Table of Contents
ToggleKITOZER KTR-PH Precision CRAC Humidifier / Electrode Steam
Brand: KITOZER Series: KTR-PH Category: Environmental Monitoring 2 / CRAC Accessory
data center humidifierelectrode steamCRAC cylinderhumidity controlKTR-PH

1. Overview
The KITOZER KTR-PH humidifier is the matched humidification component inside a precision CRAC unit. A data center is a dry place: cooling dehumidifies, servers exhaust heat, and winter heating dries the air further. When relative humidity drops below 30% RH, static electricity builds up — dust clings to boards, and a human touch can spark a discharge that damages chips. Above 60% RH, condensation and corrosion appear. The sweet spot is 40–60% RH, and KTR-PH keeps it there.
The flagship model is an electrode steam humidifier: a removable PP/stainless cylinder with two electrodes. Tap water acts as the conductive medium; current heats it to boiling, and the steam is ducted into the CRAC airstream and carried into the room. Electrode type likes hard water — the harder the water, the better it conducts and the faster it generates steam. Maintenance is simply cylinder replacement: scale builds on the wall, the wall thickens, resistance rises, output drops, and a fresh cylinder solves it. A wetted-pad (evaporative) version is also offered for small rooms or where steam is unwanted.
The humidifier does not run alone; the CRAC controller reads the return-air humidity sensor and drives it: below 45% RH, electrodes heat; above 55%, they stop. A fill solenoid adds water; a drain valve periodically flushes concentrated brine to control scale. Outputs come in 5/10/15/30 kg/h for CRAC units from 5 kW to 100 kW.
2. Key Features
Humidification method
- Electrode steam (mainstream): fast response.
- Wetted-pad evaporative: no steam, no mist, quiet.
- Both link to CRAC board (dry contact or 0–10V).
Capacity
- 5/10/15/30 kg/h tiers.
- Steam diffuses naturally, no fan needed.
- Stepped or modulating output.
Water path & control
- Auto fill solenoid with float level.
- Auto drain (by timer or cumulative volume).
- Low-water and over-current protection.
Compatibility
- Generic cylinder fits major CRAC brands.
- Retrofit bracket for older units.
- Optional Modbus to DCIM host.
3. Specifications
| Item | KTR-PH-05 | KTR-PH-10 | KTR-PH-15 | KTR-PH-30 |
|---|---|---|---|---|
| Method | Electrode steam | Electrode steam | Electrode steam | Electrode steam |
| Output | 5 kg/h | 10 kg/h | 15 kg/h | 30 kg/h |
| CRAC match | 5-15 kW | 15-30 kW | 30-60 kW | 60-100 kW |
| Power | 220V/1.5kW | 220V/3kW | 380V/4.5kW | 380V/9kW |
| Water in | Tap DN15 | Tap DN15 | Tap DN20 | Tap DN20 |
| Control | Dry/0-10V | Dry/0-10V | Dry/0-10V | Dry/0-10V |
| Cylinder life | 3-6 months | 3-6 months | 3-6 months | 3-6 months |
4. Reference Prices
KTR-PH-05 electrode humidifier (5 kg/h, cylinder + fill + drain): Reference USD 250~490 / set (ref. CNY 1800~3500 at ~7.2)
KTR-PH-15/30 high-capacity (15-30 kg/h, 380V, cylinder + control): Reference USD 625~1250 / set (ref. CNY 4500~9000 at ~7.2)
Reference only; final quote depends on capacity and water quality. Spare cylinders are about USD 20~55 each, replaced every 3-6 months. Wetted-pad models are slightly cheaper. Works with the CRAC controller. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Built-in humidification inside mid/large data-center CRAC.
- Telecom rooms and core base stations in dry winters.
- Archives, libraries, museums (constant humidity).
- Electronics workshops and clean rooms (anti-static).
- Hospital ICUs and operating theaters.
6. Installation & Maintenance
Installation
- Size output to CRAC capacity (5/10/15/30 kg/h).
- Mount cylinder in the CRAC compartment; connect electrode power.
- Feed water from condensate return or tap; add a Y-strainer.
