ToggleKITOZER KTR-RAC Server Rack Airflow / Front-to-Back Duct System
Brand: KITOZER Series: KTR-RAC Category: Modular Cold Aisle 2 / Rack Ducting
rack coolingfront-to-backrack fan unitblanking panelhot/cold isolation
1. Overview
KITOZER KTR-RAC is a set of airflow accessories that solve the problem of “hot air recirculation” inside server racks. Most data center servers draw cool air in the front and exhaust hot air out the back. The trouble is inside the rack and between racks: if the rack lacks blanking panels, empty U-spots let hot exhaust from the back recirculate to the front (hot air recirculation), get sucked back in by the servers ahead, and create a vicious cycle that overheats and crashes local equipment.
KTR-RAC closes the path “cool air in, hot air out”: blanking panels seal all empty U-spots on the rack front (cold aisle side) so hot exhaust can’t cross back from the rear; a rack fan unit (RFU) on the rear door or top actively pulls hot air toward the hot aisle or exhaust duct; bottom and top gaps are sealed with brushes/gaskets. Now cool air enters only through server fronts, hot air exits only at the rear, with no mixing.
This system is the “last meter” of cold/hot aisle containment: the macro environment may already have aisle containment (front/rear doors sealed across a row), but if individual racks don’t isolate internally with blanking panels and fans, cool air still leaks through empty U-spots. KTR-RAC refines isolation down to each rack and each U. It suits high-density racks (8kW+ per rack), blade servers, and retrofits in older halls without aisle containment.
2. Key Features
Front-to-back guidance
- All server intakes face the cold aisle; exhaust faces the hot aisle.
- Internal baffles/duct plates guide airflow straight over equipment.
- Eliminates cross-flow and dead corners.
Blanking & sealing
- 1U/2U metal blanking panels seal empty U-spots and block recirculation.
- Brush gaskets (top/bottom/sides) close gaps.
- Panels match rack color for a clean look.
Rack fan unit (RFU)
- Mounted on rear door or top; axial/centrifugal fans.
- Sized by rack heat load (200~800 CFM per fan).
- Thermostatic speed control: fans ramp up by intake temperature to save energy and noise.
Top/side exhaust
- Top exhaust duct sends hot air straight to the ceiling hot aisle.
- Side exhaust for racks against walls.
- Optional return hose to CRAH return.
3. Specifications
| Item | KTR-RAC-2 | KTR-RAC-5 | KTR-RAC-8 |
|---|---|---|---|
| Rack heat load | ≤4kW/rack | 4~8kW/rack | 8~15kW/rack |
| Blanking panels | 1U ×10 | 1U ×20 | 1U/2U ×30 |
| Rack fan units | 1 group (2 fans) | 1 group (4 fans) | 2 groups (8 fans) |
| Airflow per group | 400 CFM | 800 CFM | 1600 CFM |
| Fan speed control | Fixed | Thermostatic | Thermostatic + RS485 |
| Sealing | Top/bottom brush | Top/bottom/side brush | Full seal + baffles |
| Exhaust mode | Rear direct | Rear/top | Top duct to hot aisle |
| Noise | ≤55dB(A) | ≤60dB(A) | ≤65dB(A) |
4. Reference Prices
KTR-RAC-2 low-density rack duct kit (10 blanking panels, 2-fan RFU, top/bottom brushes): Reference USD 208~486 / rack (ref. CNY 1,500~3,500 at ~7.2)
KTR-RAC-5/8 high-density rack duct system (blanking, 4~8-fan RFU, thermostatic, full seal, top exhaust): Reference USD 694~2,083 / rack (ref. CNY 5,000~15,000 at ~7.2)
Reference only; final quote depends on per-rack configuration. RFU, blanking, brushes and ducting priced separately; row-level discounts available. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- High-density server racks (8kW+) cooling upgrade.
- Blade and GPU server racks.
- Older hall duct retrofits (no aisle containment).
- Racks against walls needing side exhaust.
- Hot/cold mixing and local hot-spot remediation.
6. Installation & Maintenance
Installation
- Confirm front-to-back layout; all equipment intakes face front.
- Fit blanking panels to every empty U; snap in place.
- Apply brush gaskets top/bottom/sides to close gaps.
- Mount RFU on rear door or top; power (220V or 48V).
