Table of Contents
ToggleKITOZER KTR-EV Precision Air Conditioner Evaporator Coil
Brand: KITOZER Series: KTR-EV Category: Data Center Engineering / Precision AC Evaporator
evaporator coilcopper tubehydrophilic finprecision AC partsKTR-EV
1. Overview
The evaporator is the component that actually moves the heat inside a precision air conditioner. The compressor sends pressurized refrigerant to the evaporator, where it throttles into a cold low-pressure gas; warm room air blown across the finned coil gives up its heat, then returns to the cold aisle as cooled air. In short, the compressor is the heart and the evaporator is the heat-exchanging lung — whether the cooling is enough and the temperature is stable depends largely on the evaporator efficiency.
The KITOZER KTR-EV series uses copper tubes through hydrophilic aluminum fins with hydraulic expansion, so tube and fin make tight contact and reduce thermal resistance. Tubes are de-oiled copper, 0.35~0.45 mm wall, rated to 4.5 MPa; fins carry a hydrophilic coating so condensate runs off as a film instead of bridging between fins and carrying moisture into the air stream. Coils come in 20/40/60 kW tiers, replacing original evaporators of mainstream precision AC brands or custom-bent to the unit dimensions.
Precision AC runs continuously (8760 h/year) in a damp, dusty environment, so evaporators face fin collapse, dust fouling, copper oxidation and tiny leaks at U-bend welds. KTR-EV adds fin anti-corrosion treatment and oil-return bends. Selection hinges on matching the unit nominal cooling capacity, connector sizes, overall dimensions and mounting orientation — not on a close-enough fit.
2. Key Features
Heat exchange
- Copper tube + hydrophilic fin expansion, low contact resistance.
- Staggered multi-row arrangement for full heat transfer.
- Face velocity held at 2.0~2.6 m/s to avoid carry-over.
- Hydrophilic film lets condensate drain freely.
Durability & sealing
- De-oiled copper tube, 0.35~0.45 mm wall.
- One-piece U-bends cut down weld points.
- Factory pressure-leak test (4.5 MPa N2 for 24 h).
- Fin anti-corrosion treatment for damp sites.
Compatibility & custom
- Covers 20/40/60 kW mainstream units.
- Custom bent rows to fit the original unit.
- Welded or flanged connections.
- Drip tray and drain hose available.
3. Specifications
| 项目 | KTR-EV-20 | KTR-EV-40 | KTR-EV-60 |
|---|---|---|---|
| 适配制冷量 | 20 kW级 | 40 kW级 | 60 kW级 |
| 铜管管径 | Φ9.52 mm | Φ9.52 mm | Φ12.7 mm |
| 排数 | 4排 | 6排 | 6排 |
| 翅片材质 | 亲水铝箔 | 亲水铝箔 | 亲水铝箔 |
| 翅片间距 | 2.0 mm | 2.0 mm | 2.1 mm |
| 迎面风速 | 2.2~2.6 m/s | 2.2~2.6 m/s | 2.0~2.4 m/s |
| 工作压力 | ≤4.5 MPa | ≤4.5 MPa | ≤4.5 MPa |
| 接口方式 | 焊接/法兰 | 焊接/法兰 | 焊接/法兰 |
4. Reference Prices
KTR-EV-20 evaporator coil (20kW, 4-row):Reference USD 486~903 / pc (ref. CNY 3,500~6,500 at ~7.2)
KTR-EV-40 evaporator coil (40kW, 6-row):Reference USD 903~1,667 / pc (ref. CNY 6,500~12,000 at ~7.2)
KTR-EV-60 evaporator coil (60kW, 6-row):Reference USD 1,667~3,056 / pc (ref. CNY 12,000~22,000 at ~7.2)
Reference only; final quote depends on capacity, core count, airflow, channel count, current rating, battery cells, length and point count. 1-year warranty included; volume pricing available. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Replacing aged/leaking evaporators in precision AC.
