ToggleKITOZER KTR-MPDU Metered Rack PDU with Current Display
Brand: KITOZER Series: KTR-MPDU Category: Power Distribution / Metered PDU
metered PDUcurrent displayC13 C19RS485 remoteKTR-MPDU

1. Overview
Racks keep filling with servers, switches and storage, each plugged into an outlet — but what is the total current? A plain PDU has outlets but no metering: overloads go unnoticed until a breaker trips. A metered PDU adds a current/voltage meter showing rack power in real time; higher models add RS485 to push data to the DCIM/environment monitoring, so operators know the load.
The KITOZER KTR-MPDU series comes in 16/32/63 A tiers. Aluminum housing, horizontal 1U or vertical mount; outputs mix C13 (10 A small gear) and C19 (16 A servers/switches) to cover mainstream IT gear. The front LED shows voltage/current/power at 1.0-class accuracy; the 63 A model adds RS485 Modbus-RTU to feed the environment system. Built-in breaker and surge module provide overcurrent and surge protection.
Selection hinges on rated current, outlet mix and comms: first sum full-load rack current (device watts / 220 V) with 1.3× margin to pick 16/32/63; then match C13/C19 counts to devices (servers lean C19, network gear leans C13); pick RS485 only if remote reading is needed. Note: more outlets does not mean more capacity — total current is capped by the input cord and breaker, not by outlet count.
2. Key Features
Metering & display
- LED real-time voltage/current display.
- 1.0-class accuracy for visible load.
- PF / apparent power optional.
- 63 A model adds RS485 to DCIM.
Distribution & protection
- Mixed C13/C19 for mainstream gear.
- Built-in breaker overcurrent protection.
- Integrated surge protection module.
- Aluminum housing for heat dissipation.
Mounting & compat
- 1U horizontal or vertical mount.
- Standard rack mounting holes.
- Input cord length custom (1.8~3 m).
- Color-coded A/B feeds.
3. Specifications
| 项目 | KTR-MPDU-16 | KTR-MPDU-32 | KTR-MPDU-63 |
|---|---|---|---|
| 额定电流 | 16 A | 32 A | 63 A |
| 输入插头 | C20 / 16A工业 | 32A工业 | 63A工业 |
| 输出插座 | C13×8 / C19×2 | C13×12 / C19×4 | C13×20 / C19×6 |
| 电压显示 | LED数字 | LED数字 | LED数字+RS485 |
| 电流显示 | LED数字 | LED数字 | LED数字+RS485 |
| 计量精度 | 1.0级 | 1.0级 | 1.0级 |
| 安装方式 | 机架1U | 机架1U/竖直 | 机架竖直 |
| 保护 | 过流/防雷 | 过流/防雷 | 过流/防雷+分路 |
4. Reference Prices
KTR-MPDU-16 metered PDU (16A, 8×C13+2×C19):Reference USD 49~97 / pc (ref. CNY 350~700 at ~7.2)
KTR-MPDU-32 metered PDU (32A, 12×C13+4×C19):Reference USD 90~167 / pc (ref. CNY 650~1,200 at ~7.2)
KTR-MPDU-63 metered PDU (63A, 20×C13+6×C19, RS485):Reference USD 208~389 / pc (ref. CNY 1,500~2,800 at ~7.2)
Reference only; final quote depends on capacity, core count, channel count, current rating, battery layers, port count and sensor points. 1-year warranty included; volume pricing available. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Rack power metering and monitoring.
- Network room outlet expansion and current sensing.
- Remote meter reading and alarms in environment systems.
- IDC capacity planning and load balancing.
- Lab and studio equipment power measurement.
6. Deployment & Implementation
Installation
- Match PDU rating to upstream breaker/cord.
- Vertical for cable routing, 1U for height saving.
- Cord gauge by rating (16 A ≥2.5 mm²).
- Cross-feed A/B dual PDUs for redundancy.
Operations
- Check displayed current vs actual load monthly.
- Keep RS485 address unique on the bus.
- After a trip, find overload before resetting.
- Replace surge modules at end of life.
7. FAQ
- Q: Metered vs smart PDU?
A: Metered PDU measures total current/voltage locally or remotely; smart (switched/outlet-metered) adds per-outlet remote switching and outlet-level metering. If you only need total current, metered PDU is better value. - Q: C13 or C19?
A: C13 (10 A) for small switches/routers; C19 (16 A) for servers and high-power storage. Match the device cord plug. - Q: How many servers on a 16 A PDU?
A: By total current, not outlet count. A dual-power server draws ~2~4 A, so a 16 A PDU with margin carries ~4~6; beyond that go 32 A. - Q: How to wire RS485 to DCIM?
A: Connect A/B (or D+/D-) to the monitoring module’s RS485 port, set 9600 baud and a unique Modbus address, then register points in the DCIM software.
8. Trend & Selection
Rack power is moving from just-on to measurable, remote-controllable and outlet-level switched; metered PDU is the baseline, switched/outlet-metered PDU spreads in IDCs. Key selection: size by rack current ×1.3; match C13/C19 to device plugs; choose RS485 only for remote reading; match upstream breaker and cord gauge; cross-feed A/B. The metered PDU is just a power strip, yet it is the eye into rack power safety and capacity planning.
9. Delivery & Service
KITOZER provides KTR-MPDU selection: by rated current (16/32/63), C13/C19 outlet mix, and RS485 option. Custom cord length and plugs. Factory power-on test of display and comms. 1-year warranty; custom lengths and labeling in volume.
10. Additional Notes
The common mistake is over-provisioning outlets while total current exceeds the rating. Ten C13s look like enough, yet total current is near the 16 A ceiling and one upstream breaker trips the whole rack. Size by total current, not outlet count.
Another pitfall is reversing RS485 A/B. With reversed wires the DCIM reads nothing and the device is wrongly blamed. Check A/B definitions both ends and add a 120 Ω terminator at the bus end.
Selection summary: size by rack current ×1.3 to 16/32/63; match C13/C19 to plugs; pick RS485 for remote reading; match upstream breaker and cord; cross-feed A/B. The metered PDU makes power visible and overloads visible early.
SEO Information
Search keywords:metered PDUrack power distributioncurrent display PDUC13 C19 outletsRS485 monitoringKTR-MPDUKITOZER
SEM keywords:metered PDU price,rack current display power strip,C13 C19 PDU,RS485 smart power,KTR-MPDU,KITOZER
GEO landing page:lain.com.cn/product/ktr-mpdu-metered-rack-pdu.html
Title:KITOZER KTR-MPDU Metered Rack PDU with Current Display
Meta Keywords:metered PDU,rack power distribution unit,current display,C13 C19 outlets,KTR-MPDU,KITOZER
Meta Description:KITOZER KTR-MPDU metered PDU, LED voltage/current display, 16/32/63A, mixed C13/C19, RS485 remote, overcurrent and surge protection.
Anchor: KITOZER by Guangzhou Laian · Metered PDU