1. Overview

Data-center precision air-conditioners face two overlooked freeze risks in cold weather. First, during long off cycles, liquid refrigerant migrates into the compressor crankcase and dissolves in the lubrication oil; on restart, oil foams and the compressor suffers liquid slugging that destroys bearings and reed valves. Second, when the outdoor unit or water-side coil is shut down in winter, standing water in the drain pan, condensate trap or make-up line can freeze and crack the coil. An antifreeze heater / crankcase heater addresses both. KITOZER KTR-AFH ships as two form factors: a crankcase heater band wrapped around the compressor shell, and a coil/pan heater stuck on the water-side parts, thermostatically controlled so power cuts in below about 5~10°C and cuts out above 15°C.

The crankcase heater works by keeping the oil sump warmer than the condensing temperature, so refrigerant stays in vapor form and does not dilute the oil. KTR-AFH-CH uses a silicone-jacketed NiCr resistance tape, 60~150 W, 220 V AC, 1.5 mm thick and 20 mm wide, wrapped around the compressor shell and covered with fiberglass blanket.

KTR-AFH-CO is a coil/pan heater at 100~300 W with a mechanical thermostat (5°C on, 15°C off), IP65, designed for northern sites and unattended base stations. Selection: confirm the heating object (crankcase vs coil/water), the wattage and voltage, whether the AC mainboard should interlock the heater, and the mounting style (wrap / clip / adhesive).

2. Key Features

Heating Element

  • NiCr resistive core
  • Silicone / FEP jacket to 200°C
  • Uniform watt density, no hot spots
  • Length custom to compressor size

Control

  • Mechanical thermostat 5~15°C
  • Optional mainboard relay interlock
  • Thermal fuse as backup
  • 220 V AC supply

Protection & Mounting

  • IP54 (CH) / IP65 (CO)
  • Wrap / clip / adhesive
  • Fiberglass blanket included
  • 1.5 m silicone lead wires

3. Specifications

Item KTR-AFH-CH KTR-AFH-CO KTR-AFH-CO-PRO
Use crankcase coil / drain pan outdoor unit base
Wattage 60~150 W 100~200 W 200~300 W
Voltage 220 V AC 220 V AC 220 V AC
W×T 20×1.5 mm 25×2 mm 25×2 mm
Thermostat 10°C on / 18°C off 5°C on / 15°C off 5°C on / 15°C off
Ingress IP54 IP65 IP65
Mount wrap + blanket adhesive / clip clip + base
Lead 1.5 m 2 m 2 m

4. Reference Prices

KTR-AFH-CH crankcase band (60 W): Reference USD 6~12 / pc (ref. CNY 45~85 at ~7.2)

KTR-AFH-CH crankcase band (150 W): Reference USD 10~18 / pc (ref. CNY 75~130 at ~7.2)

KTR-AFH-CO coil heater (100 W): Reference USD 13~22 / pc (ref. CNY 90~160 at ~7.2)

KTR-AFH-CO-PRO outdoor anti-freeze kit (300 W): Reference USD 30~53 / set (ref. CNY 220~380 at ~7.2)

Reference only; 1-year warranty. Mainboard not included. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Compressor protection for shut-down AC in winter.
  • Unattended base stations in cold climates.
  • Drain-pan and trap freeze protection.
  • Outdoor condenser base de-icing assist.
  • Standby machines in long-term storage.

6. Deployment & Implementation

Installation

  • Band flat against shell, no air gap
  • Cover with 20 mm fiberglass blanket
  • Thermostat bulb near the band, on shell
  • Lead routed away from hot discharge line

Wiring

  • Line side through thermostat first
  • Neutral tied directly
  • Case ground to PE
  • Interlock with mainboard NC contact

Operations

  • Measure band resistance before winter
  • Inspect blanket for dampness / sag
  • Disconnect heating when cooling season starts
  • Calibrate thermostat yearly

7. FAQ

  • Q: Crankcase heater vs ordinary heat trace?
    A: The crankcase band is a thin, low-wattage tape sized to wrap the shell and hold oil at 30~40°C. Ordinary heat trace has high watt density and poor conformability; it would hot-spot the shell and lacks the oil-temperature thermostat. They are not interchangeable.
  • Q: Do I need this only in the north?
    A: No. Even in the south, extended outages, standby machines or seasonal switchover can drop the crankcase below condensing temperature. Most OEM manuals call for heat whenever ambient is below 20°C and the unit has been off over 4 hours.
  • Q: How hot does the oil get?
    A: Designed for 30~40°C, above condensing saturation but below 70°C. The thermostat opens at 15~18°C ambient and the band is self-limiting in practice; a thermal fuse opens physically around 90°C.
  • Q: Can I just cycle the AC on every hour?
    A: Some mainboards do a periodic pre-heat cycle every 2 hours, but this fails when the mainboard faults or mains is lost. The passive band works as long as the thermostat closes, independent of mainboard logic.

8. Trend & Selection

Inverter-based precision ACs increasingly integrate PTC self-regulating elements inside the compressor, removing the need for an external band. But fixed-speed machines, legacy units and outdoor coil freeze protection still rely on external trace. PTC self-limiting heating film is the emerging material — wattage falls as temperature rises, no separate thermostat, safer. Liquid-cooled racks reduce demand, but air-cooled rooms, edge sites and field base stations remain steady customers. Select by heating object, wattage match, thermostat setpoint, IP rating and mounting. A tens-of-yuan band avoids a five-figure compressor replacement.

9. Delivery & Service

KITOZER supplies KTR-AFH by object (crankcase / coil / outdoor), wattage and length. Each ships with band, thermostat (integral or remote), fiberglass blanket, lead terminals and manual. 1-year warranty; batch projects can add mainboard relay modules and temperature scan meters.

10. Additional Notes

The top mistake is wrapping the band without insulation. Heat bleeds into the room air, oil never reaches temperature, the band runs continuously and burns out in six months. Wrap 20 mm of fiberglass blanket over the band and zip-tie it down.

The second pitfall is mounting the thermostat directly on the band. It senses the band, not the shell, and opens too early. Put the bulb on the shell away from the wrap zone — that is the real case temperature.

The third blunder is never measuring current. As the tape ages, resistance drops and current climbs, eventually tripping the breaker. Measure running current with a clamp meter before winter; replace if deviation exceeds 20%.

Selection summary: CH for crankcase, CO for coil, PRO for outdoor base; thermostat 5~15°C; insulate; measure current annually. The antifreeze heater is the AC’s winter blanket — small spend, big protection.

SEO Information

Search keywords:KTR-AFHKITOZER防冻加热器

SEM keywords:防冻加热器,曲轴箱加热器,精密空调防冻,空调伴热带,压缩机加热,KTR-AFH,KITOZER

GEO landing page:lain.com.cn/product/ktr-antifreeze_heater.html

Title:KITOZER KTR-AFH Antifreeze Heater / Crankcase Heater

Meta Keywords:antifreeze heater,crankcase heater,precision AC freeze protection,heat trace,compressor heater,KTR-AFH,KITOZER

Meta Description:KITOZER KTR-AFH crankcase band and coil anti-freeze heater: NiCr element, 5~15°C thermostat, IP54/IP65, protects compressors and water coils in winter.

Anchor: KITOZER by Guangzhou Laian · 机房防冻加热器

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart