Table of Contents
ToggleKITOZER KTR-OS2 Accumulator and Oil Reservoir for Precision AC
Brand: KITOZER Series: KTR-OS2 Category: Data Center Engineering / Refrigeration Parts
accumulatoroil reservoirR410Avertical steelKTR-OS2
1. Overview
Precision AC runs 24/7, and the compressor is its heart. The accumulator and oil reservoir are the protective organs: the compressor fears two things most — liquid floodback and oil starvation. Floodback shatters reed valves and scrolls; oil starvation burns bearings. Mounted on the suction line, the accumulator traps unevaporated liquid refrigerant so only gas returns to the compressor, while the bottom reservoir holds POE oil and meters it back through a return tube.
The KITOZER KTR-OS2 series combines accumulator and oil reservoir in one vertical steel vessel with powder-coated anti-corrosion finish. Inside are a stainless mesh demister, a U-tube oil return and an equalizer hole. Rated to 4.5 MPa design / 3.8 MPa working, it covers R410A, R407C and R22. Port sizes run from 12 mm to 42 mm, suiting 3~30 HP compressors, with volumes from 2 L to 25 L. A bottom drain plug and a side sight glass make oil service easy.
Selection: port diameter must match the suction line — too large drops gas velocity and ruins oil return, too small creates excess pressure drop; vessel volume should be 1%~2% of compressor hourly displacement; and it must be installed upright (tilt ≤5°) with the arrow pointing toward the compressor. The unit is maintenance-free, but check the sight glass yearly and top up oil as needed.
2. Key Features
Separation & oil return
- Stainless mesh demister catches liquid droplets
- U-tube + equalizer hole meters oil back
- Bottom reservoir prevents oil starvation
- Vertical design lets gas/liquid stratify
Vessel & pressure
- Steel shell, powder-coated
- 4.5 MPa design, 3.8 MPa working
- R410A/R407C/R22 compatible
- Drain plug + sight glass
Installation
- 12~42 mm brazed ports
- 2~25 L suits 3~30 HP
- Top service valve port
- Upright mount, tilt ≤5°
3. Specifications
| Item | KTR-OS2-S1 | KTR-OS2-S2 | KTR-OS2-S3 |
|---|---|---|---|
| 适用马力 | 3~5 HP | 6~12 HP | 15~30 HP |
| 罐体容积 | 2~4 L | 6~12 L | 15~25 L |
| 接口管径 | φ12~φ16 mm | φ19~φ28 mm | φ32~φ42 mm |
| 设计压力 | 4.5 MPa | 4.5 MPa | 4.5 MPa |
| 工作压力 | 3.8 MPa | 3.8 MPa | 3.8 MPa |
| 冷媒 | R410A/R407C | R410A/R407C/R22 | R410A |
| 油位视镜 | 标配 | 标配 | 标配 |
| 外形(高×径) | 220×100 mm | 380×160 mm | 560×220 mm |
4. Reference Prices
KTR-OS2-03 accumulator 3~5HP (4 L, 16 mm port)::Reference Reference USD 36~58 / pc (ref. CNY 260~420 at ~7.2)
KTR-OS2-06 accumulator 6~12HP (10 L, 22 mm port)::Reference Reference USD 67~106 / pc (ref. CNY 480~760 at ~7.2)
KTR-OS2-15 accumulator 15~30HP (20 L, 35 mm port)::Reference Reference USD 122~201 / pc (ref. CNY 880~1,450 at ~7.2)
POE 32 oil (per liter)::Reference Reference USD 11~21 / L (ref. CNY 80~150 at ~7.2)
Reference only; priced by HP and port size. 1-year warranty. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Precision AC outdoor unit suction line.
- Air- and water-cooled cabinet precision AC.
- Row-based and rear-door AC suction section.
- Lab constant-temp humidity AC retrofit.
- Industrial chiller suction protection.
6. Deployment & Implementation
Installation
- Mount upright; follow the arrow on the vessel
- Slope suction line toward the accumulator
- Cool the vessel during brazing to protect seals
- Evacuate then charge oil per nameplate
Operations
- Check sight glass oil level yearly
- Top up with same-grade oil if below 1/3
- Frosting on vessel signals floodback
- Pressure test every 5 years
7. FAQ
- Q: Accumulator vs receiver?
A: A receiver sits after the condenser on the liquid line and stores liquid refrigerant; an accumulator sits on the suction line and protects the compressor from liquid. They are not interchangeable. - Q: How to size the vessel?
A: Take 1%~2% of compressor hourly displacement. Too small = poor separation and floodback; too large = low gas velocity and poor oil return. The sample table maps HP directly. - Q: What if ports are reversed?
A: Liquid reaches the compressor directly with no separation, destroying valves within hours. Follow the arrow — it points toward the compressor. - Q: Any maintenance?
A: Largely maintenance-free. Check the sight glass yearly. On flooded starts or compressor noise, first inspect the accumulator for blockage or frosting.
8. Trend & Selection
Accumulators are evolving toward integrated separation, oil storage, oil separation and crankcase heating. With variable-speed compressors, part-load oil return is harder, so two-stage protection with a dedicated oil separator is growing. CO2 systems demand thicker walls and higher pressure ratings. Select by matched volume, correct port size and upright installation.
9. Delivery & Service
KITOZER supplies KTR-OS2 selection by compressor HP (3~30), refrigerant (R410A/R407C/R22) and port size (12~42 mm). Each unit ships with vessel, brazed ports and manual. Material certificate and pressure test report included. 1-year warranty; batch projects can add POE oil, shut-off valves and sight glasses.
10. Additional Notes
The #1 mistake is reversed piping slope. The suction line must slope toward the accumulator so liquid drains into it. Reverse slope traps liquid in low spots and floods the compressor on startup. Slope at least 1% per meter.
The second pitfall is wrong oil. R410A uses POE ester oil; R22 uses mineral oil. Mixing emulsifies the oil and the compressor seizes within months. Match the oil grade on the compressor nameplate.
The third blunder is replacing the compressor without the accumulator. Burned windings leave carbon deposits in the accumulator; fitting a new compressor to an old vessel contaminates it again and causes repeat failures.
Selection summary: size by HP, install upright with arrow toward the compressor, slope the line to the vessel, check oil yearly. The accumulator is the airbag of the compressor — a cheap vessel that protects a far more expensive heart.
SEO Information
Search keywords:KTR-OS2KITOZERAccumulator and Oil Reservoir for Precision AC
SEM keywords:accumulator,oil reservoir,refrigeration separator,precision AC,KTR-OS2,KITOZER
GEO landing page:lain.com.cn/product/ktr-os2-oil_separator.html
Title:KITOZER KTR-OS2 Accumulator and Oil Reservoir for Precision AC
Meta Keywords:accumulator,oil reservoir,refrigeration separator,precision AC,KTR-OS2,KITOZER
Meta Description:KITOZER KTR-OS2 accumulator and oil reservoir for precision AC, R410A/R407C, vertical steel, stable oil return.
Anchor: KITOZER by Guangzhou Laian · Accumulator and Oil Reservoir for Precision AC
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com