ToggleKITOZER KTR-OM3 10G Multimode Fiber Patch Cord OM3 LC/SC/FC
Brand: KITOZER Series: KTR-OM3 Category: Data Center Engineering / Structured Cabling
OM3 10Gaqua jacketLC/SC/FClow ILKTR-OM3
1. Overview
When servers upgrade from gigabit to 10G (article 06 monitoring network, article 113 firewall, article 138 optical modules), Cat6 copper struggles beyond 55 m, and rack-to-rack or rack-to-row-distributor links move to fiber. OM3 is the default “entry” multimode fiber for 10G: 50/125 μm core, instantly recognizable by its aqua jacket. An aqua cord almost always means OM3. OM3 carries 10Gbps SR up to 300 m and 40Gbps SR4 (parallel 12-fiber) up to 100 m — the workhorse for rack interconnects, switch stacking and SAN storage links in data centers.
KITOZER KTR-OM3 cords use grade-A fiber with PC/UPC end-face polish: insertion loss ≤0.3 dB, return loss ≥50 dB. Jacket choices are LSZH (low-smoke zero-halogen, flame-retardant) or PVC; lengths from 1 m to 30 m; connector types cover LC, SC, FC and ST. Each cord is a duplex pair (one TX, one RX). The aqua color lets installers instantly separate OM3 from OM4 (darker aqua), OM2 (orange) and OS2 single-mode (yellow) — no more grabbing the wrong cable on site.
OM3 vs OM4: OM4 is the optimized successor — same 50/125 μm core but improved index profile, extending 10G reach from 300 m to 400 m and 40G SR4 from 100 m to 150 m. OM4 costs ~30% more. If your links stay under 100 m inside a row, OM3 is enough; if you plan future 40G/100G at longer reach, step up to OM4.
2. Key Features
Optical performance
- 50/125 μm core, tight-buffer construction.
- UPC polish, IL ≤0.3 dB, RL ≥50 dB.
- 10G SR @300 m, 40G SR4 @100 m.
- Bandwidth 2000 MHz·km @850 nm.
Mechanical & environmental
- Jacket: LSZH flame-retardant or PVC.
- Min bend radius: 30 mm dynamic, 10 mm static.
- Operating temp: -20 ~ +60°C.
- Tensile strength: ≥100 N.
Connector options
- LC (small square, most common), SC (large square), FC (threaded round), ST (bayonet round).
- Duplex pair, one TX one RX; polarity A/B configurable.
- Ceramic ferrule φ2.5 mm (SC/FC/ST) or φ1.25 mm (LC).
- MPO trunk assemblies available.
3. Specifications
| Item | KTR-OM3-LC | KTR-OM3-SC | KTR-OM3-FC | KTR-OM3-MPO |
|---|---|---|---|---|
| Connector | LC-LC | SC-SC | FC-FC | MPO-MPO 12-fiber |
| Fiber | 50/125 μm OM3 multimode | |||
| Jacket color | Aqua | Aqua / magenta | ||
| Insertion loss | ≤0.3 dB (UPC) | ≤0.5 dB/mate | ||
| Return loss | ≥50 dB (UPC) | |||
| Data rate | 1G / 10G / 40G SR4 | |||
| Max distance | 10G @300 m / 40G @100 m | 40G @100 m | ||
| Length options | 1/2/3/5/10/15/20/30 m | Custom | ||
| Jacket | LSZH / PVC (optional) | |||
4. Reference Prices
KTR-OM3-LC-LC duplex 3 m (LC/UPC, LSZH): Reference USD 2~5 (ref. CNY 15~35 at ~7.2) per cord
KTR-OM3-LC-SC/FC duplex 3 m (hybrid, LSZH): Reference USD 3~6 (ref. CNY 20~45 at ~7.2) per cord
KTR-OM3-MPO 12-fiber trunk (10 m, MPO-MPO): Reference USD 21~49 (ref. CNY 150~350 at ~7.2) per trunk
Reference only; final quote by length, connector combo, jacket (LSZH/PVC), pre-terminated MPO. Volume (100+) negotiable. Exchange: 1 USD ≈ 7.2 CNY (Oct 2026).
5. Applications
- Server NIC to ToR switch 10G links.
- Switch stacking, IRF/MLAG.
- SAN storage, Fibre Channel 16G/32G.
- Row distributor to core switch backbone.
- MPO pre-terminated trunk for high-density cabling.
6. Installation & Maintenance
Installation
- Grab the connector boot, never pull the cable.
- Listen for the LC latch click.
