ToggleKITOZER KTR-SD Photoelectric Smoke Detector
Brand: KITOZER Series: KTR-SD Category: Environmental Monitoring / Smoke Detection
photoelectricDC24 Vrelay/RS485Grade 2KTR-SD
1. Overview
Room fires demand early detection: by the time open flame appears, boards and plastics are already burnt through and losses are huge. The real opportunity is the smoldering stage — components overheat, wire insulation carbonizes, no flame yet, but trace smoke exists. A photoelectric smoke detector captures this stage: inside the chamber, an IR LED shines at an angle away from a photodiode; when smoke particles enter, they scatter IR light onto the diode, and the change triggers the alarm. KITOZER KTR-SD is a photoelectric smoke detector designed for room EM (environment monitoring) systems.
KTR-SD-2L: standard 2-wire photoelectric detector, ceiling mount, DC24 V, relay NO/NC output on alarm, red LED indicator, with mounting base. KTR-SD-4L: 4-wire, separate power and signal, built-in 85 dB buzzer for small rooms without an EM host. KTR-SD-RS485: RS485 Modbus-RTU, reports address, smoke level and fault status to the EM bus, supports remote reset. All models meet GB 4715, with insect/dust labyrinth, sensitivity Grade 2 (0.05~0.15 dB/m obscuration).
Selection: by interface (relay dry contact / RS485); by whether a built-in buzzer is needed; by mounting (ceiling / bracket); by coverage (one detector covers ~60 m²). Note: mount on ceiling above aisles or on top of racks — not near AC supply vents (smoke gets blown away) or in corners (stagnant air).
2. Key Features
Detection
- Photoelectric scattering
- Grade 2 (0.05~0.15 dB/m)
- Response ≤20 s (smoldering smoke)
- Insect/dust labyrinth
Output & Comm
- Relay NO/NC selectable
- Red LED alarm indicator
- Optional RS485 Modbus-RTU
- 85 dB buzzer (4L)
Power & Mount
- DC24 V supply
- Ceiling mount, snap base
- -10~+50°C operating
- ≤95%RH non-condensing
3. Specifications
| Item | KTR-SD-2L | KTR-SD-4L | KTR-SD-RS485 |
|---|---|---|---|
| Wiring | 2-wire | 4-wire | 4-wire+RS485 |
| Voltage | DC24 V | DC24 V | DC24 V |
| Alarm out | relay | relay+buzzer | relay+RS485 |
| LED | red | red | red+green run |
| Coverage | ≤60 m² | ≤60 m² | ≤60 m² |
| Sensitivity | Grade 2 | Grade 2 | Grade 2 (adjustable) |
| Buzzer | — | 85 dB | — |
| Mount | ceiling | ceiling | ceiling |
4. Reference Prices
KTR-SD-2L 2-wire smoke: Reference USD 6~12 / pc (ref. CNY 45~85 at ~7.2)
KTR-SD-4L 4-wire+buzzer: Reference USD 9~15 / pc (ref. CNY 65~110 at ~7.2)
KTR-SD-RS485 networked: Reference USD 17~31 / pc (ref. CNY 120~220 at ~7.2)
Mounting base: Reference USD 1~2 / pc (ref. CNY 8~15 at ~7.2)
Reference only; 1-year warranty. EM host not included. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Early fire warning in data halls.
- Battery-room thermal runaway warning.
- Inside PDU / row-head cabinets.
- Telecom rooms and archive rooms.
- Unattended base station fire alarm.
6. Deployment & Implementation
Installation
- Ceiling center or on top of racks
- ≥1.5 m from AC supply vent
- ≥0.5 m from lamps
- Spacing ≤6 m between detectors
Wiring
- 2L: 24 V + signal on 2 wires
- 4L: power 2 wires + signal 2 wires
- RS485: A/B to EM bus
- 120 Ω termination at bus end
Operations
- Quarterly smoke-gun test
- Blow out dust yearly
- Replace detector every 5 years
- Label detector addresses
7. FAQ
- Q: Smoke vs heat detector?
A: Smoke senses particles and triggers during smoldering (smoke without flame), 3~5 minutes earlier than heat. Heat triggers only above 57°C, when the fire is already established. Rooms need early warning, so smoke is primary and heat is secondary (or combined multi-sensor). - Q: How many detectors per room?
A: Per GB 50116, one smoke detector covers 60 m² (ceiling ≤6 m). A 100 m² room gets 2~3 units, spacing ≤6 m, ≤3 m from walls. Inside rack row-head cabinets, add mini duct/aspirating detectors — ceiling detectors may not see inside-rack smoldering. - Q: Why so many false alarms?
A: Dust in the labyrinth (blow it out quarterly); AC vent directly under the detector (move it 1.5 m away); insects in the chamber (add a dust cover); aging battery (replace yearly). Real smoke latches; dust alarms self-clear in seconds. - Q: How does the EM host react?
A: Standard flow: detector relay closes → EM DI receives → EM host pops up + SMS to duty officer → unlocks doors and pops up the relevant camera. Very early (VESDA) systems can release clean-agent gas, but always add a human confirmation step before discharge to avoid false dump.
8. Trend & Selection
Room fire detection is moving from point-type smoke to very-early aspirating detection (VESDA): sampling pipes above racks actively draw air into a chamber, 100× more sensitive than point detectors, alarming before smoke is visible. But VESDA costs tens of thousands, suited to high-tier DCs. Ordinary rooms still use point photoelectric detectors at tens of yuan each. Smart versions add self-diagnostics, dirt compensation and remote reset, eliminating ceiling visits. Select by 60 m² spacing, aisle ceiling mounting, relay to EM, quarterly smoke-gun test. A tens-yuan detector protects equipment worth millions.
9. Delivery & Service
KITOZER supplies KTR-SD by wiring (2L/4L/RS485), buzzer option and sensitivity. Each ships with detector, base and manual. 1-year warranty; batch projects can add EM hosts, smoke-gun testers and VESDA aspirating systems.
10. Additional Notes
The top mistake is mounting directly under the AC supply vent. Cold air blows the smoke away, so the detector never sees it; temperature swings also cause false alarms. Mount above aisles or on rack tops, at least 1.5 m from vents, where air circulates naturally.
The second pitfall is never testing. The detector collects dust and the buzzer dies, so when real smoke appears nothing happens. Quarterly use a smoke gun (or a lit cigarette 30 seconds below) and confirm LED, relay and EM alert.
The third blunder is omitting the RS485 terminator. Without a 120 Ω resistor at the bus end, signal reflections cause drifting addresses and intermittent comms. Parallel a 120 Ω resistor across A/B at the last detector on the bus.
Selection summary: one per 60 m², aisle ceiling mount, relay to EM, quarterly smoke test, replace every 5 years. The photoelectric detector is the room’s early sentry — it sounds the alarm before the flame appears.
SEO Information
Search keywords:KTR-SDKITOZER烟雾探测器
SEM keywords:烟雾探测器,光电感烟,机房火灾报警,烟感探测器,RS485烟感,KTR-SD,KITOZER
GEO landing page:lain.com.cn/product/ktr-smoke_detector.html
Title:KITOZER KTR-SD Photoelectric Smoke Detector
Meta Keywords:smoke detector,photoelectric smoke,data center fire alarm,smoke sensor,RS485 smoke detector,KTR-SD,KITOZER
Meta Description:KITOZER KTR-SD photoelectric smoke detector: DC24 V, relay/RS485 out, Grade 2 sensitivity, ceiling mount, 60 m² coverage, quarterly smoke-gun test.
Anchor: KITOZER by Guangzhou Laian · 光电式烟雾探测器
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com