ToggleKITOZER KTR-3PSPD Three-Phase 380V Surge Protection Box for Data Center
Brand: KITOZER Series: KTR-3PSPD Category: Power Distribution / Surge Protection
3-phase 380V40~100kAremote alarm4+0 wiringKTR-3PSPD

1. Overview
Room power comes from an outdoor HV transformer; during thunderstorms surges ride the line into the room, reaching thousands of volts and punching through UPS, server PSUs and switches. A surge protective device (SPD) sits between lines and PE: high-impedance normally, instant low-impedance on a surge to divert current to earth and clamp voltage to ≤2.5 kV. A 380 V three-phase room needs a three-phase SPD box with B+C two-stage protection.
The KITOZER KTR-3PSPD uses 35 mm DIN-rail modules (or wall-mount box), wired 3+1 or 4+0 (TN-S uses 4+0, one SPD across L1/L2/L3/N). Ratings: Iimp (10/350 µs) 15~25 kA, In (8/20 µs) 40 kA, Imax 100 kA, Up ≤1.8 kV. Each module has a green/red failure window and optional dry-contact remote alarm to the environment host. The box includes a main switch and (on some models) a surge counter.
Selection: class — B at the transformer LV side (10/350 µs, Iimp ≥15 kA), C at the room distribution (8/20 µs, In ≥20 kA), with ≥10 m between stages or a decoupler; wiring — TT uses 3+1, TN-S uses 4+0, and the N-PE module is mandatory; and current capacity — general rooms pick C In 40 kA/Imax 100 kA, high-lightning regions (south/east coastal) pick In 60 kA. SPDs are consumables; swap the module, not the box.
2. Key Features
Current capacity
- In 40 kA (8/20 µs)
- Imax 100 kA
- Iimp 15 kA (10/350 µs)
- Up ≤1.8 kV
Wiring
- 3-phase 380 V 4+0
- 35 mm DIN modules
- Wall-mount box option
- Failure window
Alarm
- Dry-contact remote
- Failure remote alarm
- Surge counter (opt.)
- Overcurrent disconnector
3. Specifications
| Item | KTR-3PSPD-S1 | KTR-3PSPD-S2 | KTR-3PSPD-S3 |
|---|---|---|---|
| 型号 | KTR-3PSPD-C40 | KTR-3PSPD-C60 | KTR-3PSPD-B100 |
| 防护等级 | C级 | C级(加强) | B级(一级) |
| In(8/20μs) | 40kA | 60kA | 100kA |
| Imax | 100kA | 120kA | 150kA |
| Iimp(10/350) | — | — | 25kA |
| 电压保护Up | ≤1.8kV | ≤1.8kV | ≤2.0kV |
| 接线 | 4+0 | 4+0 | 3+1 |
| 遥信 | 标配 | 标配 | 标配+计数 |
4. Reference Prices
KTR-3PSPD-C40 3-phase C-class (In 40 kA, 4+0): Reference USD 94~153 / pc (ref. CNY 680~1100 at ~7.2)
KTR-3PSPD-C60 3-phase C-class reinforced (In 60 kA): Reference USD 136~222 / pc (ref. CNY 980~1600 at ~7.2)
KTR-3PSPD-B100 3-phase B-class (Iimp 25 kA): Reference USD 250~389 / pc (ref. CNY 1800~2800 at ~7.2)
Spare SPD module (single pole, 20~40 kA): Reference USD 11~21 / pc (ref. CNY 80~150 at ~7.2)
Reference only; priced by class and current capacity. 1-year warranty. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Room distribution C-class SPD.
- Transformer LV side B-class SPD.
- UPS input surge protection.
- Outdoor equipment distribution.
- Surveillance/fire system power SPD.
6. Deployment & Implementation
Installation
- Parallel across L/N and PE
- Leads ≤0.5 m
- B/C spacing ≥10 m or decoupler
- Ground resistance ≤4 Ω
Operations
- Check failure window quarterly
- Wire remote alarm to environment host
- Inspect modules after a strike
- Replace whole set every 3~5 years
7. FAQ
- Q: B vs C class?
A: B (stage 1) at the transformer LV side diverts large energy (10/350 µs, Iimp ≥15 kA); C (stage 2) at the room distribution clamps residual surges (8/20 µs, In ≥20 kA). Two stages work together; one alone is not enough. - Q: How do I know a module failed?
A: Window turns red; the dry contact triggers and the environment host alarms. Once failed, the SPD no longer protects — replace the spare module promptly. - Q: Ground resistance?
A: Combined room ground ≤1 Ω for critical rooms, ≤4 Ω for general. SPD ground leads should be as short as possible, ≤0.5 m — longer leads add inductance and raise clamping voltage. - Q: SPD lifespan?
A: Normal life 5~10 years, but every strike consumes capacity. In high-lightning areas, check every 2~3 years and replace when the window turns red. Do not wait for failure.
8. Trend & Selection
SPDs are moving from pure protection to protection plus monitoring — smart SPDs with leakage current, surge count and temperature upload to the environment platform for life prediction. High-current (≥100 kA) modular SPDs grow with PV and wind grid ties. Integrated boxes (SPD + isolation transformer + surge counter) spread in small rooms.
9. Delivery & Service
KITOZER supplies KTR-3PSPD by class (B/C), current capacity (40/60/100 kA), wiring (3+1/4+0) and alarm (dry contact/counter). Ships with box, SPD modules, DIN rail and manual. Factory test report included. 1-year warranty; batch projects can add ground bars, arresters and decouplers.
10. Additional Notes
The #1 mistake is C-class only, no B-class. The room distribution has a C SPD but the transformer LV side lacks B, so large energy hits the undersized C stage, destroying it in one strike and taking downstream gear with it. B+C together are complete.
The second pitfall is SPD leads over 1 m. Lead inductance lifts clamping from 1.8 kV to over 3 kV and equipment still gets hit. Keep leads ≤0.5 m, straight, no loops.
The third blunder is not swapping failed modules. A red window unnoticed means the SPD is open-circuit and surges pass straight through. Wire the remote dry contact to the environment host for automatic alarm.
Selection summary: B at the transformer, C at the room, leads ≤0.5 m, ground ≤4 Ω, remote alarm to host. The SPD box is the power system’s lightning arrestor — it idles daily but saves the day in a storm.
SEO Information
Search keywords:KTR-3PSPDKITOZERThree-Phase 380V Surge Protection Box for Data Center
SEM keywords:three phase SPD box,380V surge protector,power lightning protection,data center SPD,KTR-3PSPD,KITOZER
GEO landing page:lain.com.cn/product/ktr-3pspd-3ph_spd_box.html
Title:KITOZER KTR-3PSPD Three-Phase 380V Surge Protection Box for Data Center
Meta Keywords:three phase SPD box,380V surge protector,power lightning protection,data center SPD,KTR-3PSPD,KITOZER
Meta Description:KITOZER KTR-3PSPD three-phase 380V surge protection box, 40~100 kA, dry-contact remote alarm, 4+0 wiring for room distribution.
Anchor: KITOZER by Guangzhou Laian · Three-Phase 380V Surge Protection Box for Data Center
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com