KITOZER coax video SPD surge protector

KITOZER KTR-CXSP Coaxial Signal Surge Protector / Video SPD

Brand: KITOZER Series: KTR-CXSP Category: Power Distribution / Surge Protection

coax SPDBNC10 kA≤0.3 dBKTR-CXSP

1. Overview

Room CCTV cameras, satellite dishes and RF feeds run on coaxial cables that enter from outside or the telecom room. In thunderstorm seasons these cables pick up lightning surges that ride into the room and destroy camera BNC ports, DVR board cards and even switches. A coaxial SPD (surge protective device) is wired in series on the coax line: it passes signal normally, but in nanoseconds diverts surge energy to ground when a spike hits, protecting the equipment behind it.

KITOZER KTR-CXSP is designed for CCTV and RF feeds. KTR-CXSP-BNC: BNC female-female, 75 Ω, insertion loss ≤0.3 dB, nominal discharge 10 kA (8/20 μs), operating voltage ≤24 V, for analog CVBS cameras. KTR-CXSP-F: F-type, 75 Ω, for satellite and CATV. KTR-CXSP-N: N-type, 50 Ω, for industrial RF and microwave links. KTR-CXSP-POE-BNC: combined SPD protecting both coax video and DC12 V power in one pass-through.

Selection: by connector (BNC/F/N); by impedance (75 Ω video / 50 Ω RF); by discharge current (10 kA for most sites, 20 kA for long outdoor runs); and by whether video+power combo is needed. The ground lead must use ≥6 mm² yellow-green wire to the room’s equipotential bar, kept as short as possible.

2. Key Features

Electrical

  • 10 kA nominal (8/20 μs)
  • 20 kA max discharge
  • Voltage protection level ≤90 V
  • Response time ≤1 ns

Signal

  • 75 Ω / 50 Ω options
  • Insertion loss ≤0.3 dB
  • VSWR ≤1.2
  • Bandwidth 0~2 GHz

Structure

  • BNC / F / N connectors
  • Metal case, DIN-rail or wall
  • M5 ground stud
  • -40~+85°C operating

3. Specifications

Item KTR-CXSP-BNC KTR-CXSP-F KTR-CXSP-POE
Connector BNC F-F F-type BNC+DC12V
Impedance 75 Ω 75 Ω 75 Ω
Nominal current 10 kA 10 kA 10 kA
Max current 20 kA 20 kA 20 kA
Up ≤90 V ≤90 V ≤90 V
Insertion loss ≤0.3 dB ≤0.3 dB ≤0.5 dB
Operating V ≤24 V ≤24 V ≤24 V
Ground wire 6 mm² 6 mm² 6 mm²

4. Reference Prices

KTR-CXSP-BNC video SPD: Reference USD 5~9 / pc (ref. CNY 35~65 at ~7.2)

KTR-CXSP-F RF F-type SPD: Reference USD 6~10 / pc (ref. CNY 40~75 at ~7.2)

KTR-CXSP-N N-type SPD: Reference USD 8~13 / pc (ref. CNY 55~95 at ~7.2)

KTR-CXSP-POE video+power combo: Reference USD 10~18 / pc (ref. CNY 75~130 at ~7.2)

Reference only; 1-year warranty. Ground bar not included. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Outdoor camera coax feed at building entry.
  • Satellite / CATV drop protection.
  • Microwave / RF link front-end.
  • DVR/NVR input protection.
  • Intercom / antenna distribution.

