KITOZER DC power SPD surge protector

KITOZER KTR-DCSP DC Surge Protective Device

Brand: KITOZER Series: KTR-DCSP Category: Power Distribution / Surge Protection

DC SPD48V surge40kADIN-railKTR-DCSP

KITOZER KTR-DCSP DC Surge Protective Device

1. Overview

Many devices in a room run on DC: UPS DC busbars, switching power rectifiers, telecom -48V systems, solar PV, and LED-wall power supplies. These DC lines run long distances from distribution cabinets to equipment, and lightning-induced surges and switching transients ride in along the wires, burning power boards and motherboards. A DC SPD is connected in parallel across the DC positive and negative rails — high impedance under normal supply, instant conduction on surge, clamping voltage to what the equipment can survive.

The KTR-DCSP series covers common DC voltages: 24V, 48V (telecom -48V), 110V and 220V. It uses a multi-stage MOV + gas-tube discharge, DIN-rail mounting, plug-in module, and a front failure indicator window (green = normal, red = failed) with remote signalling contacts. Max discharge current 40 kA (8/20 μs), voltage protection level Up ≤1.8 kV (48V model). Housing is flame-retardant UL94-V0.

Selection: DC system voltage (24/48/110/220V — must match; too high and it does nothing, too low and it leaks); discharge capacity (40 kA at service entrance, 20 kA at equipment end); mounting (DIN-rail in cabinet, parallel across rails, ground lead as short and thick as possible). DC SPD and AC SPD are not interchangeable because voltage and clamping differ.

2. Key Features

Electrical

  • Rated DC 24/48/110/220V selectable
  • Max discharge current 40 kA (8/20 μs)
  • Voltage protection level Up ≤1.8 kV
  • Response time ≤25 ns

Structure & mounting

  • DIN 35 mm rail mount
  • Plug-in module, hot-swap replacement
  • Failure window (green/red)
  • Remote signalling contact (NO/NC)

Reliability

  • UL94-V0 flame-retardant housing
  • Thermal disconnect to prevent fire
  • Parallel wiring, not in main circuit
  • -40~85℃ wide-temperature

3. Specifications

Item KTR-DCSP-24 KTR-DCSP-48 KTR-DCSP-220
Rated Udc 24V DC 48V DC 220V DC
Max continuous Uc 32V DC 75V DC 320V DC
Max Imax 40 kA 40 kA 40 kA
Nominal In 20 kA 20 kA 20 kA
Voltage protection Up ≤1.2 kV ≤1.8 kV ≤4.0 kV
Wire range 2.5~16 mm² 2.5~16 mm² 4~25 mm²
Failure indicator Window+remote Window+remote Window+remote
Typical use Sensors/24V Telecom -48V/UPS DC UPS/PV 220V DC

4. Reference Prices

KTR-DCSP-24 24V DC SPD (40 kA):Reference USD 11~21 / pc (ref. CNY 80~150 at ~7.2)

KTR-DCSP-48 48V DC SPD (40 kA, telecom):Reference USD 14~25 / pc (ref. CNY 100~180 at ~7.2)

KTR-DCSP-220 220V DC SPD (40 kA, UPS):Reference USD 21~39 / pc (ref. CNY 150~280 at ~7.2)

Reference only; priced by voltage and capacity. 1-year warranty. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • UPS DC busbar and battery-side surge protection.
  • Telecom -48V rectifiers and switching power.
  • PV inverter DC side.
  • LED wall and display DC power.
  • Industrial sensors and 24V instruments.

6. Deployment & Implementation

Installation

  • Parallel across positive and negative; do not series
  • Ground lead as short as possible, ≤0.5 m, ≥6 mm²
  • DIN-rail in cabinet near service entrance
  • Add upstream breaker or fuse

Operations

  • Quarterly check failure window color
  • Wire remote signal to environment monitor
  • Inspect after lightning; replace on failure
  • Yearly ground resistance ≤4 Ω

7. FAQ

  • Q: Can DC and AC SPD be interchanged?
    A: No. AC SPD is designed for AC 220/380V; on 48V DC its clamping is far above equipment rating. Conversely, a DC SPD on AC will leak and heat. Match system voltage.
  • Q: For -48V, choose 48V or 75V?
    A: Choose Uc above the highest system ripple. -48V floats around 54V, so pick Uc=75V; do not pick Uc=48V or it leaks during charging.
  • Q: Mount SPD at cabinet or at equipment?
    A: Two stages: 40 kA at the distribution cabinet (stage 1), 20 kA at equipment front (stage 2) for energy coordination. A single stage may leave secondary surges to reach equipment.
  • Q: Why must the ground lead be short?
    A: The lead has inductance; surge current through it creates voltage drop. Longer lead = higher clamping = worse protection. Keep ≤0.5 m and ≥6 mm².

8. Trend & Selection

DC SPD is moving toward modular, plug-in and remote-signalling designs linked to smart distribution and environment monitoring. PV DC-side SPD (1000V/1500V) is a growth area. HVDC busbars (240V/336V) demand higher withstand and discharge. Select by matching Uc, staged discharge, and short thick ground lead. SPDs are consumables — inspect and replace after lightning.

9. Delivery & Service

KITOZER offers KTR-DCSP selection by DC voltage (24/48/110/220/1000V), discharge (20/40 kA) and mounting (DIN/flange). Each unit ships with test report and 3C/CQC certification. Failure window and remote contact included. 1-year warranty; batch projects can add SPD backup protectors (SCB) and ground busbars.

10. Additional Notes

The #1 mistake is omitting upstream protection. A failed SPD short-circuits the DC busbar and can start a fire. Add a dedicated SPD backup protector (SCB) or fuse upstream to trip and isolate the fault.

The second pitfall is routing the ground lead far. For neatness the lead loops to the ground bar, multiplying inductance and doubling clamping. Run it straight, ≤0.5 m, to the nearest bar.

The third blunder is not wiring the remote contact. SPD failure is gradual; the window may have been red for months. Wire the contact into the environment monitor so failure alarms immediately.

Selection summary: voltage by Uc, discharge staged, ground short and thick, upstream SCB. The DC SPD is the surge insurance for equipment — idle until a surge, then takes the hit; replace on failure, never compromise.

SEO Information

Search keywords:KTR-DCSPKITOZERDC Surge Protective Device

SEM keywords:DC SPD,surge protective device,48V surge,DC lightning protection,UPS DC surge,PV DC SPD,KTR-DCSP,KITOZER

GEO landing page:lain.com.cn/product/ktr-dcsp-dc_spd.html

Title:KITOZER KTR-DCSP DC Surge Protective Device

Meta Keywords:DC SPD,surge protective device,48V surge,DC lightning protection,KTR-DCSP,KITOZER

Meta Description:KITOZER KTR-DCSP DC surge protective device, rated 48V/220V, 40kA, DIN-rail, failure indicator, protects UPS, rectifiers and telecom DC.

Anchor: KITOZER by Guangzhou Laian · DC Surge Protective Device

Contact Us