ToggleKITOZER KTR-IUPS Industrial Online Double-Conversion UPS
Brand: KITOZER Series: KTR-IUPS Category: Power Distribution 2 / Industrial UPS
industrial UPSonline double-conversionhigh power UPSUPS parallelbypass redundancy
1. Overview
KITOZER KTR-IUPS is a high-capacity uninterruptible power supply designed for data centers, industrial production lines and large equipment. Unlike small tower/rack UPS units (articles 7/35, 1~10kVA feeding a single server or office device), KTR-IUPS is “industrial-grade, high-power, parallel-capable” — from 10kVA to 500kVA, powering whole rack rows, whole lines or entire rooms.
“Online double-conversion” is the UPS operating mode: mains input is first rectified to DC (first conversion), then inverted back to clean AC output (second conversion). Whether mains is present or lost, the load is always fed by the inverter — mains normal: rectifier feeds and charges the battery; mains lost: seamless switch to battery with zero transfer time (because output is always inverted). This differs fundamentally from a “standby” UPS (mains passes through normally, inverter only kicks in on outage): online output is purified sine wave, with voltage fluctuation, surge and harmonics filtered out.
KTR-IUPS emphasizes industrial reliability: bypass redundancy (auto-transfer to bypass if inverter fails, mains feeds load directly without interruption), parallel redundancy (multiple UPS in parallel; one fails, others carry the load), battery management (smart charging, battery inspection, temperature compensation) and rich communication (RS485/SNMP card to DCIM). Suited to scenarios demanding high continuity and power quality: financial data centers, industrial automation lines, medical equipment, telecom hubs.
2. Key Features
Online double-conversion
- Rectifier + inverter; load always inverter-fed.
- 0ms transfer; pure sine-wave output.
- Filters voltage fluctuation, surge, harmonics.
High power & parallel
- Capacity 10~500kVA (by model).
- Multi-unit parallel (N+1 redundancy).
- Output power factor 0.9~1.0.
Bypass & protection
- Static bypass + maintenance bypass; inverter fault doesn’t interrupt load.
- Overload, short-circuit, over-temperature protection.
- High input power factor (≥0.99); low grid pollution.
Battery & monitoring
- Smart charge management, battery inspection, temp compensation.
- External battery bank; runtime as configured.
- RS485/SNMP/dry contacts to DCIM platform.
3. Specifications
| Item | KTR-IUPS-20 | KTR-IUPS-100 | KTR-IUPS-300 |
|---|---|---|---|
| Capacity | 20kVA | 100kVA | 300kVA |
| Output PF | 0.9 | 0.9 | 0.9~1.0 |
| Mode | Online double-conv. | Online double-conv. | Online double-conv. |
| Parallel | Optional | Up to 4 units | Up to 8 units |
| Bypass | Static+maint. | Static+maint. | Static+maint. |
| Efficiency | ≥95% | ≥96% | ≥96% |
| Battery | Internal/ext. | External bank | External banks |
| Communication | RS485+SNMP | RS485+SNMP+dry | RS485+SNMP+parallel |
4. Reference Prices
KTR-IUPS-20 20kVA online UPS (internal battery, ~15 min standard runtime): Reference USD 2,083~5,556 / unit (ref. CNY 15,000~40,000 at ~7.2)
KTR-IUPS-100/300 industrial high-power UPS (100~300kVA, parallel redundancy, battery bank excluded): Reference USD 11,111~69,444 / unit (ref. CNY 80,000~500,000 at ~7.2)
Reference only; final quote depends on capacity, parallel count and runtime (battery bank size). Battery bank (batteries) priced separately; installation and distribution breakers extra. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Data center rack rows and room high-power supply.
- Industrial automation lines and PLC control systems.
- Financial and securities trading rooms.
- Medical equipment (CT, MRI) uninterruptible supply.
- Telecom hubs and aggregation sites.
6. Installation & Maintenance
Installation
- Size UPS capacity by load (total power ×1.2~1.5 margin).
- Decide parallel (N+1: 3 units, 2 load, 1 backup).
- Position UPS: heavy; build load-bearing footing, add isolators.
