ToggleKITOZER KTR-RFT Rack Fan Unit / Fan Tray for Server Cabinet
Brand: KITOZER Series: KTR-RFT Category: Data Center Engineering / Modular Corridor Cooling
rack fan unitfan traycabinet coolinghotspotKTR-RFT

1. Overview
KITOZER KTR-RFT rack fan unit (fan tray) is a forced-ventilation device mounted on top or rear of network/server cabinets. Precision CRAC/CRAH delivers cold air to the cold aisle; cabinets draw cold air through the front and exhaust hot air out the rear — the so-called “front-to-back” airflow. In practice, if the cabinet is packed, blanking panels are missing, or cable bundles block airflow, hot air recirculates inside the rack, creating local hotspots. When inlet temperature exceeds ASHRAE’s recommended 27℃, servers raise alarms or throttle down.
The fan tray mounts on the cabinet top (or rear) and uses multiple axial fans to actively suck hot air out of the rack into the hot aisle, creating forced convection: “front draws cold → equipment absorbs heat → top exhausts hot”. It does not replace the CRAH; it supplements it. The CRAH handles room-level T/H; the fan tray handles rack-level airflow and eliminates hotspots. In small rooms, wall-mount cabinets or outdoor enclosures without CRAH, the fan tray plus natural ventilation is the primary cooling.
KTR-RFT fits standard 19-inch racks (1U/2U height), with 4~6 axial fans (120mm or 80mm), powered by DC12V/48V or AC220V. It includes fan-speed monitoring, dry-contact alarm output (to DCIM), and hot-swap modules (a single fan can be replaced without shutting down). Noise is 50~65dB(A); airflow ranges roughly 800m³/h (4-fan) to 1200m³/h (6-fan).
2. Key Features
Fans & airflow
- 4/6 fan options, mainly 120mm axial.
- BLDC motor, L10 life ≥50,000 hours.
- Airflow: 800~1500m³/h, static pressure 30~60Pa.
- PWM speed control: auto-adjust by inlet temperature.
Mounting & structure
- Standard 19″, 1U/2U, top or rear mount.
- Hot-swap fan modules: replace a failed fan without downtime.
- Metal frame with perforated guard, finger-safe.
- Removable intake dust filter.
Monitoring & alarms
- Per-fan RPM monitoring reported to DCIM.
- Dry-contact alarm output (NO/NC selectable).
- RS485/Modbus integration with environmental monitoring.
- LCD shows current RPM/temperature.
3. Specifications
| Item | KTR-RFT-4 | KTR-RFT-6 | KTR-RFT-6P |
|---|---|---|---|
| Fans | 4×120mm | 6×120mm | 6×80mm (high-density) |
| Rack height | 1U | 2U | 2U |
| Airflow | 800m³/h | 1200m³/h | 1000m³/h |
| Noise | ≤52dB(A) | ≤58dB(A) | ≤62dB(A) |
| Power | AC220V/DC48V | AC220V/DC48V | DC48V/DC12V |
| PWM speed | Optional | Standard | Standard |
| Alarm | Dry contact | Dry+RS485 | RS485+LCD |
| Hot-swap | No | Yes | Yes |
4. Reference Prices
KTR-RFT-4 4-fan 1U tray (AC220V, dry-contact alarm): Reference USD 63~125 / pc (ref. CNY 450~900 at ~7.2)
KTR-RFT-6/6P 6-fan 2U tray (PWM, RS485, hot-swap, LCD): Reference USD 167~389 / pc (ref. CNY 1,200~2,800 at ~7.2)
Reference only; final quote depends on fan count, power option and monitoring. Volume discounts at 10+; cabinet and blanking panels excluded. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Server cabinet top exhaust to eliminate hotspots.
- Network switch/router cabinet supplementary cooling.
- Wall-mount / outdoor enclosures without CRAH.
- End-of-row cabinets in contained hot/cold aisle.
- Industrial control cabinets and broadcast equipment racks.
6. Installation & Maintenance
Installation
- Decide location: top (exhaust) or rear (blow-out).