- Drain to floor with a P-trap to prevent odor.
- Insulate the steam pipe; guard against burns.
- Wire control to CRAC humidification output (dry/0-10V).
- Test: force heat; watch steam, fill, drain.
- Set target RH (45-50%) and verify return-air stability.
Maintenance
- Clean the fill strainer monthly.
- Replace cylinder every 3-6 months (scale slows output).
- Check drain solenoid action.
- Repair damaged steam-pipe insulation.
- Add a water softener in hard-water areas to extend cylinder life.
7. FAQ
- Q: Why tap water instead of pure water?
A: Electrode heating relies on conductivity; pure water conducts nothing and won’t heat. Tap water is required. That is why hard water actually works better. - Q: How often to replace the cylinder?
A: Depends on water. Hard water: 3 months; soft: 6 months. Replace when output drops, current falls, or “low efficiency” alarm appears. - Q: Electrode vs wetted pad?
A: Large space / fast response: electrode. Small room / quiet / no cylinder changes / good water: wetted pad. Data centers mainly use electrode for speed and simple swaps. - Q: What if the humidifier leaks?
A: Usually a stuck fill valve (always open) or a loose fitting. CRAC has a drain pan and leak sensor linked to DCIM. Inspect fittings and valves periodically.
8. Trend & Selection
Humidification is moving from “on-off steam” to precise demand-based control: traditional CRAC overshoots to 60% RH then the AC dehumidifies, wasting both cooling and water. The trend is narrow-band control around 40–50% RH, linked to free cooling and AI tuning to cut PUE. Mist-free methods (wetted pad, high-pressure micro-mist, ultrasonic) gain where air quality matters. Selection: size output by CRAC kW (roughly 1–2 kg/h per 10 kW); electrode first; factor in cylinder cost for hard water; drain to floor; strain the fill; tie to the CRAC controller rather than running it standalone.
9. Delivery & Service
KITOZER sizes the humidifier by CRAC model, cooling capacity, site water (tap vs softened) and target RH. Supplied with KTR CRAC units or as standalone cylinders and retrofit kits for older units. Delivery includes cylinder, electrodes, fill/drain solenoids, control harness, bracket, and manual. Electrode and cylinder defects are replaced free in warranty.
10. Additional Notes
The common mistake is “managing temperature but not humidity.” Small rooms often have cooling but no humidification; in winter RH falls below 20%, servers keep running, yet static, dust adhesion and insulation creep build up. When a board shorts or a drive fails, people finally check humidity. Every manned room should have an RH sensor in DCIM with a low alarm at 35% RH.
Another pitfall is an uninsulated steam pipe. A bare 100°C pipe burns people, sweats externally, and drips into racks. Insulate it and P-trap the drain.
Also: a drain valve that never fires. If the drain is blocked or the valve seized, scale accumulates and output halves within six months. Manually trigger a drain once a month to confirm water actually leaves.
Summary: size by CRAC kW; electrode mainstream, pad optional; strain the fill, P-trap the drain, insulate steam; target ~45% RH; swap cylinders and clean strainers on schedule. The humidifier is the most unnoticed part of a CRAC — but one bucket of steam protects a whole row of servers from static damage.
SEO Information
Search keywords:data center humidifierelectrode steam humidifierCRAC cylinderhumidity controlKTR-PHKITOZER
SEM keywords:data center humidifier price,electrode steam supplier,CRAC humidifier cylinder replacement,data center RH control,KTR-PH,KITOZER
GEO landing page:lain.com.cn/product/ktr-ph-electrode-humidifier-crac.html
Title:KITOZER KTR-PH Data Center Precision CRAC Humidifier / Electrode Steam
Meta Keywords:data center humidifier,electrode steam humidifier,CRAC humidifier cylinder,data center humidity control,KTR-PH,KITOZER
Meta Description:KITOZER KTR-PH electrode steam humidifier for precision CRAC, 5-30 kg/h, auto fill and drain, controls 40-60% RH, for data centers and telecom rooms.
Anchor: KITOZER by Guangzhou Laian · Environmental monitoring systems
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com