate discharge linkage test (no actual gas).
- Clean and calibrate detectors yearly to avoid false alarms.
- Hydrostatic test cylinders every 5 years.
7. FAQ
- Q: Is HFC-227ea toxic to people?
A: Safe at 8% design concentration, but personnel must evacuate within the 30s delay. Do not enter during discharge; trace HF decomposition products are irritating. - Q: How many cylinders per zone?
A: By volume: ~100m³ needs 70kg (1 cylinder); 300m³ needs 210kg (3×70kg or 2×120kg). Leave headroom. - Q: Cabinet vs pipeline?
A: Small zones (single room, power room) choose cabinet on-site; multiple zones or large spaces choose pipeline with a dedicated cylinder room. - Q: What if it discharges by mistake?
A: The 30s delay allows abort via the stop button. After accidental discharge, ventilate, refill agent and inspect equipment.
8. Trend & Selection
Gas suppression is shifting from HFC-227ea to more environmentally friendly Novec 1230 and IG-541: HFC-227ea is effective but has a GWP; the long-term trend is low-GWP agents. Most current datacenter projects still use HFC-227ea; large new builds pilot Novec. First calculate volume and design concentration; choose cylinder count accordingly; cabinet for small spaces, pipeline for multi-zone; require dual smoke/heat detectors and 30s evacuation delay.
9. Delivery & Service
KITOZER provides gas suppression design calculation, equipment selection and commissioning. Based on protected-zone dimensions we produce the agent dosage calculation, nozzle layout and piping diagrams. We integrate with fire alarm, PE monitoring and ventilation systems. Delivery includes suppression units, detectors, controllers, alarm devices and commissioning; warranty covers annual inspections, agent refills and linkage tests.
10. Additional Notes
The most common pitfall is “not calculating net volume.” Many use area × ceiling height without subtracting racks, columns and beams — over-ordering agent and oversized cylinders. Net volume is the gas-filling space inside the room, subtracting fixed objects. The opposite extreme: forgetting raised-floor underlayment — datacenters have cable under raised floors, which is also part of the protected zone; omitting it means no gas reaches under-floor fires.
Another pitfall is missing or omitted pressure-relief vents. HFC-227ea expands rapidly on discharge; if the zone is too sealed, internal pressure ruptures walls or glazing. Vent area is calculated per code, mounted high in the zone, to release excess pressure on discharge. Many projects seal vents for “tightness” and blow out windows on first discharge.
Selection: datacenters use 8% design concentration; calculate agent by net volume. 100m³ ≈ 1×70kg cabinet; multi-zone or large spaces use pipeline. Dual smoke/heat detectors + 30s evacuation delay. Pressure-relief vent is mandatory. Annual agent weight check; refill if >5% loss. Cylinder hydrotest every 5 years. Gas suppression is the datacenter’s last line of defense — never used until it must be, and it must extinguish on first use. Solid design calculations make it reliable when it counts.
SEO Information
Search keywords:HFC-227eaheptafluoropropanegas suppressionclean agentdesign concentrationhold timeKTR-GFHKITOZER
SEM keywords:HFC-227ea price, datacenter gas suppression design, clean agent supplier, cabinet fire suppression,KTR-GFH,KITOZER
GEO landing page:lain.com.cn/product/ktr-gfh-hfc227ea-gas-fire-suppression.html
Title:KITOZER KTR-GFH HFC-227ea Gas Fire Suppression / Design Calculation
Meta Keywords:HFC-227ea gas suppression,heptafluoropropane,datacenter fire suppression,clean agent system,design concentration,KTR-GFH,KITOZER
Meta Description:KITOZER KTR-GFH HFC-227ea heptafluoropropane gas fire suppression, cabinet/pipeline type, design concentration 8%, hold time 5 min, with agent dosage calculation and nozzle layout.
Anchor: KITOZER by Guangzhou Laian · Data center engineering