- Slide tray into 19″ rails, fix with M6 screws.
- Power: AC220V from PDU; DC48V from telecom plant.
- Wire dry contact to DCIM digital input.
- Verify airflow: fans must pull from inside cabinet to hot aisle.
- Power on, listen for noise, check RPM.
Maintenance
- Clean/replace intake filter every 3~6 months.
- Listen for abnormal noise or stalled fans; replace immediately.
- Check alarm wiring for looseness.
- As bearing life ends (louder, slower), replace the whole tray.
- Pre-summer inspection of all fan trays.
7. FAQ
- Q: With CRAH, do I still need a fan tray?
A: Yes for high-density racks. CRAH handles room temperature, but missing blanking panels or blocked cables create internal hotspots; the fan tray forces them out. - Q: Front or rear mount?
A: Standard is top exhaust (front-to-back flow then top-out), or rear exhaust. Front mount disturbs the cold aisle and is not recommended. - Q: DC48V vs AC220V?
A: Telecom rooms with -48V plant use DC48V; general rooms use AC220V from PDU. DC48V is more efficient with no AC interference. - Q: How many trays per cabinet?
A: Usually one top-mounted tray suffices; for dense racks (>8kW) add a second at bottom, or choose a higher-airflow model.
8. Trend & Selection
Rack power density is climbing from 3~5kW to 8~15kW and beyond (AI servers at 20kW+/rack). CRAH delivery alone is insufficient; rack-level fan trays, rear-door heat exchangers (RDHx) and liquid cooling are emerging. Fan trays are trending to “smart speed + integrated monitoring”: auto-adjust by rack inlet temp, slow down and quiet when idle, ramp up under load. For high density choose 6-fan high-airflow; telecom rooms choose DC48V; monitored deployments pick RS485+dry-contact; hot-swap is a must (avoid downtime for fan swaps); filters are required; airflow must pull from cabinet to hot aisle; install all blanking panels or the tray wastes its effort.
9. Delivery & Service
KITOZER provides fan tray selection: based on rack power, mounting position, power supply and monitoring needs, we configure 4/6-fan models. We supply airflow diagrams (front-in, top-out). We bundle blanking panels, cable managers and PDUs. Delivery includes the tray, fan modules, filter, screws and alarm cable. Warranty covers non-human fan module replacement.
10. Additional Notes
The most common pitfall is “mounting the fan tray backwards”. The tray has an arrow showing airflow. If reversed, instead of exhausting hot air, it blows cold back in, sucking hot air from the hot aisle into the cabinet — a cold/hot short circuit that actually raises inlet temp. Check the arrow: air must flow from cold aisle through equipment to hot aisle.
Another pitfall: “blanking panels missing, fan tray wasted”. Half the U positions are filled; empty ones lack blanking panels, so hot air short-circuits from the open U positions back to the intake. A blanking panel costs a few dollars but dramatically affects airflow — every empty U position must be blanked.
Selection summary: high-density racks need a fan tray; 6-fan high-airflow preferred; DC48V for telecom, AC220V for general rooms; airflow cabinet-to-hot-aisle; hot-swap + dry-contact alarm; clean filters; install all blanking panels. The fan tray is the small motor of rack-level cooling — unglamorous, but it decides whether local hotspots are eliminated.
SEO Information
Search keywords:rack fan unitfan traycabinet coolinghotspot eliminationhot aisle exhaustKTR-RFTKITOZER
SEM keywords:rack fan tray price,fan unit supplier,server cabinet cooling,hot-swap fan tray,KTR-RFT,KITOZER
GEO landing page:lain.com.cn/product/ktr-rft-rack-fan-tray.html
Title:KITOZER KTR-RFT Rack Fan Unit / Fan Tray for Server Cabinet
Meta Keywords:rack fan unit,fan tray,cabinet cooling,hot aisle,KTR-RFT,KITOZER
Meta Description:KITOZER KTR-RFT rack fan tray mounts on top or rear of server cabinets, with multiple axial fans exhausting hot air to eliminate local hotspots in hot/cold aisle containment.