Table of Contents
ToggleKITOZER KTR-PSPD Power Surge Protective Device (SPD) T1/T2/T3
Brand: KITOZER Series: KTR-PSPD Category: Power Distribution / Surge Protection
surge protective deviceT1 SPDlightning protection3-stage SPDKTR-PSPD
1. Overview
KITOZER KTR-PSPD is a power surge protective device (SPD) for data center power distribution. The most expensive assets in a data hall are servers, switches and UPS — and these electronics are most vulnerable to surges: lightning induction, grid switching transients, and heavy load switching all produce kilovolt-to-ten-kilovolt spikes on the mains. A surge traveling along the power line can burn power supplies, punch through motherboards or destroy storage. The SPD clamps the surge to a safe residual voltage (≤1.5kV) and diverts energy to ground, protecting downstream equipment.
Data hall lightning protection is not a single SPD but a “three-stage” scheme: Stage 1 (main switchboard incoming, T1 test, Iimp≥25kA/10/350μs) discharges most of the lightning current; Stage 2 (floor/row cabinet, T2 test, In≥40kA/8/20μs) further clamps; Stage 3 (PDU/equipment front-end, T2 fine protection, In≥10kA) protects sensitive electronics. The three stages work together, attenuating step by step until residual voltage at the equipment end is safe. KTR-PSPD offers a full modular SPD line from T1 to T3, DIN-rail mount, plug-in replacement of failed modules, with remote alarm contacts (to DCIM).
The core components are metal-oxide varistors (MOV) and gas discharge tubes (GDT): MOV responds fast (nanoseconds) but has limited current capacity; GDT handles high current but responds slower. Stage 1 uses GDT+MOV combination; Stages 2/3 use MOV. Each stage has a failure indicator: window green=OK, red=failed, meaning the MOV has aged and needs replacement. SPDs with remote contacts close a dry contact on module failure, alerting DCIM without a site visit.
2. Key Features
Stage 1 SPD (T1, main switchboard)
- Iimp (10/350μs) ≥25kA/pole.
- In≥25kA, Imax≥60kA (8/20μs).
- Voltage protection level Up≤2.5kV.
- Modular plug-in, failure window + remote contact.
Stage 2 SPD (T2, row/floor cabinet)
- In≥40kA (8/20μs), Imax≥80kA.
- Up≤1.8kV.
- 2P/3P+N/4P options.
- DIN-rail mount, 35mm standard rail.
Stage 3 SPD (T2 fine, PDU/equipment)
- In≥10kA, Imax≥20kA.
- Up≤1.5kV (fine protection).
- Socket-type or rail-type, plugs into PDU or equipment front.
- Lightning strike counter (some models).
3. Specifications
| Item | KTR-PSPD-T1 | KTR-PSPD-T2 | KTR-PSPD-T3 |
|---|---|---|---|
| Class | Stage 1 (T1) | Stage 2 (T2) | Stage 3 (T2 fine) |
| Location | Main switchboard | Row/floor cabinet | PDU/equipment |
| Iimp (10/350) | 25kA/pole | — | — |
| In (8/20) | 25kA | 40kA | 10kA |
| Imax (8/20) | 60kA | 80kA | 20kA |
| Up | ≤2.5kV | ≤1.8kV | ≤1.5kV |
| Poles | 3P+N | 3P+N/4P | 1P+N |
| Remote alarm | Standard | Standard | Optional |
4. Reference Prices
KTR-PSPD-T1 Stage 1 3P+N modular SPD (main switchboard): Reference USD 111~250 / set (ref. CNY 800~1,800 at ~7.2)
KTR-PSPD-T2 Stage 2 3P+N SPD (row cabinet): Reference USD 56~125 / set (ref. CNY 400~900 at ~7.2)
KTR-PSPD-T3 Stage 3 fine SPD (PDU/equipment): Reference USD 17~49 / pc (ref. CNY 120~350 at ~7.2)
Reference only; final quote depends on poles, discharge capacity and remote alarm. Volume discount at 10+ sets; grounding bars and cables not included. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Data center main switchboard Stage 1 lightning protection.
- Floor distribution and row cabinet Stage 2.
- Rack PDU and UPS front-end Stage 3 fine protection.
- Outdoor base station and telecom site incoming power.
- Broadcast, medical and industrial control system surge protection.
6. Installation & Maintenance
Installation
- T1 SPD parallel after the main breaker on incoming lines, across phases and N.
- T2 SPD at row cabinet input; keep ≥10m cable separation from T1 (decoupling) or add a decoupling inductor.
