Brand: KITOZER Series: KTR-PB Category: Power Distribution / Surge Protection
3-stage SPD40-100kARemote alarm35mm railKTR-PB
1. Overview
Lightning is the #1 enemy of room equipment. A direct strike on an outdoor antenna or rooftop sends tens of thousands of volts of surge down power and signal lines into the room, destroying switches, servers and UPSes. Even without a local strike, remote lightning induces surges on the grid that degrade power supplies year after year. A surge protective device (SPD) sits in parallel on the power line as a voltage clamp: normally it is high-impedance and idle, but when voltage exceeds the clamp (say 1000 V), it instantly conducts and diverts surge current to ground, holding the residual voltage within equipment tolerance (under 1500 V at the device end), then returns to high impedance. The SPD box packages SPD modules in a metal enclosure with terminals and remote alarm — mounted at the room distribution cabinet input, and is mandatory in room power systems.
KITOZER KTR-PB is a 3-stage room power SPD box. KTR-PB-40: Class-2 SPD box, 40 kA (8/20 μs), Ucpv 385 V, residual voltage under 1800 V, with remote dry-contact to the EM host — for floor distribution to room cabinet. KTR-PB-80: Class-1 SPD box, 80 kA, for the room main distribution cabinet input. KTR-PB-100: combined B+C SPD box, 100 kA (10/350 μs), for high-thunderstorm regions or overhead outdoor feeds. All use plug-in 35 mm rail modules: when a module fails the indicator turns red and you pull it out and swap — no need to power down the whole box. Degradation window (green=good, red=failed) and remote terminals included.
Selection: confirm stage (main cabinet 80-100 kA, floor box 40 kA, rack PDU 10-20 kA final stage); confirm 3-phase vs single (main room = 3-phase 380 V, rack PDU = single 220 V); confirm remote contacts (required if tying to EM host); confirm waveform (8/20 μs for induced lightning, 10/350 μs for direct strike — rooms typically need 8/20 μs). Critical: the SPD must ground reliably — earth resistance under 4 ohm, ground wire at least 16 mm², or surge cannot drain to ground.
2. Key Features
Electrical
- 40 / 80 / 100 kA discharge
- Ucpv 385 V
- Voltage protection level under 1800 V
- Response time under 25 ns
Construction
- Painted metal enclosure
- 35 mm rail plug-in modules
- Degradation window (green/red)
- Dry-contact remote output
Wiring
- 3-phase 5-wire (L1/L2/L3/N/PE)
- Top-in bottom-out terminals
- 35 mm² max wire
- Rail or wall mount
3. Specifications
| Item | KTR-PB-40 | KTR-PB-80 | KTR-PB-100 |
|---|---|---|---|
| Class | Class 2 (C) | Class 1 (B) | B+C combo |
| Discharge (8/20μs) | 40 kA | 80 kA | 100 kA |
| Ucpv | 385 V | 385 V | 385 V |
| Residual voltage | <1800 V | <2000 V | <2200 V |
| Phases | 3/1 phase opt. | 3-phase 5-wire | 3-phase 5-wire |
| Remote alarm | Yes | Yes | Yes |
| Typical use | Floor box | Room main cabinet | Overhead feed |
4. Reference Prices
KTR-PB-40 Class-2 SPD box (3-phase): Reference USD 49 to 76 / pc (ref. CNY 350 to 550 at ~7.2)
KTR-PB-80 Class-1 SPD box (3-phase): Reference USD 90 to 132 / pc (ref. CNY 650 to 950 at ~7.2)
KTR-PB-100 B+C combo SPD box: Reference USD 125 to 194 / pc (ref. CNY 900 to 1400 at ~7.2)
SPD spare module: Reference USD 11 to 21 / pc (ref. CNY 80 to 150 at ~7.2)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Room main cabinet input surge protection.
- Floor distribution box secondary protection.
- UPS front-end surge protection.
- Outdoor AC unit power protection.
- Outdoor base station / cabinet feeds.
6. Deployment & Installation
Placement
- Wire in after the main breaker
- Near the grounding bar; keep lead short
- Mount SPD modules vertically on rail
- Leave space in front for module swap
Grounding
- Earth resistance under 4 ohm
- Ground wire at least 16 mm²
- Ground lead under 0.5 m
- Connect to room equipotential bar
Alarm Link
- Wire remote contacts to EM host DI
- SPD failure (red window) triggers alarm
- Replace module promptly on alarm
- Inspect annually before thunder season
7. FAQ
- Q: How many SPD stages does a room need?
