KITOZER 12V 200Ah VRLA battery

KITOZER KTR-BAT200 12V 200Ah VRLA Battery

Brand: KITOZER Series: KTR-BAT200 Category: Power Distribution / UPS Battery

12V 200AhVRLAAGMfront terminalKTR-BAT200

1. Overview

The UPS itself stores no energy; the battery string does. When mains drops, the battery bank feeds the inverter, bridging to the diesel generator (usually 5~15 min) or riding through brief outages. Capacity determines runtime: a 10 kVA UPS at ~8 kW needs about 40~50 Ah for 30 minutes, depending on inverter efficiency and end-of-discharge voltage. 12V200Ah is the workhorse for cell sites, small/medium UPS and outdoor integrated power: 12 V nominal, 200 Ah (C20), four in series for 48 V telecom strings or sixteen/thirty-two for 192/384 V UPS buses. The KTR-BAT200 is a valve-regulated lead-acid (VRLA) battery with AGM (absorbent glass mat) starved-electrolyte design — acid held in the mat, no spilling, no watering, mountable in any orientation except long-term inversion. Float design life 12~15 years at 25°C; front terminals for dense cabinet rows.

KTR-BAT200 key data: 12 V nominal, 200 Ah (C20, 2.25 V/cell at 25°C), 522×240×218 mm (L×W×H), 224 mm over terminals, ~65 kg. M8 copper front terminals. Positive plate pasted lead-calcium alloy, negative pasted/tubular, AGM separator, ABS flame-retardant case. Float voltage 2.25~2.27 V/cell, equalize 2.30~2.35 V/cell, end-discharge 1.80 V/cell. Self-discharge ≤3%/month at 25°C, operating -15~+50°C (best 20~25°C). Order codes: KTR-BAT200-FT front terminal (battery cabinets) and KTR-BAT200-TM top terminal (traditional racks).

Selection: series count by UPS bus — 16 strings for 192 V, 32 for 384 V; capacity by runtime (10 kVA at 30 min ≈ one 200 Ah string or two 100 Ah in parallel); load the rack — ~65 kg/cell, 32 cells ≈ 2080 kg, so rack structure must be reinforced; and temperature — every 10°C above 30°C halves life, so the battery room must be air-conditioned to 25°C.

2. Key Features

Type

  • VRLA sealed lead-acid
  • AGM starved electrolyte, no spill
  • Pb-Ca grid, low self-discharge
  • ABS flame-retardant case

Electrical

  • 12 V 200 Ah (C20)
  • Float 2.25~2.27 V/cell
  • Equalize 2.30~2.35 V/cell
  • End 1.80 V/cell

Mechanical & Environment

  • M8 front terminals
  • 522×240×218 mm
  • ~65 kg
  • -15~+50°C operating

3. Specifications

Item KTR-BAT100 KTR-BAT200 KTR-BAT12-200
Voltage 12 V 12 V 12 V
Capacity (C20) 100 Ah 200 Ah 200 Ah
Dimensions 330×172×214 522×240×218 522×240×218
Weight ~30 kg ~65 kg ~65 kg
Terminal Front M8 Front M8 Top M8
Float V 2.25 V/cell 2.25 V/cell 2.25 V/cell
Design life 10~12 yr 12~15 yr 12~15 yr
Use Small UPS site/large UPS traditional racks

4. Reference Prices

KTR-BAT100 12V100Ah front terminal:Reference USD 94~128 / pc (ref. CNY 680~920 at ~7.2)

KTR-BAT200 12V200Ah front terminal:Reference USD 178~233 / pc (ref. CNY 1280~1680 at ~7.2)

KTR-BAT12-200 12V200Ah top terminal:Reference USD 174~225 / pc (ref. CNY 1250~1620 at ~7.2)

Copper link bars + bolts:Reference USD 3.5~6.3 / set (ref. CNY 25~45 at ~7.2)

Reference only; 3-year warranty. Cabinets and install not included. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Small/medium UPS DC strings.
  • 48 V telecom strings (4×12 V in series).
  • Outdoor integrated power backup.
  • Data center 15~30 min UPS ride-through.
  • EPS emergency power backup.