- Place thermostat probe at mid intake; set trigger (e.g. start at 27℃).
- Connect top exhaust duct to hot aisle or ceiling return.
- Test: intake-to-exhaust temperature difference should be ≥10℃ with no recirculation.
Maintenance
- Clean RFU intake filters regularly; wash when airflow drops.
- Verify blanking panels aren’t removed (empty U must stay sealed).
- Replace fans on noise or stoppage.
- Check intake temperature; if hot spot persists, increase airflow.
- Re-fit gaskets when aged or detached.
7. FAQ
- Q: We already have cold aisle containment — is rack ducting still needed?
A: Yes. Aisle containment solves the row-level problem, but empty U-spots cause internal recirculation; blanking and RFU are the rack-level final isolation. - Q: Do blanking panels really help?
A: Yes. Measured intake temperatures near empty U-spots can drop 3~8℃ after blanking — the lowest-cost cooling improvement. - Q: Are fans noisy?
A: Fixed-speed fans are louder; choose thermostatic models: low speed and quiet when cool, ramp up only when hot. RS485 models allow remote speed monitoring. - Q: How many fans per rack?
A: By heat load: ~2 fans for 4kW, ~4 for 8kW, ~8 for 15kW; lean toward more but match CRAH cooling capacity.
8. Trend & Selection
Rack cooling evolves from “letting the AC blow” toward “fine ducting + liquid cooling”: high-density racks (20kW+ per rack) push air cooling to its limit and adopt rear-door heat exchangers or liquid cooling. But in air-cooled halls, KTR-RAC-style low-cost “blanking + RFU + sealing” retrofits still deliver immediate results. The trend is RS485-monitored fans linked to DCIM for temperature tuning. Calculate per-rack heat load (sum equipment watts); blank every empty U (cheapest cooling); add thermostatic RFU for dense racks; seal gaps; route top exhaust to the hot aisle; verify intake/exhaust delta; choose fans with washable filters.
9. Delivery & Service
KITOZER provides rack duct selection: based on per-rack power, U occupancy and existing CRAH capacity, we configure blanking count, RFU airflow and exhaust mode. We produce rack ducting layout drawings (blanking positions, fan location, exhaust routing). Bundled with racks, aisle containment and in-row cooling. Delivery includes blanking panels, RFU fan units, brush gaskets, baffles, exhaust hoses and accessories. Warranty covers fan speed tuning and hot-spot remediation.
10. Additional Notes
The most common pitfall is “empty U-spots with no blanking.” A rack holds 8 servers but 10 empty U-spots above, no blanking. Hot exhaust recirculates through the empty spots to the front, gets sucked back in by lower servers — hotter air sucked in, sucking hotter air — classic recirculation. Blanking panels cost very little (tens of yuan each) yet deliver immediate results. Rule: every empty U must have a blanking panel; whoever removes it must put it back.
Another pitfall: “fans installed but filters clogged.” Over time, RFU intake filters accumulate dust and airflow shrinks unnoticed. Only at summer highs does the intake hit 40℃ and reveal the fans are barely turning. Recommend: remove and wash filters quarterly; monitor fan speed.
Selection summary: size blanking and fans by heat load; blank every empty U; thermostatic RFU for dense racks; seal gaps; route top exhaust to the hot aisle; wash filters quarterly; intake/exhaust delta ≥10℃ is a pass. Ducting is the rack’s breathing pipe — clear pipes keep servers from heatstroke.
SEO Information
Search keywords:rack coolingfront-to-backrack fan unitblanking panelhot/cold isolationrecirculation fixKTR-RACKITOZER
SEM keywords:rack airflow duct price,rack fan unit supplier,front-to-back blanking panels,high-density rack cooling,KTR-RAC,KITOZER
GEO landing page:lain.com.cn/product/ktr-rac-rack-airflow-front-to-back.html
Title:KITOZER KTR-RAC Server Rack Airflow / Front-to-Back Duct System
Meta Keywords:rack airflow,front-to-back cooling,rack fan unit,blanking panel,hot aisle containment,KTR-RAC,KITOZER
Meta Description:KITOZER KTR-RAC server rack airflow system with front-to-back duct, rack fan unit, blanking panels and roof exhaust to isolate hot/cold air and improve rack cooling.
Anchor: KITOZER by Guangzhou Laian · Environmental monitoring systems
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com