1. Overview
The worst scenario in a room is “the AC died and nobody noticed.” When the precision AC or its fans trip, rack air temperature climbs from 25°C to 40°C+ in about 15 minutes, and servers hit thermal shutdown. A temperature alarm solves this: a digital display panel in the rack or aisle, connected to an NTC probe, shows live temperature; when it crosses the set upper (e.g. 30°C) or lower (e.g. 10°C) threshold, it triggers a built-in siren and a relay to an external strobe or the EM host. It is the simplest, cheapest and most non-negotiable piece of room environmental monitoring. The upgrade path is a combined temp/humidity sensor with RS485 to an EM host; but if you just want “someone yells when it gets hot,” a standalone alarm does the job.
The KTR-TA series: KTR-TA-1 (single-channel, LED display, built-in buzzer + relay, one NTC probe with 3 m cable, DC12 V); KTR-TA-2 (dual-channel, two probes for hot/cold aisle comparison with independent thresholds); KTR-TA-RS485 (temp+humidity, temp ±0.5°C, humidity ±3%RH, RS485 Modbus-RTU to EM host). Range -40~+125°C, accuracy ±0.5°C at 25°C, NTC 10K B=3950, 3 m probe cable standard (extendable to 10 m). Upper/lower thresholds set on the panel; hysteresis 1~5°C to prevent chatter. Built-in 85 dB buzzer; relay dry contact 30 V DC 2 A. ABS white case, 86×86 mm standard wall box, or DIN-rail in power panels.
Selection: by number of points — single rack uses one channel, hot/cold aisle comparison uses dual; by integration — standalone alarm for small rooms, RS485 for EM-hosted rooms; by probe location — probe on rack intake (cold aisle), never on the AC supply air; and by power — DC12 V adapter, optional PoE.
2. Key Features
Sensing
- NTC 10K B=3950
- -40~+125°C range
- ±0.5°C accuracy
- 3 m cable, extendable
Alarm Output
- Built-in 85 dB buzzer
- Relay dry contact 2 A
- Upper/lower dual thresholds
- 1~5°C hysteresis
Comm & Power
- Optional RS485 Modbus-RTU
- 4-digit LED display
- DC12 V supply
- Wall box / DIN rail
3. Specifications
| Item | KTR-TA-1 | KTR-TA-2 | KTR-TA-RS485 |
|---|---|---|---|
| Channels | 1× temp | 2× temp | temp+humidity |
| Temp range | -40~+125°C | -40~+125°C | -20~+60°C |
| Temp accuracy | ±0.5°C | ±0.5°C | ±0.5°C |
| Humidity | — | — | ±3%RH |
| Alarm | buzzer+relay | buzzer+relay | buzzer+relay+RS485 |
| Probe cable | 3 m | 3 m ×2 | 3 m |
| Display | 4-digit LED | 4-digit LED | 4-digit LED |
| Power | DC12V | DC12V | DC12V/PoE |
4. Reference Prices
KTR-TA-1 single-channel alarm:Reference USD 9~15 / pc (ref. CNY 65~110 at ~7.2)
KTR-TA-2 dual-channel alarm:Reference USD 15~25 / pc (ref. CNY 110~180 at ~7.2)
KTR-TA-RS485 temp+humidity:Reference USD 21~36 / pc (ref. CNY 150~260 at ~7.2)
External 12 V strobe siren:Reference USD 5~8 / pc (ref. CNY 35~60 at ~7.2)
Reference only; 1-year warranty. EM host not included. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Single-rack intake over-temp alarm.
- Hot/cold aisle delta monitoring.
- Battery room over-temp reminder.
- Power room temperature rise alarm.
- Small rooms without EM host.
6. Deployment & Implementation
Installation
- Display panel by the door or aisle
- Probe on rack intake mid-height
- Not directly under AC supply vent
- Cable in rack cable channel
Setup
- Upper 30°C, lower 10°C
- Hysteresis 2°C to prevent chatter
- Relay to strobe or EM DI
- Self-test beep on power-up
Operations
- Quarterly cup-hand on probe to test
- Replace damaged probe cables
- Calibrate against a reference thermometer
- Yearly battery change on battery models
7. FAQ
- Q: Temperature alarm vs EM host?
A: An EM host is a whole system with screen, SMS and many sensors. A temperature alarm is a standalone device that does one thing — sense and alarm. Small rooms use a standalone + strobe; large rooms wire its relay to the EM DI as a redundant alarm. - Q: Where should the probe go?
A: Rack intake at mid-height (1.5 m above floor), clipped to a blanking panel or post — that’s the air the servers actually breathe. Not rack top (hot air pools), not floor level (cold air), and not directly at the AC vent (freezing cold, not the rack’s real intake). - Q: Why does it alarm repeatedly at the threshold?
A: No hysteresis. Set 30°C and the room oscillates 29.5~30.5°C, so it beeps on/off. Set hysteresis to 2°C — alarm at 30°C, clear only at 28°C — and the chatter stops. - Q: Does it alarm on mains loss?
A: Standard units go dark with power. For mains-failure alarm, choose a battery-backed model or power the alarm from the UPS circuit — when the AC dies, the alarm must keep yelling.
8. Trend & Selection
Temperature alarms are moving from LED boxes to wireless: WiFi/LoRa sensors push data to a cloud platform with phone-app alerts, no wiring. Battery BMS already includes per-cell temperature, but room ambient alarms remain a separate device. In liquid-cooled racks, supply/return coolant temperature monitoring is a new scenario requiring coolant-rated probes. Select: standalone single-channel for small rooms, RS485 for EM integration, probe on rack intake, 2°C hysteresis, UPS-powered. A tens-to-hundreds-yuan device is the room’s goalkeeper.
9. Delivery & Service
KITOZER supplies KTR-TA by channels (1/2), RS485 option, temp/temp+humidity. Each ships with alarm unit, NTC probe, DC12 V adapter and manual. 1-year warranty; batch projects can add strobes, EM hosts and SMS modules.
10. Additional Notes
The #1 mistake is mounting the probe at the AC vent. It reads 15°C forever because cold air blows on it, while server intake is already 35°C. Put the probe on the rack intake, at least 1 m from the vent — that’s the real inlet temperature.
The second pitfall is never testing. Units hang on the wall and are never probe-covered. When the AC truly dies, the buzzer is dead. Quarterly cup-hand the probe to 35°C and confirm the buzzer and relay fire.
The third blunder is powering from a wall outlet. When the AC trips, mains may dip too and the alarm dies with it. Power the alarm from the UPS circuit or use a battery-backed model — it must keep yelling when the AC dies.
Selection summary: standalone for small rooms, RS485 for EM, probe on intake, 2°C hysteresis, UPS-powered. The temperature alarm is the room’s thermometer — small device, big watch.
SEO Information
Search keywords:KTR-TAKITOZERTemperature Alarm
SEM keywords:temperature alarm,data center temperature monitor,NTC sensor,sound-light alarm,RS485 temperature,room temp alarm,KTR-TA,KITOZER
GEO landing page:lain.com.cn/product/ktr-temp_alarm.html
Title:KITOZER KTR-TA Room Temperature Alarm
Meta Keywords:temperature alarm,data center temperature monitor,NTC sensor,sound-light alarm,RS485 temperature,room temp alarm,KTR-TA,KITOZER
Meta Description:KITOZER KTR-TA temperature alarm: digital display + NTC probe, over-temp siren + relay output, RS485 to EM host, mounted in-rack or on aisle wall.