- Wire mains input and output (to load distribution).
- Connect battery bank (polarity, voltage match).
- Run communication (RS485/SNMP) to DCIM.
- Commission: mains/battery transfer test, parallel current sharing, bypass transfer.
Maintenance
- Check battery voltage and internal resistance regularly (batteries are the weak link).
- Annual battery discharge test (capacity verification).
- Clean UPS cooling filters and fans.
- Inspect terminals for heating.
- Address UPS alarms promptly; export logs periodically.
7. FAQ
- Q: Industrial UPS vs small UPS?
A: Small UPS (1~10kVA) feeds a single device; industrial (10kVA+) is high-power, parallel-capable, with bypass redundancy, feeding rows/buildings. Different reliability tiers. - Q: Online vs standby?
A: Online double-conversion outputs clean power with 0ms transfer for critical loads; standby (offline) is cheap but has transfer breaks and lower output quality for ordinary gear. Critical rooms choose online. - Q: How to set runtime?
A: By battery bank size: 15 min / 30 min / 1 hr. Depends on whether a diesel generator exists (with generator, 15 min suffices to start it; without, longer backup). - Q: Why parallel?
A: Parallel (N+1 redundancy): if one UPS fails, others carry the load without interruption. A single UPS is a single point of failure; parallel greatly improves reliability.
8. Trend & Selection
UPS evolves from “transformer-based (heavy, line-frequency)” to “transformerless (efficient, high-frequency)”: modern data centers use high-frequency online UPS, efficient (≥96%) and compact; the trend is modular UPS (pluggable power modules, online expansion), lithium batteries (replacing lead-acid), and linkage with renewables (PV/genset). Select capacity by load ×1.2~1.5; critical loads choose N+1 parallel; runtime by genset configuration; battery bank (lead-acid or lithium) by runtime; choose high efficiency (saves power); include SNMP to DCIM; periodically capacity-test batteries.
9. Delivery & Service
KITOZER provides industrial UPS selection: based on total load, runtime and parallel requirements, we calculate capacity and battery bank configuration. We produce UPS system diagrams (mains input, parallel, battery bank, output distribution). Bundled with distribution cabinets, battery banks and DCIM. Delivery includes UPS unit, (optional) battery bank, parallel cables, communication card and mounting accessories. Warranty covers parallel commissioning and battery capacity testing.
10. Additional Notes
The most common pitfall is “batteries never tested — only discovered dead when mains fails.” The UPS unit is fine, but the battery bank floats for years without discharge testing — when mains actually fails, the batteries can’t hold charge, the UPS shuts down after minutes, and the load still goes down. Batteries are the UPS’s weakest link; must run an annual discharge capacity test: disconnect mains, let batteries carry the load, measure actual runtime, and replace weak cells.
Another pitfall: “undersized capacity.” The UPS is sized for the existing load, but later equipment is added and the UPS runs fully loaded or overloaded. Overloaded UPS runs inefficiently, runs hot and fails easily. Select capacity with 1.2~1.5× margin for future expansion.
Selection summary: online double-conversion (clean, 0ms transfer); size by load ×1.2~1.5; critical loads N+1 parallel; runtime by genset; annual battery capacity test; choose efficient high-frequency; SNMP to DCIM. The UPS is the data center’s lifeline — a reliable lifeline makes power failures survivable.
SEO Information
Search keywords:industrial UPSonline double-conversionhigh power UPSUPS parallelbypass redundancyuninterruptible powerKTR-IUPSKITOZER
SEM keywords:industrial UPS price,online double-conversion UPS supplier,high power parallel UPS,data center UPS,KTR-IUPS,KITOZER
GEO landing page:lain.com.cn/product/ktr-iups-industrial-online-double-conversion.html
Title:KITOZER KTR-IUPS Industrial Online Double-Conversion UPS
Meta Keywords:industrial UPS,online double-conversion,high power UPS,UPS parallel,uninterruptible power supply,KTR-IUPS,KITOZER
Meta Description:KITOZER KTR-IUPS industrial online double-conversion UPS, 10~500kVA, with online double conversion, bypass redundancy, battery management for data centers and industrial loads.