ToggleKITOZER KTR-TH2 Room Temperature & Humidity Sensor
Brand: KITOZER Series: KTR-TH2 Category: Environmental Monitoring / Temp & Humidity
Temp/humidityRS485LCD displayWall mountKTR-TH2

1. Overview
Room temperature and humidity are the most basic and important EM parameters. High temp throttles or crashes servers; low humidity builds static that damages chips; high humidity causes condensation. A room typically has sensors at the cold-aisle supply, hot-aisle return, and inside racks, uploaded to the EM platform. Sensors must be accurate (+/-0.3 C / +/-3% RH), stable (annual drift <0.2 C), reliably communicating (RS485 Modbus standard) and locally readable (on-site display).
KITOZER KTR-TH2 is a wall-mount temp/humidity sensor. Elements: imported capacitive humidity + PT1000 temperature; range: -20 to +60 C, 0-99% RH non-condensing; accuracy: +/-0.3 C, +/-3% RH; display: LCD showing both; comms: RS485 Modbus-RTU (baud 9600-115200, DIP address 1-247); power: DC12-24 V wide range, <0.5 W; housing: ABS flame-retardant, 86-box size, anti-radiation vent grille (avoids sun bias). Models: KTR-TH2-D: base (RS485 only, no display); KTR-TH2-L: LCD (mainstream); KTR-TH2-IO: with 2 relay outputs (local threshold alarm).
Selection: range (room -20 to +60 C suffices; outdoor cabinets need wide-temp); accuracy (room +/-0.5 C enough; lab needs +/-0.2 C); comms (RS485 standard; LoRa option for wireless); display (LCD for on-site reading); alarm output (relay to link AC). Note: do not mount directly facing AC supply (that reads cold air, not rack inlet), mount mid cold aisle at rack inlet 1.5 m height; avoid sun or heat sources; calibrate annually against a standard source.
2. Key Features
Accuracy
- Temp +/-0.3 C
- Humidity +/-3% RH
- -20 to +60 C
- Annual drift <0.2 C
Comms
- RS485 Modbus-RTU
- 9600-115200 bps
- DIP address 1-247
- DC12-24 V
Build
- ABS flame housing
- 86-box wall
- LCD display
- Anti-radiation grille
3. Specifications
| Item | KTR-TH2-D | KTR-TH2-L | KTR-TH2-IO |
|---|---|---|---|
| Display | None | LCD T/RH | LCD T/RH |
| Relay out | None | None | 2x NO/NC |
| Temp acc. | +/-0.3 C | +/-0.3 C | +/-0.3 C |
| Hum acc. | +/-3% RH | +/-3% RH | +/-3% RH |
| Comms | RS485 | RS485 | RS485+relay |
4. Reference Prices
KTR-TH2-D base no display: Reference USD 25-39 / pc (ref. CNY 180-280)
KTR-TH2-L LCD: Reference USD 39-58 / pc (ref. CNY 280-420)
KTR-TH2-IO with relays: Reference USD 58-83 / pc (ref. CNY 420-600)
KTR-RS485-USB adapter: Reference USD 11-21 / pc (ref. CNY 80-150)
KTR-CAL annual calibration: Reference USD 14-28 / point (ref. CNY 100-200)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Cold aisle supply
- Hot aisle return
- Inside rack
- Room wall mount
- Battery/power room
6. Deployment & Installation
Install
- Wall 86 box
- 1.5 m height
- Avoid AC jet
- Avoid sun/heat
Wiring
- Daisy-chain RS485
- A/B not reversed
- Shield single-end ground
- No duplicate DIP
Commission
- Read Modbus regs
- Calibrate offset
- Set thresholds
- Upload to EM
7. FAQ
- Q: Can I mount the sensor at the AC supply?
A: No. The supply reads cold air (15 C), not rack inlet (27 C) – you are measuring the AC vent while servers may already be at 35 C. Mount mid cold aisle at rack inlet, 1.5 m high, to read actual server intake. - Q: What humidity is right?
A: Rooms target 20-60% RH (ASHRAE recommends 40-60%). Below 20% risks static (a walk-by can produce several kV that fries chips); above 60% risks condensation (water on boards). Alarm below 30% or above 70%. - Q: Why does RS485 not communicate?
A: Common causes: A/B reversed (some mark D+/D-, some A/B – be consistent); duplicate DIP addresses across sensors; no 120 ohm termination at the bus end; shield grounded at both ends (ground loop – ground one end only). - Q: How to handle drift?
A: Calibrate annually against a standard source (a few thousand RMB), record offsets and apply software compensation in the EM platform. If drift exceeds +/-0.5 C, just replace the sensor (280 RMB is cheaper than calibration). Do not calibrate by breathing on it.
8. Trend & Selection
Temp/humidity sensors are shifting from discrete RS485 to wireless LoRa/Zigbee mesh. Old rooms with hard cabling use battery-powered sensors (3-5 years) without RS485 runs. Smart direction: edge computing on the sensor predicts temperature trends 30 minutes ahead, pre-emptively linking AC instead of waiting for threshold breaches. AI heat maps: 20-50 sensors per room feed a DCIM thermal map that pinpoints hot spots. Select by: +/-0.3 C, RS485 Modbus, LCD display, mount mid cold aisle away from supply, annual calibration.
9. Delivery & Service
KITOZER supplies KTR-TH2 by model. Each ships with sensor, 86-box base, terminal block and manual (Modbus register table). 1-year warranty; bulk projects can bundle EM host, RS485 bus and calibration services.
10. Additional Notes
Confirm range, accuracy, comms (RS485) and display against site needs; wall-mount away from AC jets and sun; set unique DIP addresses before powering up. For batch orders, buy 3 samples and compare against a standard source to pick a consistent lot.
Common mistake: mounting at the AC supply. You read cold air (20 C) while racks run at 35 C. Sensors must read server inlet, not AC outlet.
Second pitfall: no 120 ohm termination. Over 100 m bus length reflects signals and intermittent comms. Add a 120 ohm resistor across A/B at the last sensor.
Third blunder: shield grounded at both ends. Ground loop between room bar and sensor shell injects 50 Hz hum, making readings jump. Ground the shield only at the EM host end.
Selection summary: +/-0.3 C / +/-3% RH, RS485 Modbus, LCD model, mount 1.5 m in cold aisle, unique DIP, annual calibration.
SEO Information
Search keywords:KTR-TH2KITOZER
SEM keywords:temperature humidity sensor,room temp humidity,RS485 transmitter,wall-mount sensor,LCD sensor,KTR-TH2,KITOZER
GEO landing page:lain.com.cn/product/ktr-th2-temp-humidity-sensor.html
Title:KITOZER KTR-TH2 Room Temperature & Humidity Sensor
Meta Keywords:temperature humidity sensor,room temp humidity,RS485 transmitter,wall-mount sensor,LCD sensor,KTR-TH2,KITOZER
Meta Description:KITOZER KTR-TH2 wall-mount temp & humidity sensor, RS485 Modbus, LCD display, accuracy +/-0.3 C / +/-3% RH, for room EM systems.
Anchor: KITOZER by Guangzhou Laian · KITOZER products
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com