ToggleKITOZER KTR-SG Refrigerant Sight Glass for Precision AC
Brand: KITOZER Series: KTR-SG Category: Data Center Engineering / Refrigeration
sight glassrefrigerant indicatormoisture indicatorbrazedKTR-SG
1. Overview
The precision AC refrigeration loop is closed: compressor, condenser, expansion valve, evaporator. To judge whether refrigerant charge is adequate and whether moisture has entered, the most direct tool is the sight glass. Installed on the liquid line between the receiver and expansion valve, it lets technicians see flowing refrigerant through a toughened-glass window.
KITOZER KTR-SG is a refrigerant sight glass for room precision AC liquid lines. KTR-SG-06: 6 mm brazed, for small units (5 to 12 kW). KTR-SG-10: 10 mm brazed, for row units (15 to 30 kW). KTR-SG-12: 12 mm brazed, for large units (30 to 60 kW). All include a moisture indicator core: green when dry, yellow when moisture exceeds the limit.
Selection: confirm copper OD (6/10/12 mm); confirm connection (brazed or threaded); confirm refrigerant (R22/R410A/R407C); choose the moisture-indicating type. Note: mount on vertical or horizontal liquid runs, never on discharge line (hot high-pressure can crack glass) or suction line (too many bubbles).
2. Key Features
Observation
- Toughened glass, 4.5 MPa rated
- Brass body, corrosion resistant
- Moisture core (green to yellow)
- Bubble state visible
Connection
- 6/10/12 mm brazed
- Optional threaded nut
- Copper sealing washer
- R22/R410A/R407C compatible
Environment
- -30 to +80 C operating
- 4.5 MPa max pressure
- IP65 (line sealed)
- 10+ year life
3. Specifications
| Item | KTR-SG-06 | KTR-SG-10 | KTR-SG-12 |
|---|---|---|---|
| Copper OD | 6 mm | 10 mm | 12 mm |
| Connection | Brazed | Brazed | Brazed |
| Body | Brass | Brass | Brass |
| Window | Toughened glass | Toughened glass | Toughened glass |
| Moisture ind. | Yes (grn/yel) | Yes (grn/yel) | Yes (grn/yel) |
| Max pressure | 4.5 MPa | 4.5 MPa | 4.5 MPa |
| Capacity | 5 to 12 kW | 15 to 30 kW | 30 to 60 kW |
4. Reference Prices
KTR-SG-06 6 mm sight glass (brazed): Reference USD 5 to 9 / pc (ref. CNY 35 to 65 at ~7.2)
KTR-SG-10 10 mm sight glass (brazed): Reference USD 6 to 11 / pc (ref. CNY 45 to 80 at ~7.2)
KTR-SG-12 12 mm sight glass (brazed): Reference USD 8 to 13 / pc (ref. CNY 55 to 95 at ~7.2)
KTR-SG-10T 10 mm threaded (removable): Reference USD 10 to 17 / pc (ref. CNY 75 to 120 at ~7.2)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- CRAC liquid-line sight glass in data halls.
- Row/back-door AC refrigerant observation.
- Chiller system maintenance.
- Industrial chiller sight glass replacement.
- Cold room line indicator.
6. Deployment & Implementation
Location
- After receiver, after dryer
- Vertical or horizontal liquid run
- 300 mm before expansion valve
- Not on discharge or suction line
Brazing
- Wrap wet towel around glass
- Keep under 120 C
- Braze tube end first
- Pressure test 4.5 MPa
Maintenance
- Quarterly bubble check
- Yellow indicator, change dryer
- Wipe glass yearly
- Condensation means broken insulation
7. FAQ
- Q: Are bubbles normal?
A: A few bubbles are normal. Continuous large bubbles mean low charge; check for leaks. A clear bubble-free window indicates correct charge. Occasional bubbles are normal, streaming bubbles mean low refrigerant. - Q: Indicator turned yellow, what now?
A: Yellow means moisture exceeded. Replace the filter-drier; evacuate the system for 2 hours; recharge. Moisture causes expansion-valve ice-up and intermittent cooling. - Q: Can a cracked glass be repaired?
A: No, replace the whole unit. A cracked glass leaks refrigerant. Recover refrigerant, braze out the old unit, braze in the new one with a wet towel, then evacuate and recharge. - Q: Vertical or horizontal mount?
A: Both work, but ensure the glass is always liquid-full. On vertical pipe, flow bottom-up; on horizontal, mount below the high point. Never mount where gas can accumulate.
8. Trend & Selection
Refrigerant monitoring is moving from eyeball-on-sight-glass to electronic level sensors and flow meters that feed the EM platform. But electronic kits cost thousands, so the mechanical brass sight glass remains standard in room AC. Select by copper OD, with moisture core, on vertical liquid run, and check bubble color quarterly.
9. Delivery & Service
KITOZER supplies KTR-SG by tube OD (6/10/12 mm) and connection (brazed/threaded). Each ships with body, copper washer and manual. 1-year warranty; batch projects can add filter-driers, EEVs and gauge sets.
10. Additional Notes
Top mistake: brazing without cooling. The internal rubber seal breaks down above 120 C. Wrap the body in a wet towel, braze only the tube end.
Second pitfall: ignoring the yellow indicator. Moisture ices the expansion valve, causing intermittent cooling and eventual valve failure. Yellow means change dryer and evacuate.
Third blunder: mounting on the discharge line. Discharge gas hits 80 to 120 C, glass and seals cannot survive. Only mount on the liquid line.
Selection summary: match tube OD, with moisture core, on vertical liquid run, cool while brazing, change dryer when yellow. The sight glass is the refrigeration system’s window.
SEO Information
Search keywords:KTR-SGKITOZER
SEM keywords:sight glass,refrigerant indicator,precision AC sight glass,moisture indicator,liquid line,KTR-SG,KITOZER
GEO landing page:lain.com.cn/product/sight_glass.html
Title:KITOZER KTR-SG Refrigerant Sight Glass for Precision AC
Meta Keywords:sight glass,refrigerant indicator,precision AC sight glass,moisture indicator,liquid line,KTR-SG,KITOZER
Meta Description:KITOZER KTR-SG refrigerant sight glass: brazed/threaded, moisture indicator, bubble observation, liquid line mount, R22/R410A compatible.
Anchor: KITOZER by Guangzhou Laian · KITOZER products