6. Deployment & Implementation

Installation

  • Rack load ≥600 kg/shelf
  • Leave terminal wiring clearance
  • Series with copper bars, torque M8 ~12 N·m
  • Red positive / blue negative leads

Environment

  • Battery room 20~25°C
  • Ventilate, no H₂ buildup
  • Avoid direct sunlight
  • Avoid heat and corrosive gas

Operations

  • Quarterly measure per-cell float voltage
  • Annually discharge-test capacity
  • Coat terminals with petroleum jelly
  • Plan replacement after 5 years

7. FAQ

  • Q: How long will a 12V200Ah last?
    A: Rough math: 10 kW load, 0.9 inverter efficiency, 192 V bus → ~58 A. A 200 Ah battery at 0.25C delivers ~160 Ah → ~2.7 h. Real UPS at 8 kW gets ~30 min; check the vendor’s discharge curve.
  • Q: How long do batteries last?
    A: Design life 12~15 yr at 25°C float. Real rooms run 30°C+ → expect 8~10 yr. Capacity fades after 5 yr; annual capacity test below 80% means plan replacement.
  • Q: Is a swollen battery safe?
    A: No — swelling indicates overcharge or internal shorting. Replace immediately and check the charger float voltage. Never mix one new cell into an old string; mismatched internal resistance drags down both.
  • Q: Why air-condition the battery room?
    A: Lead-acid life is temperature-sensitive: every 10°C above 25°C halves life. A 35°C room turns a 12-year design into 6. Room AC at 25°C is the highest-return maintenance spend.

8. Trend & Selection

Data-center battery paths are diverging: VRLA remains the workhorse for small/medium rooms; LFP lithium is penetrating large cloud data centers — half the volume and weight, 3~5× cycle life, but 2~3× the unit cost and requiring a dedicated BMS cabinet. 5G sites and outdoor power already favor lithium. Select: VRLA 12V200Ah for small/medium rooms, LFP for long runtime and high energy density, keep the room at 25°C, start capacity checks at year 5, and replace whole strings — never mix. The battery is the UPS’s ammunition; quiet on float, vital in outage.

9. Delivery & Service

KITOZER supplies KTR-BAT200 by capacity (100/200 Ah) and terminal (front/top). Each ships with battery, copper links and manual. 3-year warranty; batch projects can add battery cabinets, racks, cell monitors and BMS.

10. Additional Notes

The #1 mistake is mixing old and new cells. Swapping one fresh cell into an aged string means the old cell overcharges and the new one undercharges; after a few cycles both are dead. Replace the whole string in same-batch, same-capacity, same-age cells.

The second pitfall is wrong terminal torque. M8 at 12 N·m: too loose → high resistance and overheating at high current; too tight → crushed copper washer and worse contact. Use a torque wrench to spec.

The third blunder is an unventilated battery room. VRLA cells evolve small amounts of hydrogen during charging; a sealed room can reach explosive limits. Fit exhaust fans for 6~8 air changes/hour, use fire-rated doors, and keep the room clear.

Selection summary: VRLA for small rooms, LFP for long runtime, room at 25°C, capacity checks from year 5, whole-string replacement. The battery is the UPS’s grain — unnoticed until the lights go out.

SEO Information

Search keywords:KTR-BAT200KITOZER12V 200Ah VRLA Battery

SEM keywords:battery,12V 200Ah,VRLA battery,UPS battery,AGM valve regulated,front terminal battery,KTR-BAT200,KITOZER

GEO landing page:lain.com.cn/product/ktr-battery_12v200.html

Title:KITOZER KTR-BAT200 12V 200Ah VRLA Battery

Meta Keywords:battery,12V 200Ah,VRLA battery,UPS battery,AGM valve regulated,front terminal battery,KTR-BAT200,KITOZER

Meta Description:KITOZER KTR-BAT200 12V 200Ah VRLA AGM battery, 12~15 year float design life, front terminal, for UPS and telecom backup in data centers.

Anchor: KITOZER by Guangzhou Laian · 12V 200Ah Battery

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart