1. Overview

Data-center precision air conditioners run nearly non-stop, and the compressor is the heart. When the unit cycles off, the crankcase (the oil sump at the bottom of the shell) cools below the condenser; liquid refrigerant (R22/R410A/R134a) migrates toward the colder sump and dissolves in the lubricant. On the next start, diluted oil loses viscosity, the oil pump starves, and the compressor suffers poor lubrication, liquid slugging, and oil emulsification — often seizing within minutes. The crankcase heater solves this small but critical problem: a heating strip bonded to the lower shell keeps the oil 5~10°C warmer than the rest of the system during off hours, so liquid refrigerant stays out of the sump and the oil stays pure.

The KTR-CH series offers three sizes: KTR-CH-50 (50 W, for 3~5 HP scroll), KTR-CH-90 (90 W, for 5~10 HP scroll / small screw), and KTR-CH-150 (150 W, for 10~25 HP screw). The element is a silicone rubber heater belt or PTC self-limiting pad, 30/45 mm wide, length cut to the shell circumference. Supply is AC 220 V ±10%, 50/60 Hz; insulation class E or above; IP40 inside the compressor compartment. It is bonded and strapped to the lower third of the shell, then wrapped in insulation. The heater is wired through the contactor’s normally-closed auxiliary: it heats only while the compressor is off and cuts out on run.

Selection: size by compressor horsepower (roughly 10~15 W per HP); choose belt length to wrap the shell once with slight overlap; confirm supply voltage (220 V vs 380 V); and confirm control logic — replacement machines may have an existing circuit, while retrofits need an auxiliary contact or timer so heating follows off-hours and a pre-start warm-up of 6~12 h is enforced.

2. Key Features

Element

  • Silicone rubber belt, 150°C rated
  • PTC self-limiting, over-temp auto-cutback
  • Even heating, no hot spots
  • Dielectric 1500 V / 1 min

Electrical

  • AC 220 V ±10% supply
  • 50 / 90 / 150 W ratings
  • Current 0.23~0.68 A
  • 85°C self-resetting thermostat

Mechanical

  • Stainless straps on the shell
  • Alu-foil tape lowers thermal resistance
  • External insulation blanket
  • 1.5 m high-temp silicone leads

3. Specifications

Item KTR-CH-50 KTR-CH-90 KTR-CH-150
Power 50 W 90 W 150 W
Compressor 3~5 HP scroll 5~10 HP scroll/screw 10~25 HP screw
Voltage AC 220 V AC 220 V AC 220 V
Belt size 30×500 mm 45×700 mm 45×1000 mm
Surface temp ~60~70°C ~65~75°C ~70~80°C
Control NC aux. contact NC aux. contact NC aux. contact
Lead length 1.5 m 1.5 m 2 m
Ingress IP40 IP40 IP40

4. Reference Prices

KTR-CH-50 silicone belt (50 W):Reference USD 8~13 / pc (ref. CNY 60~95 at ~7.2)

KTR-CH-90 silicone belt (90 W):Reference USD 12~18 / pc (ref. CNY 85~130 at ~7.2)

KTR-CH-150 silicone belt (150 W):Reference USD 17~25 / pc (ref. CNY 120~180 at ~7.2)

Kit (insulation + straps + thermostat):Reference USD 4~7 / add-on (ref. CNY 30~50 at ~7.2)

Reference only; 1-year warranty. Belt length custom-cut to shell circumference. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Precision-AC compressor crankcase heating.
  • Outdoor unit oil viscosity in cold climates.
  • Cold-storage / constant-HVAC long-shutdown protection.
  • Pre-start warm-up on new machines.
  • Retrofit of missing or failed heater belts.

6. Deployment & Implementation

Installation

  • Mount on lower-third oil sump area
  • Clean shell, apply alu-foil thermal tape
  • Strap tight, no air gaps
  • Wrap 20 mm rubber insulation outside

Wiring

  • Wire via NC auxiliary contact
  • Heater off while compressor runs
  • Pre-heat 8~12 h before long shutdown start
  • Route leads away from hot discharge line

Operations

  • Annually measure belt resistance
  • Check insulation blanket stays in place
  • Oil temp should read 5~10°C above ambient
  • Inspect insulation in dew seasons

7. FAQ

  • Q: Is the heater always on?
    A: No. Correct wiring heats only during off cycles and cuts out on run. Always-on wastes power and cooks the oil. Use the contactor’s NC auxiliary or a timer.
  • Q: How long to pre-heat a new unit?
    A: A new or long-stopped compressor needs 8~12 h of control-power heating (some makers specify 24 h) to drive dissolved refrigerant out of the oil before start. Skipping this is the #1 cause of new-compressor seizures.
  • Q: How hot should the belt feel?
    A: Warm to the touch (60~70°C) is normal. If it burns on contact (>90°C), the PTC or thermostat has failed — power off and replace.
  • Q: Signs of a failed heater?
    A: Frequent low-pressure trips, foaming oil sight glass, noisy start-up, or oil-pressure alarm. Check belt resistance on shutdown; open circuit means replace.

8. Trend & Selection

Modern indoor units often embed oil heaters internally; external belts are now spare-parts and retrofit items. The trend is PTC self-limiting pads replacing plain silicone belts — no separate thermostat, power throttles as temperature rises, safer. New refrigerants (R32/R454B) are more sensitive to oil migration and need slightly larger heating. Select by HP, bond to the lower sump third, insulate, heat only off-cycle, and pre-heat new machines overnight. A few-dollar belt protects a compressor worth thousands.

9. Delivery & Service

KITOZER supplies KTR-CH by compressor HP (3~25), voltage and belt length. Each unit ships with belt, stainless straps, alu-foil tape, insulation and manual. 1-year warranty; batch projects can add auxiliary contacts, timers and wiring guidance.

10. Additional Notes

The #1 mistake is bonding the belt on the upper shell — that is the empty gas cavity, not the oil. Heat there warms the metal but not the oil. Always target the lower third.

The second pitfall is skipping the insulation blanket. Without it, heat bleeds into the compartment, the oil never reaches target, and power is wasted. Wrap 20 mm of rubber insulation outside.

The third blunder is starting a new machine without pre-heat. After transport, the sump is full of liquid refrigerant; one start causes liquid slugging and can crack the crankshaft. Regardless of factory talk, energize control power overnight before the first compressor start.

Selection summary: size by HP, mount low-third, strap and insulate, heat only off-cycle, pre-heat new units overnight. The crankcase heater is the compressor’s bedtime warmer — small part, big protection.

SEO Information

Search keywords:KTR-CHKITOZERCrankcase Heater

SEM keywords:crankcase heater,compressor heater,silicone heater belt,precision AC compressor,oil heater,KTR-CH,KITOZER

GEO landing page:lain.com.cn/product/ktr-crankcase_heater.html

Title:KITOZER KTR-CH Crankcase Heater for Precision AC Compressors

Meta Keywords:crankcase heater,compressor heater,silicone heater belt,precision AC compressor,oil heater,KTR-CH,KITOZER

Meta Description:KITOZER KTR-CH crankcase heater bonded to the compressor shell, heats oil during off-cycles to stop liquid-refrigerant migration and protect compressor start-up.

Anchor: KITOZER by Guangzhou Laian · Crankcase Heater

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart