ToggleKITOZER KTR-2V500 2V500Ah VRLA Battery
Brand: KITOZER Series: KTR-2V500 Category: Power Distribution / Battery Bank
2V500AhVRLA AGMLong lifeDeep cycleKTR-2V500
1. Overview
Batteries are the UPS last line of defense. After mains loss, the diesel generator takes 10-30 seconds to start; during that gap the battery bank carries everything. An undersized bank makes the UPS transfer to bypass and servers drop; a poorly matched bank has a weak cell that dies early, dragging the whole string down and shutting the UPS early. Datacenters string 2 V or 12 V cells into 380-480 V DC buses. 2 V cells, with big single jars and good heat dissipation, suit large-capacity (200 Ah+) long backup; 12 V small batteries suit small UPS and emergency lighting. 500 Ah is the mainstream 2 V size: 40 cells (2 V x 40) in parallel strings support a 100 kVA UPS for 15 minutes.
KITOZER KTR-2V500 is a 2 V 500 Ah VRLA AGM battery. Nominal 2 V, rated 500 Ah (C10, 25 C); cylindrical jar about 240x190x765 mm, about 78 kg including terminals; float design life 15 years at 25 C (float 2.25 V/cell); lead-calcium grids, AGM absorbent glass mat, non-spill; tinned-copper M8 bolt terminals; self-discharge under 3% per month; operating temp -15 to +50 C (ideal 20-25 C). Models: KTR-2V500-F: standard 15-year float; KTR-2V500-L: 20-year long-life (reinforced plates); KTR-2V500-H: high-rate (15-minute UPS discharge).
Selection: size by backup time (100 kVA UPS at 0.9 PF = 90 kW, 384 V bus = 234 A; 15-minute discharge factor is about 1.8, so 500 Ah delivers ~900 Ah for 15 minutes, enough for parallel strings); confirm bus voltage (192/240/384/480 V dictates cell count); choose high-rate for short discharge; verify rack/room floor loading (78 kg x 40 cells = 3,120 kg per string, check floor). Note: battery-room temperature must stay 20-25 C; every 10 C above halves life.
2. Key Features
Electrical
- 2 V 500 Ah C10
- Float 2.25 V/cell
- Equalize 2.35 V/cell
- <3% self-discharge/month
Build
- AGM separator
- Pb-Ca grids
- Tinned Cu M8 terminal
- Valve-regulated non-spill
Life
- 15-yr float at 25 C
- 800 cycles at 80% DOD
- Long cycle life
- Low self-discharge
3. Specifications
| Item | KTR-2V500-F | KTR-2V500-L | KTR-2V500-H |
|---|---|---|---|
| Nominal V | 2 V | 2 V | 2 V |
| Capacity | 500 Ah C10 | 500 Ah C10 | 500 Ah C10 |
| Design life | 15 yr | 20 yr | 12 yr |
| Max discharge | 3000 A/5min | 3000 A/5min | 5000 A/1min |
| Size (mm) | 240x190x765 | 240x190x765 | 240x190x765 |
| Weight | 78 kg | 82 kg | 78 kg |
| Use | UPS/DC panel | Long backup/ESS | High-rate UPS |
4. Reference Prices
KTR-2V500-F 15-yr standard: Reference USD 174 to 215 / pc (ref. CNY 1250-1550 at ~7.2)
KTR-2V500-L 20-yr long-life: Reference USD 215 to 271 / pc (ref. CNY 1550-1950 at ~7.2)
KTR-2V500-H high-rate: Reference USD 188 to 233 / pc (ref. CNY 1350-1680 at ~7.2)
Inter-cell link (tinned copper): Reference USD 5 to 8 / pc (ref. CNY 35-60 at ~7.2)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Datacenter UPS battery banks
- Telecom room DC panels
- Substation operating power
- Solar ESS plants
- Industrial EPS emergency power
6. Deployment & Installation
Mount
- Rack/cabinet layered
- Insulating mats between layers
- Verify floor load
- Ventilation gaps
Wiring
- Link torque 12 N·m
- Series polarity consistent
- Main cable sized correctly
- Coat terminals with grease
Ops
- Measure cell voltage quarterly
- Capacity test annually
- Room 20-25 C
- Swap weak cells promptly
7. FAQ
- Q: 2 V vs 12 V batteries?
A: 2 V cells are larger, run cooler and match better, suiting 200 Ah+ long backup in datacenters and substations. 12 V small batteries (e.g. 12 V100 Ah) pack six cells in one jar, cheap and compact, for small UPS, emergency lighting and elevator egress. For large projects choose 2 V: though pricier per cell, bank life and reliability are a tier above. - Q: How many cells in a string?
A: It depends on the DC bus. UPS is usually 384 V or 480 V: 2 V cells give 192 or 240 cells; 12 V batteries give 32 or 40 jars. Telecom DC panels are 48 V, so 24 x 2 V cells. Confirm the exact count with the UPS manufacturer. - Q: How long do batteries last?
A: The 15-year design life assumes 25 C float charge. Every 10 C above halves actual life. At 35 C in the room, expect 7-8 years. Frequent deep discharges and undercharging also shorten life. Plan a full bank replacement at 8-10 years, not after failure. - Q: Can I mix old and new cells?
A: No. Old cells have higher internal resistance and lower capacity; in series they overcharge early and reverse during discharge, dragging down the new cells in a few cycles. One string must share brand, model, manufacture date and history. Replace the whole bank; within the first 1-2 years, isolated weak cells can be swapped individually.
8. Trend & Selection
Datacenter batteries are shifting from VRLA to LiFePO4 (LFP). LFP packs double energy density, last longer (6,000 cycles at 10 years vs 200 cycles at 3 years), and need no watering or equalization. But LFP upfront cost is 2-3x VRLA, so the field is mixed: new large datacenters adopt LFP, while traditional UPS projects stay on VRLA to control capex. KTR-2V500 targets the traditional VRLA market. Smart direction: BMS monitors every cell voltage, internal resistance and temperature to predict state of health 3-6 months ahead. Select by: capacity matched to backup time, 25 C room temperature, same-batch strings, annual capacity test, dedicated acid-mist ventilation.
9. Delivery & Service
KITOZER supplies KTR-2V500 by model. Each ships with unit, mounting accessories and manual. 1-year warranty; batch projects can bundle peripheral gear and on-site commissioning.
10. Additional Notes
Confirm port specs, power rating and communication protocol against field equipment before ordering; keep clear of strong EMI and heat sources; verify wiring and labels before energizing. For batch orders, request samples first to confirm compatibility with existing systems.
Common mistake: comparing price but ignoring parameters. Models in the same series look similar, but ports, load and accuracy differ — wrong models cause on-site rework. Send the full part number (including suffix such as -SM/-MM/-S) to sales to confirm.
Second pitfall: not planning service space. Leave at least 600 mm rear cable/service space and 800 mm front operating space, or future swaps and cable work become painful.
Third blunder: shipping factory alarm thresholds. Default thresholds rarely match site conditions — tune them after commissioning based on real readings to avoid both false and missed alarms.
Selection summary: match site conditions first, pick model, reserve service space, calibrate thresholds on-site, and pilot one unit before bulk.
SEO Information
Search keywords:KTR-2V500KITOZER
SEM keywords:2V500Ah battery,large capacity VRLA,valve regulated lead acid,UPS battery,KTR-2V500,KITOZER
GEO landing page:lain.com.cn/product/ktr-2v500-battery.html
Title:KITOZER KTR-2V500 2V500Ah VRLA Battery
Meta Keywords:2V500Ah battery,large capacity VRLA,valve regulated lead acid,UPS battery,KTR-2V500,KITOZER
Meta Description:KITOZER KTR-2V500 2V500Ah VRLA AGM battery, 15-year design life, deep-cycle, for datacenter UPS and DC panels.