KITOZER data center monitoring mobile app software

KITOZER KTR-MA Data Center Monitoring Software & Mobile App

Brand: KITOZER Series: KTR-MA Category: Environmental Monitoring 2 / Software Platform

monitoring softwaremobile appDCIMcloud platformKTR-MA

1. Overview

KITOZER KTR-MA room environment monitoring software plus mobile app is the upper-computer platform that consolidates every sensor, UPS, AC and power unit in a room. Sensors, UPS and AC each collect and display locally; KTR-MA aggregates them for central viewing, alarming and history. It runs on a control-room PC (Windows) and ships with a mobile app (iOS/Android), so managers see temperature, humidity, UPS battery voltage and leak alarms from their phone.

Software and app are two ends of one system: the PC end is full-featured for configuration, reports, history curves and multi-room management; the mobile end is for “on-the-go” viewing, pushing alarms via WeChat/SMS/app push. Both share one data platform in real time.

KTR-MA connects over RS485 or Ethernet to every smart device: temp/humidity sensors, leak cable, smoke detector, communication-enabled UPS, precision AC, power meter, access control and cameras. Protocols: Modbus RTU/TCP, SNMP, dry contacts. A mid-size room — a dozen devices, dozens of points — lives on one screen.

2. Key Features

Data acquisition

  • Modbus RTU/TCP, SNMP, dry contact.
  • RS485 bus + gateway, up to 256 points.
  • Polling 1~60s adjustable.

Display & alarm

  • Floor-plan view with point icons.
  • Out-of-range pop-up + sound + log.
  • App push, SMS, email, WeChat.

History & reports

  • History curves (temp/humidity/voltage).
  • Alarm log, Excel export.
  • Auto daily/weekly/monthly reports.

Architecture

  • PC: Windows 7/10/11.
  • App: iOS 12+/Android 8+.
  • On-premise or cloud-hosted.

3. Specifications

Item KTR-MA-S KTR-MA-P KTR-MA-C
Edition Single-room Multi-room Cloud platform
Points ≤64 ≤256 Unlimited
Rooms 1 10 Unlimited
PC client Yes Yes Web browser
Mobile app Yes Yes Yes
Alarms Pop-up+push +SMS+email +WeChat+voice
Deploy Local PC Local server Cloud hosted

4. Reference Prices

KTR-MA-S single-room (64 points, PC+app, pop-up push): Reference USD 278~556 / set (ref. CNY 2000~4000 at ~7.2)

KTR-MA-P/C multi-room/cloud (256 points, SMS/email/WeChat, history reports): Reference USD 833~2778 / set (ref. CNY 6000~20000 at ~7.2)

Reference only; final quote depends on point count, room count, alarm channels (SMS/WeChat) and deployment (local/cloud). Sensor and UPS/AC comms integration extra. Exchange: 1 USD ≈ 7.2 CNY (Oct 2026).

5. Applications

  • Self-owned enterprise rooms, unattended remote monitoring.
  • Branch rooms consolidated at HQ.
  • IDC colo, customer views own rack environment.
  • Bank branch ELV rooms, central alarm to sub-branch.
  • Base stations and edge sites, mobile-app alarms.

6. Installation & Maintenance

Installation

  • Install KTR-MA PC client on control-room PC.
  • Connect RS485 gateway/serial server to room bus.
  • Add devices: select model, set address, register map.
  • Draw room floor plan; drag point icons.
  • Set high/low thresholds per point.
  • Configure recipients (phone/WeChat).
  • Download app; log in with same account.
  • Test: simulate high temp; verify push and SMS.

Maintenance

  • Quarterly: check comm links (serial server, cable).
  • Back up history to another drive.
  • Update recipients on staff changes.
  • Re-integrate after UPS/AC firmware upgrades.
  • Keep app updated.

7. FAQ

  • Q: Must the monitoring PC run 24/7?
    A: The on-prem version needs a host running 24/7 to collect and alarm. If you don’t want a dedicated PC, choose the cloud edition (KTR-MA-C): data goes straight to the cloud, no local PC needed, view anytime in the app.
  • Q: UPS/AC not in the device list?
    A: Major UPS/AC brands ship standard Modbus — software drivers are bundled. Rare devices need a protocol document; we write the driver. Devices without comms use a dry-contact module for alarm-only status.
  • Q: Is SMS billed?
    A: Software is free; SMS goes through a third-party gateway at ~0.05~0.1 CNY per message. WeChat alerts are free via official account. Critical alarms: send both SMS and WeChat.
  • Q: How long is history kept?
    A: Local edition defaults to 1 year (configurable 2~3); cloud edition 3+ years. Export curves and alarm logs to Excel for backup.

8. Trend & Selection

Room monitoring shifts from “local software + big screen” to “cloud platform + mobile app”: early you watched a control-room wall; today you watch a phone and alarms push to WeChat. Trends: cloud-native (no server to buy), AI prediction (forecast overheating from temp trends), 3D visualization (digital twin). Selection: a small single room uses local (KTR-MA-S); multi-room or unattended sites use cloud (KTR-MA-C); alarms at least app push plus SMS; size points by actual devices +30% headroom; confirm UPS/AC have comms ports before buying software.

9. Delivery & Service

KITOZER provides deployment: based on the device list (UPS/AC models, sensor types), we configure drivers, points and alarms. Delivery includes PC installer, app download link, manual and 1 year free upgrade. Software bugs fixed free in warranty; new device drivers developed free. Bundled with temp/humidity sensors (KTR-THS), leak cable (KTR-LK) and monitoring host (KTR-EMC).

10. Additional Notes

The most common pitfall is “sensors only, no UPS/AC.” Temp and humidity are monitored, but UPS battery voltage and AC runtime are not — a failed battery or stopped AC goes unnoticed until the room overheats. Connect everything: environment (temp/humidity/leak/smoke) + power (UPS/battery/panel) + AC (run/fault status).

The second pitfall: “thresholds set but no one receives alarms.” Alarms push to a departed employee’s phone, or the SMS gateway runs out of credit — the alarm fires but nobody sees it. Set at least 2~3 recipients (primary on-call, backup, supervisor) and periodically test that alerts actually arrive.

Third pitfall: no history backup. A failed PC disk wipes a year of alarm logs. Auto-backup history to another drive or cloud; quarterly verify backups are complete.

Selection summary: connect environment + power + AC; alarms to multiple people with periodic tests; back up history; unattended sites go cloud. Monitoring software is the room’s nervous system — what you don’t see you can’t manage; fully wired and alarmed, the room truly runs unattended.