- T3 SPD directly at PDU input or equipment power socket.
- Ground lead short and thick: ≤0.5m, ≥6mm² (T1 ≥16mm²).
- Wire remote contact to DCIM digital input.
- Insulation-test with megohmmeter before energizing.
Maintenance
- Quarterly check SPD failure window (green=OK, red=failed).
- Post-thunderstorm inspection; repeated strikes age SPD faster.
- On red window, immediately swap same-type module (hot-swap, no shutdown).
- Remote alarm to DCIM for 24/7 unattended monitoring.
- Typical SPD life 5~10 years, shorter in lightning-prone areas.
7. FAQ
- Q: With Stage 1, do I still need Stages 2 and 3?
A: Yes. Stage 1 discharges large current but residual voltage is still 2.5kV; the three stages clamp step by step until ≤1.5kV at the equipment. Stage 1 alone still lets surges damage equipment. - Q: Must I replace the SPD when the window turns red?
A: Yes. Red means the MOV has failed open and protection is gone — downstream equipment is unprotected. Modules are hot-swappable, no shutdown needed. - Q: Can SPDs catch fire?
A: Cheap ones can. Certified SPDs have an internal disconnector that safely disconnects on failure. Choose products with 3C/CQC certification. - Q: How long should the ground lead be?
A: As short as possible, ≤0.5m. A long lead adds inductance, slows current discharge, raises residual voltage and degrades protection.
8. Trend & Selection
SPDs are evolving from “bare MOV” to “modular + remote alarm + smart monitoring”: SPDs with strike counters, waveform logging and remote comms (RS485/IoT) are becoming standard in new data halls. The trend is hot-swap modules (no downtime), safer failure disconnectors, and DCIM-linked alarms. Size three stages by distribution architecture (T1 at main, T2 at row, T3 at PDU); T1 Iimp≥25kA, T2 In≥40kA; ground short and thick ≤0.5m; remote alarm mandatory to DCIM; choose 3C/CQC-certified brands; in lightning-prone regions (I≥40kA) upsize Stage 1; replace failed modules immediately.
9. Delivery & Service
KITOZER provides power surge protection selection: based on the power architecture (utility incoming, transformer, UPS, row cabinet, PDU), we design a three-stage SPD scheme and produce the protection diagram (SPD positions, wiring, grounding). We bundle grounding bars, ground cables and equipotential bonding. Delivery includes SPD modules, bases and remote terminals. Warranty covers non-lightning failures; lightning damage handled per damaged count.
10. Additional Notes
The most common pitfall is “only Stage 1, no Stages 2/3”. A big SPD is installed in the main switchboard and everyone thinks lightning protection is done — nothing at row cabinets or PDUs. After Stage 1 discharges, residual voltage is still 2.5kV; after another 10+ meters of cable to the rack, that spike is enough to kill server power supplies. Three-stage protection is a chain; break one link and it fails.
Another pitfall: “ground lead routed long”. The SPD ground terminal is looped two or three meters to the ground bar, with thin wire. The longer the ground lead, the higher the inductance; the voltage drop across the lead during a surge raises the actual residual voltage at the equipment. Correct: SPD grounds locally, lead short/thick/direct, ≤0.5m, ≥6mm² (T1 ≥16mm²).
Selection summary: three stages are all required; T1 at main, T2 at row, T3 at PDU; ground short/thick ≤0.5m; remote alarm to DCIM; replace on red window; choose 3C-certified brands. The SPD is the data hall’s power lightning rod — unnoticeable on a normal day, but it saves equipment in a thunderstorm.
SEO Information
Search keywords:surge protective deviceT1 SPDlightning protection3-stage SPDdata center surgeKTR-PSPDKITOZER
SEM keywords:power SPD price,T1 surge protector supplier,data center lightning protection,3-stage surge scheme,KTR-PSPD,KITOZER
GEO landing page:lain.com.cn/product/ktr-pspd-surge-protective-device.html
Title:KITOZER KTR-PSPD Power Surge Protective Device (SPD) T1/T2/T3
Meta Keywords:surge protective device,SPD,T1 class,data center power surge,3-stage protection,KTR-PSPD,KITOZER
Meta Description:KITOZER KTR-PSPD power SPD: T1 Iimp≥25kA, T2 In≥40kA, T3 fine protection, modular plug-in with remote alarm for distribution, row cabinet and PDU.
Anchor: KITOZER by Guangzhou Laian · Environmental monitoring systems