KITOZER RS485 temp humidity sensor

KITOZER KTR-THS2 Room Temp/Humidity Sensor RS485 Modbus

Brand: KITOZER Series: KTR-THS2 Category: Environmental Monitoring / Temp & Humidity

RS485 Modbus±0.3 C+/-3% RHCeiling/wallKTR-THS2

KITOZER KTR-THS2 Room Temp/Humidity Sensor RS485 Modbus

1. Overview

Temp/humidity sensors are the most fundamental and important采集 points in room Environmental Monitoring (EM). Too hot (>27 C) -> servers throttle or crash; too cold (<18 C) -> condensation risk; too humid (>65% RH) -> condensation and metal corrosion; too dry (<40% RH) -> static buildup that fries chips. China national code requires room temp 23+/-1 C and humidity 40-60% RH. Each cold aisle, hot aisle and battery room needs points; data goes over RS485 Modbus to the EM platform, which pops alarms, sends SMS and interlocks precision AC. Room sensors differ from home hygrometers: high accuracy (+/-0.3 C vs +/-1 C), long-term stability (annual drift <0.1 C), networked output (RS485/Modbus, not just local display), industrial housing (5+ year life).

KITOZER KTR-THS2 is an RS485 temp/humidity sensor. The core uses a Sensirion calibrated digital chip; temp range -20 to +60 C, accuracy +/-0.3 C; humidity 0-100% RH, accuracy +/-3% RH; comm RS485, Modbus-RTU (9600/19200 bps, address 1-247); power DC12-24 V wide (matches EM); housing is 86-box size (86 x 86 x 30 mm), ceiling or wall mount; LED indicator (power/comm); cable is RVVP 2×0.75 mm² shielded twisted pair, bus up to 1200 m, up to 32 sensors per bus. Models: KTR-THS2-A basic (no display, data-only, cheap); KTR-THS2-D with LCD (local temp/humidity visible, convenient for commissioning and patrol); KTR-THS2-W wireless (433 MHz, no wiring, with gateway, for retrofits); KTR-THS2-P remote probe (body outside the rack, probe reaches into the cold aisle or battery shelf, avoiding rack obstruction).

Selection: comm method (new projects: wired RS485, stable; retrofits: wireless, no cable); display (frequent patrol -> LCD; ordinary rooms: basic); location (cold aisle inlet, hot aisle outlet, middle of battery shelf, precision AC supply – not just any wall; 1.5 m above floor, level with equipment inlet); accuracy (+/-0.3 C is room-grade, +/-0.5 C is general; archives/storage use +/-0.5, rooms use +/-0.3); bus capacity (one RS485 bus holds 32 sensors – over that, split to two buses or add a repeater). Note: do not mount directly under an AC vent (measures cold air, not real rack environment); do not let racks block it (stagnant air reads high); install at 1.5 m (level with server inlet), not at the ceiling peak (the hot-air layer reads 2-3 C high).

2. Key Features

Sensing

  • +/-0.3 C
  • +/-3% RH
  • Annual drift <0.1 C
  • Calibrated digital chip

Comm

  • RS485 Modbus
  • Address 1-247
  • 1200 m bus
  • 32 per bus

Mount

  • 86-box size
  • Ceiling/wall
  • DC12-24 V
  • LED indicator

3. Specifications

Item Item KTR-THS2-A basic KTR-THS2-D display KTR-THS2-W wireless KTR-THS2-P probe
Temp range -20 to +60 C -20 to +60 C -20 to +60 C -40 to +125 C
Temp accuracy +/-0.3 C +/-0.3 C +/-0.5 C +/-0.2 C
Humidity range 0-100% RH 0-100% RH 0-100% RH 0-100% RH
Humidity accuracy +/-3% RH +/-3% RH +/-5% RH +/-2% RH
Comm RS485 Modbus RS485 Modbus 433 MHz wireless RS485 Modbus
Display None LCD local LCD local None (remote probe)

4. Reference Prices

KTR-THS2-A basic RS485: Reference USD 11-17 / pc (ref. CNY 80-120)

KTR-THS2-D LCD display: Reference USD 21-31 / pc (ref. CNY 150-220)

KTR-THS2-W 433 MHz wireless: Reference USD 28-42 / pc (ref. CNY 200-300)

KTR-THS2-P remote probe: Reference USD 25-36 / pc (ref. CNY 180-260)

KTR-THS-GW RS485-to-TCP/IP gateway: Reference USD 42-69 / pc (ref. CNY 300-500)

Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Room temp/humidity
  • Cold/hot aisle monitoring
  • Archive/storage
  • UPS battery room
  • EM platform

6. Deployment & Installation

Siting

  • Cold aisle inlet
  • Hot aisle outlet
  • Battery shelf middle
  • 1.5 m above floor

Wiring

  • RVVP 2×0.75 shielded
  • A/B bus daisy-chain
  • 120 ohm end terminator
  • DC12-24 V