6. Deployment & Implementation

Installation

  • Series in the coax, close to protected gear
  • Grade at outdoor end + room end
  • Ground lead ≤0.5 m, as short as possible
  • Ground to equipotential bar

Wiring

  • IN from outdoor, OUT to equipment
  • BNC connectors hand-tight + wrench
  • 6 mm² yellow-green ground wire
  • Multiple SPDs share one ground bar

Operations

  • Check video after thunderstorms
  • Replace when degradation window turns red
  • Test ground resistance ≤4 Ω yearly
  • SPD service life 3~5 years

7. FAQ

  • Q: Camera still fried despite SPD?
    A: Three usual causes: (1) ground lead over 1 m long — its inductance defeats clamping; (2) SPD only at room end, no grade at outdoor pole, so the long cable’s induced surge isn’t attenuated before entry; (3) ground resistance over 10 Ω, surge can’t drain. Correct: grade at outdoor pole and room end, ground lead ≤0.5 m, resistance ≤4 Ω.
  • Q: BNC, F, N — how to tell?
    A: BNC is a bayonet, 75 Ω, for analog CCTV. F is a threaded imperial connector, 75 Ω, for satellite/CATV. N is a waterproof threaded connector, 50 Ω, for industrial RF. Mismatched connectors fail or won’t plug. Check the equipment end before ordering.
  • Q: Does an SPD affect picture quality?
    A: A qualified coax SPD has ≤0.3 dB insertion loss and ≤1.2 VSWR, essentially invisible to analog CVBS and 1080P coax HD. Cheap SPDs with over 1 dB loss cause horizontal bands and snow. Spec bandwidth ≥2 GHz and loss ≤0.3 dB.
  • Q: Do IP cameras need coax SPD?
    A: No. IP cameras run on Ethernet — use an RJ45 network SPD. Coax SPD is only for BNC/F/N video, RF and satellite feeds. Don’t put a coax SPD on a network cable; connector and impedance are both wrong.

8. Trend & Selection

Coax CCTV is being displaced by IP cameras, so new coax SPD demand is softening, but retrofit and traditional security systems still buy heavily. Modern SPDs trend to multi-stage diversion with remote contact: the SPD degradation state reports to the EM host over a dry contact, eliminating manual inspection. Combined SPDs (video+power+network in one) are increasingly popular at front-end cameras. Select by connector, impedance, short ground lead and staged protection. A tens-of-yuan SPD protects cameras and board cards worth thousands.

9. Delivery & Service

KITOZER supplies KTR-CXSP by connector (BNC/F/N), with/without power combo, and discharge current. Each ships with SPD body, ground lead and manual. 1-year warranty; batch projects can add signal surge boxes and equipotential bars.

10. Additional Notes

The top mistake is long ground leads. The SPD sits in the rack but the ground lead loops twice around the rack to the bar — 2 m long with tens of nH inductance, lifting the clamping voltage from 90 V to 300 V, defeating the whole device. Keep the lead straight, short (≤0.5 m) and thick (≥6 mm²).

The second pitfall is only protecting the room end. The outdoor coax run is a huge antenna; one indoor SPD can’t absorb the whole induced surge. Grade at the outdoor camera pole and again at the room — two stages work together.

The third blunder is never replacing degraded SPDs. An SPD is a consumable; each surge event ages it. When the status window turns from green to red, replace it. A failed SPD in line is a signal breakpoint with no protection.

Selection summary: BNC for video, F for RF, N for industrial; short ground lead; staged protection; replace on degradation. The coax SPD is the surge gate on video lines — small cost, big protection.

SEO Information

Search keywords:KTR-CXSPKITOZER同轴防雷器

SEM keywords:同轴防雷器,视频SPD,BNC防雷器,信号浪涌保护,机房防雷,KTR-CXSP,KITOZER

GEO landing page:lain.com.cn/product/ktr-coax_spd.html

Title:KITOZER KTR-CXSP Coaxial Signal Surge Protector / Video SPD

Meta Keywords:coax SPD,video surge protector,BNC lightning arrester,signal surge protection,KTR-CXSP,KITOZER

Meta Description:KITOZER KTR-CXSP coax surge protector: BNC/F/N, 75/50 Ω, 10 kA discharge, ≤0.3 dB loss, protects outdoor cameras and RF feeds.