- Whole-coil replacement after cooling decay.
- Heat-exchanger cores for custom units.
- Cold storage and constant-T/RH lab AC coils.
- HVAC retrofit and spare-parts stocking.
6. Deployment & Implementation
Installation
- Power off and recover refrigerant before swap.
- Confirm original coil ports and manifold routing.
- After weld/expansion, vacuum and pressure-test.
- Slope the drip tray and connect the drain.
Operations
- Clean fins yearly (neutral cleaner, moderate pressure).
- Comb out collapsed fins.
- Watch operating pressure and supply-air temp.
- Keep dry during long shutdowns.
7. FAQ
- Q: When should the evaporator be replaced?
A: If supply air runs hot, low-side pressure drops, fins are heavily fouled, or a persistent leak keeps needing top-ups, heat exchange has decayed — replace the whole coil rather than re-welding. - Q: Hydrophilic vs plain aluminum fins?
A: Hydrophilic coating forms a water film that drains instead of bridging fin gaps, cutting air resistance and carry-over; plain fins bead up and grow algae over time. - Q: Can I replace just part of the coil?
A: Replace the whole coil in a group; patching gives uneven heat transfer, and dissimilar copper accelerates the next leak. - Q: Do I need to recharge refrigerant?
A: Racking loses charge; after the swap, vacuum and refill to the nameplate charge with the correct refrigerant (R410A/R407C).
8. Trend & Selection
Data-center AC is moving toward high sensible ratio, high airflow and free cooling, and the evaporator — the core heat exchanger — gains louvered fins, inner-grooved copper tubes and micro-channel construction to pack more transfer per unit volume and cut fan power. Key selection: match the unit nominal capacity and port dimensions first, then tube wall and expansion quality, then hydrophilic/anti-corrosion treatment; always vacuum and pressure-test and charge by weight after swap; slope the drip tray or water leaks under the floor. The evaporator is only one part of the AC, yet it decides whether the cooling actually reaches the rack.
9. Delivery & Service
KITOZER provides KTR-EV selection and customization: based on the unit nameplate capacity, dimensions and connector orientation, we match or fabricate the coil. Drip tray, drain hose and insulation can be bundled. Every unit is pressure-tested with a report. 1-year warranty; on-site guidance remote or on-site (extra).
10. Additional Notes
The common mistake is ordering on a close-enough fit. A few centimeters off in height, width or manifold port position means it will not fit or the duct must be cut. Before ordering, measure the original coil length×width×thickness, inlet/outlet port orientation and size, and send photos to verify.
Another pitfall is skipping vacuum after the swap. Technicians rush and add refrigerant without pulling vacuum, leaving air and moisture that cause ice blockage and compressor liquid slugging within six months. Pull vacuum to -0.1 MPa and hold for 2+ hours before charging by weight.
Selection summary: pick by original capacity (20/40/60 kW); verify dimensions and ports; demand expanded-tube build and hydrophilic fins; vacuum, pressure-test and charge by weight after install; slope the drip tray; clean fins yearly. The evaporator is the heat-exchanging heart — only when it is right does the cooling come back.
SEO Information
Search keywords:evaporator coilcopper heat exchangerhydrophilic finprecision AC partsdata center coolingKTR-EVKITOZER
SEM keywords:precision AC evaporator price,copper heat exchanger coil,hydrophilic fin,AC coil replacement,KTR-EV,KITOZER
GEO landing page:lain.com.cn/product/ktr-ev-evaporator-coil.html
Title:KITOZER KTR-EV Precision Air Conditioner Evaporator Coil
Meta Keywords:precision air conditioner evaporator,copper heat exchanger coil,hydrophilic fin,KTR-EV,KITOZER
Meta Description:KITOZER KTR-EV precision AC evaporator coil, copper tube with hydrophilic aluminum fins, expanded-tube, 20/40/60kW, customizable, efficient and durable.
Anchor: KITOZER by Guangzhou Laian · Precision AC parts
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com