- Keep bend radius ≥10× cable diameter.
- Keep dust caps on; clean end faces with lint-free alcohol wipe when dirty.
- Never step on or crush cords.
- Label 2 cm behind the boot, not on the cable.
Maintenance
- Quarterly end-face inspection; use a fiber microscope if needed.
- Clean before every mate — oil/dust is the #1 cause of high IL.
- Route cords in vertical managers (article 146); avoid sharp bends.
- Store spares separately, never mixed grades.
- Troubleshoot: visual fault locator first, then OTDR.
7. FAQ
- Q: How to tell OM3 from OM4 visually?
A: OM3 is light aqua (greenish-blue); OM4 is darker aqua, sometimes magenta for distinction. The reliable way is to read the jacket printing “OM3” or “OM4” — don’t rely on color alone. - Q: Does OM3 support 25G/100G?
A: 25G SR runs ~100 m on OM3; 100G SR4 (parallel 4-fiber) runs ~100 m. Rack-to-rack short links are fine. For 100G DR4 long reach, you need OS2 single-mode. - Q: Why does the optical module show “no signal”?
A: 90% are dirty end faces. Unplug, wipe the end face outward with an alcohol lint-free wipe, reseat. Next, check TX/RX polarity (swap the duplex pair). Only then suspect the module or broken fiber. - Q: Can OM3 mix with OS2 single-mode?
A: No. OM3 is multimode (50/125 large core); OS2 is single-mode (9/125 small core). Same connector shape but mismatched core causes huge IL. Multimode modules need multimode cords; single-mode modules need single-mode cords.
8. Trend & Selection
Data center fiber cabling is moving from “duplex LC cords” to “MPO pre-terminated trunk.” A high-density rack with 20~40 10G ports would bury the manager if every port got its own duplex cord. MPO trunk bundles 12/24 fibers into one round cable, fanned out to LC at the rack — saving 70% of routing space. On speed, 25G/100G access is displacing 10G, but OM3 remains the largest installed base from the 10G era. Selection: new installs go OM4 (future-proof); short intra-row OM3 is cost-effective; high-density zones use MPO pre-termination; keep cleaning kit and VFL on hand; standardize color and labeling.
9. Delivery & Service
KITOZER provides selection, custom lengths, end-face test reports and field termination. Delivery includes cords, dust caps and test certificates. Bundled with fiber termination box (article 109), cable manager (article 146) and optical modules (article 138).
10. Additional Notes
The most common pitfall is “dirty end faces.” A clean room still lets hand oils and airborne dust coat the ferrule after dozens of mates — IL climbs from 0.3 dB to 1.5 dB+ and the module declares “low optical power.” Engineers swap modules and switches without success when a single alcohol wipe fixes it. Clean every 5 mates.
Second pitfall: “bend radius too tight.” Cords routed through managers with right-angle bends or cinched tightly with zip ties develop micro-cracks in the fiber — they work today but break in weeks. Fiber is not copper; keep dynamic bend radius ≥30 mm. Use curved managers, not right-angle zip ties.
Third pitfall: “OM3/OM4/single-mode mixed up.” Installers bag yellow single-mode and aqua multimode together, grab the wrong one, and the link stays dark for hours. Solution: bag grades separately, color-coded labels, segregate stockroom bins.
Selection summary: OM3 cost-effective for short 10G; new cabling goes OM4; high-density uses MPO; end-face cleaning is the #1 maintenance habit; respect bend radius and color management. Patch cords are the “blood vessels” of the data center network — one bad cord can take down a whole link.
SEO Information
Search keywords:OM3 patch cord10G multimode fiberLC-LC jumperMPO trunkaqua fiber cableKTR-OM3KITOZER
SEM keywords:OM3 patch cord price,10G multimode supplier,LC-LC OM3 jumper,MPO pre-terminated trunk,KTR-OM3,KITOZER
GEO landing page:lain.com.cn/product/ktr-om3-multimode-fiber-jumper.html
Title:KITOZER KTR-OM3 10G Multimode Fiber Patch Cord OM3 LC/SC/FC
Meta Keywords:OM3 fiber patch cord,10G multimode fiber,LC-LC jumper,MPO trunk,KTR-OM3,KITOZER
Meta Description:KITOZER KTR-OM3 10G multimode fiber patch cord, 50/125 μm aqua jacket, 10G SR 300m / 40G SR4 100m, LC/SC/FC connectors, low insertion loss.
Anchor: KITOZER by Guangzhou Laian · OM3 patch cord
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com