A: Code requires three: Class-1 at the building main cabinet (100 kA, 10/350 μs), Class-2 at floor distribution (60 kA, 8/20 μs), Class-3 at the room cabinet or UPS front (40 kA). If the building already has Class-1, add Class-2 and -3 in the room. If the building has none, the room needs at least Class-1 (80 kA) plus a final 10 kA at the PDU. Do not rely on a single stage — residual voltage must be stepped down at each stage to below 2000 V at the device. - Q: How do I know the SPD is worn out?
A: Each SPD module has a window: green=good, red=failed. The internal MOV degrades a little with every surge, and after years leakage current rises until it fails short. When the window turns red the remote contact closes and the EM host alarms. Replace the module when you see red. Do not wait for a short circuit fire. Inspect before every thunder season. - Q: Does a long ground lead matter?
A: Yes, a lot. The longer the SPD-to-ground lead, the higher the lead inductance, and the higher the residual voltage at the equipment during a surge. Code requires the SPD-to-ground lead under 0.5 m, short and straight, no loops. A 2 m lead can add 1000 V residual, defeating protection. Mount the SPD box right next to the grounding bar. - Q: Do signal lines need SPD too?
A: Yes. Power is protected, but Ethernet, fiber (non-conductive, no SPD needed) and RS485 lines also induce surges. Outdoor Ethernet runs need RJ45 signal SPDs; outdoor RS485 lines need 485 signal SPDs; antenna feeds need antenna SPDs. Indoor short in-rack Ethernet does not. Power + signal together = complete protection.
8. Trend & Selection
SPD technology is moving from “single MOV” to “multi-module combo”: B+C units combine switching-type (10/350 μs high-current) and clamping-type (8/20 μs low residual) in one box, covering Class-1 and -2. Smart SPDs add current sensing to log every surge amplitude and count, predict lifespan, and upload storm logs remotely. Plug-in modules are standard — swap the bad module without powering down. Select by: main cabinet 80 kA 3-phase, remote dry contacts, earth under 4 ohm, short straight ground lead under 0.5 m, inspect before thunder season. The SPD box is the power system’s lightning shield — install right and you sleep through storms.
9. Delivery & Service
KITOZER supplies KTR-PB by discharge (40/80/100 kA) and phase (3/1). Each ships with box, SPD modules, mounting rail and manual. 1-year warranty; batch projects can bundle signal SPDs, grounding bars and equipotential terminal boxes.
10. Additional Notes
Top mistake: running a long, looped ground lead. The longer the lead, the higher the inductive drop during a surge, and the higher the residual — defeating protection. SPD to ground bar must be short and straight, under 0.5 m, at least 16 mm².
Second pitfall: only installing Class-1 and skipping the final stage. The 80 kA SPD at the main cabinet leaves ~2000 V residual — still enough to damage UPS and servers. Add a 10-20 kA final SPD at the rack PDU to clamp residual below equipment safety. Each stage steps down the residual.
Third blunder: leaving a failed SPD in service. A red-window SPD has shorted out and does nothing. The next strike goes straight through to gear. Swap modules the day you see red or the EM alarm. Keep spares in stock.
Selection summary: main cabinet 80 kA 3-phase, remote contacts, earth under 4 ohm, short ground lead, swap on red. The SPD box is the power system’s life insurance — do not skip it in storm-prone regions.
SEO Information
Search keywords:KTR-PBKITOZER
SEM keywords:SPD box,power surge protector,surge protective device,lightning arrestor,room SPD box,KTR-PB,KITOZER
GEO landing page:lain.com.cn/product/power_spd_box.html
Title:KITOZER KTR-PB Power SPD Surge Protection Box
Meta Keywords:SPD box,power surge protector,surge protective device,lightning arrestor,room SPD box,KTR-PB,KITOZER
Meta Description:KITOZER KTR-PB power surge protection box: 3-stage, 40-100kA, remote alarm, room distribution cabinet surge protection.
Anchor: KITOZER by Guangzhou Laian · KITOZER products
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com