Brand: KITOZER Series: KTR-FD2 Category: Data Center Engineering / Refrigeration Loop
Filter DrierReplaceable CoreR410ABrass SolderKTR-FD2

1. Overview
In a precision air-conditioning refrigeration loop, the filter drier is an unremarkable yet indispensable component. The loop is sealed after factory evacuation and refrigerant charge, but field installation, brazing and servicing inevitably introduce air, moisture, oxide scale and brazing slag. Moisture freezes at the low-temperature expansion-orifice (called ice-up) and hydrolyzes with refrigerant and oil on the high side, producing acids that attack compressor windings. Slag and scale score valve seats and bearings. Mounted in the liquid line between condenser and expansion valve, the drier uses molecular sieve to adsorb water and a mesh to trap particles. Room precision ACs run over 8,000 hours a year, so the core saturates and is replaced every 2 to 3 years.
KITOZER KTR-FD2 is a shell-type (replaceable-core) drier, as opposed to the hermetic brazed cartridge. KTR-FD2-A: 12.7 mm solder port for 5-12 kW units; KTR-FD2-B: 16 mm port for 12-25 kW; KTR-FD2-C: 22 mm port for 25-60 kW air- or water-cooled units. The shell is seamless copper tube with removable brass end caps; inside sits a replaceable composite core (molecular sieve plus mesh). When saturated, only the core is swapped. Compatible with R22, R410A and R407C and mineral or POE ester oils. Working pressure 4.5 MPa, burst pressure 25 MPa; a sight-glass variant FD2-SW shows moisture indication.
Selection: match port size to cooling capacity (12 mm for 5 kW, 16 mm for 20 kW, 22 mm for 50 kW); choose core type by refrigerant (POE ester core for R410A, mineral-oil core for R22); decide whether a sight glass is needed; respect the flow arrow, never backwards. Note: driers belong only in the liquid line, not the suction line; core swaps require pump-down, evacuation and re-charge, never venting to atmosphere.
2. Key Features
Construction
- Seamless copper shell
- Brass removable caps
- Replaceable composite core
- Solder or flange ends
Media
- Zeolite molecular sieve
- Woven metal mesh
- Adsorbs water and acid
- Catches 50 um particles
Rating
- Working press. 4.5 MPa
- Burst press. 25 MPa
- R22/R410A/R407C
- Horizontal liquid line
3. Specifications
| Item | KTR-FD2-A | KTR-FD2-B | KTR-FD2-C |
|---|---|---|---|
| Port size | OD12.7 mm | OD16 mm | OD22 mm |
| Capacity | 5-12 kW | 12-25 kW | 25-60 kW |
| Core | Replaceable | Replaceable | Replaceable |
| Working press. | 4.5 MPa | 4.5 MPa | 4.5 MPa |
| Refrigerant | R22/R410A | R22/R410A | R22/R410A/R407C |
| Sight glass | Optional | Optional | Standard |
| Mount | Horizontal | Horizontal | Horizontal |
4. Reference Prices
KTR-FD2-A drier (12 mm): Reference USD 25 to 36 / pc (ref. CNY 180-260 at ~7.2)
KTR-FD2-B drier (16 mm): Reference USD 36 to 53 / pc (ref. CNY 260-380 at ~7.2)
KTR-FD2-C drier (22 mm): Reference USD 53 to 78 / pc (ref. CNY 380-560 at ~7.2)
Replacement core (each): Reference USD 8 to 17 / pc (ref. CNY 60-120 at ~7.2)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Precision AC indoor unit liquid line
- Between condenser and TXV
- Heat-pump defrost loop
- Chiller evaporator feed
- Condensate units beside UPS
6. Deployment & Installation
Placement
- Horizontal liquid line
- Arrow with flow
- Close before TXV
- Service clearance both ends
Brazing
- Cool shell during brazing
- Keep flame off core
- Nitrogen purge after brazing
- Evacuate to -0.1 MPa
Replacement
- Swap core after year 1
- Then every 2-3 years
- Swap when sight glass changes
- Always swap after compressor overhaul
7. FAQ
- Q: What if the drier is installed backwards?
A: The mesh bypasses and debris passes through; the molecular sieve is shattered by high-pressure flow, and fragments travel to the TXV orifice, causing a second blockage. A stamped arrow on the shell must face condenser-to-TXV. - Q: How do I know the core is spent?
A: Three signs: sight-glass indicator turns from green to yellow or red; inlet-to-outlet temp difference over 3 C; cooling capacity drops with TXV hissing, looking like low charge but actually a blocked drier. - Q: Hermetic vs replaceable core?
A: Under 5 kW, a hermetic brazed cartridge under USD 10 is fine; over 25 kW, choose replaceable-core. The shell costs USD 50-80 but a core is only USD 10-15, so three core swaps over 5 years beat three whole driers. Most room precision ACs are 12 kW+, so KTR-FD2 is the right call. - Q: Do I have to recover refrigerant when swapping?
A: Yes. Close the condenser outlet valve, run the compressor to pump down the low side, close the suction valve, then open the drier. After the core swap, evacuate for at least 2 hours before recharging. Venting wastes refrigerant and lets moisture back in.
8. Trend & Selection
Precision ACs are moving toward larger capacity, longer life and lower maintenance. Though small, driers matter more as new refrigerants R32 and R454B bring hygroscopic POE ester oils that demand better molecular sieves. The trend is smart driers with pressure-differential sensors that remotely detect clogging and tell ops when to swap. Standardized shells and universal cores reduce spares cost. Select by: port sized to capacity, replaceable-core construction, sight glass, POE core for R410A, horizontal mount before the TXV. A tiny drier protects a compressor worth thousands of dollars.
9. Delivery & Service
KITOZER supplies KTR-FD2 by model. Each ships with unit, mounting accessories and manual. 1-year warranty; batch projects can bundle peripheral gear and on-site commissioning.
10. Additional Notes
Confirm port specs, power rating and communication protocol against field equipment before ordering; keep clear of strong EMI and heat sources; verify wiring and labels before energizing. For batch orders, request samples first to confirm compatibility with existing systems.
Common mistake: comparing price but ignoring parameters. Models in the same series look similar, but ports, load and accuracy differ — wrong models cause on-site rework. Send the full part number (including suffix such as -SM/-MM/-S) to sales to confirm.
Second pitfall: not planning service space. Leave at least 600 mm rear cable/service space and 800 mm front operating space, or future swaps and cable work become painful.
Third blunder: shipping factory alarm thresholds. Default thresholds rarely match site conditions — tune them after commissioning based on real readings to avoid both false and missed alarms.
Selection summary: match site conditions first, pick model, reserve service space, calibrate thresholds on-site, and pilot one unit before bulk.
SEO Information
Search keywords:KTR-FD2KITOZER
SEM keywords:filter drier,precision AC filter drier,shell filter drier,refrigeration drier,KTR-FD2,KITOZER
GEO landing page:lain.com.cn/product/ktr-fd2-filter-drier.html
Title:KITOZER KTR-FD2 Shell Filter Drier for Precision AC
Meta Keywords:filter drier,precision AC filter drier,shell filter drier,refrigeration drier,KTR-FD2,KITOZER
Meta Description:KITOZER KTR-FD2 shell filter drier with replaceable core, brass solder connections, R410A/R22, protects TXV and compressor.