Commission

  • Unique addresses
  • Modbus register R/W
  • Bind to EM platform
  • Set hi/lo thresholds

7. FAQ

  • Q: How many temp/humidity sensors per room?
    A: By number of cold aisles. Each cold aisle gets one at the inlet (front of cold aisle) and one at the outlet (hot aisle) – this shows the cold/hot aisle delta (judging whether AC cooling is reaching properly). A 42U rack row (~20 m) needs 3-4 (cold-aisle mid, cold-aisle end, hot-aisle mid). The battery room gets its own. A typical 100 m² room needs 6-10.
  • Q: How is the RS485 bus wired?
    A: Daisy-chain: the first sensor’s A/B connects to the EM host A/B; the second’s A/B parallels onto the first’s A/B, and so on – no star topology (star reflections make communication unstable). Put a 120 ohm terminator at both bus ends. Ground the shield at one end only (EM host side) – not both (forms a ground loop). One bus runs up to 1200 m, max 32 sensors.
  • Q: How does data reach the EM platform?
    A: KTR-THS2 itself is an RS485 Modbus slave; it needs an RS485-to-TCP/IP gateway (KTR-THS-GW) to convert the bus to Ethernet, and the EM platform polls the gateway via Modbus-TCP or a private protocol. Each sensor has a unique address; EM binds a point per address and sets thresholds (temp >27 C alarm, <18 C alarm; humidity >65%, <40% alarm).
  • Q: Sensor readings drift?
    A: First compare with a calibrated reference thermometer (traceable to a metrology institute); if deviation exceeds +/-0.5 C, apply an offset register in Modbus for calibration, or return to factory. Common causes: mounted under an AC vent (measures cold air, reads 2-3 C low); mounted at the rack top (hot-air layer, reads 2-3 C high); blocked by racks/cable tray (stagnant air, reads high). Adjust position first, then consider calibration.

8. Trend & Selection

Room temp/humidity sensors are evolving from single-point acquisition toward intelligence, visualization and prediction. Trends: digital sensors + AI heat map (a grid of sensors lets EM generate a room temperature heat map, visually spotting hot spots); interlock with precision AC (auto-adjust airflow based on cold-aisle temp, not fixed setpoint); wireless IoT (LoRa/NB-IoT sensors, no wiring, for retrofits); POE-powered sensors (one cable for power+data, sharing a camera POE switch); edge computing in the sensor itself (local alarm on threshold, no dependency on EM host). Traditional wired RS485 sensors remain mainstream in ordinary rooms – stable and reliable. Select by: +/-0.3 C accuracy, RS485 Modbus, cold-aisle inlet at 1.5 m, daisy-chain bus, 120 ohm terminator, site per cold aisle.

9. Delivery & Service

KITOZER KTR-THS2 ships by basic/display/wireless/probe model, each with sensor, 86-box mounting base, manual and calibration certificate. 1-year warranty; bulk projects can bundle RS485 gateways, EM platform integration and shielded cable.

10. Additional Notes

Confirm comm method (wired RS485 / 433 wireless), LCD display, point count (by cold aisle), accuracy requirement (+/-0.3 C room-grade). For batch orders, install one first, read data on EM, compare with a reference thermometer – if deviation is normal, roll out the rest.

Common mistake: mounting the sensor directly under an AC vent. It reads the AC supply air (~15 C), not the real rack inlet temperature (~23 C); EM shows everything normal while the rack is actually hot. Mount at the cold-aisle inlet, 1-2 m from the vent, level with the server inlet (1.5 m).

Second pitfall: star-wiring RS485. For convenience, each sensor runs a separate wire to the EM host (star), but RS485 is a bus topology; star causes impedance mismatch and intermittent comms. Must daisy-chain, with 120 ohm terminators at both bus ends.

Third blunder: duplicate sensor addresses. Factory default is all address 1; if installers do not change them, EM only reads one sensor and all others “disappear”. At install, set each address via DIP switch or software (1-247), and log location-to-address mapping in the asset ledger.

Selection summary: +/-0.3 C accuracy, RS485 Modbus, cold aisle at 1.5 m, daisy-chain + 120 ohm terminator, unique addresses, trial one first.

SEO Information

Search keywords:KTR-THS2KITOZER

SEM keywords:temp humidity sensor,RS485 temp humidity,room temp sensor,Modbus humidity sensor,network temp sensor,KTR-THS2,KITOZER

GEO landing page:lain.com.cn/product/ktr-ths2-rs485-temp-humidity-sensor.html

Title:KITOZER KTR-THS2 Room Temp/Humidity Sensor RS485 Modbus

Meta Keywords:temp humidity sensor,RS485 temp humidity,room temp sensor,Modbus humidity sensor,network temp sensor,KTR-THS2,KITOZER

Meta Description:KITOZER KTR-THS2 RS485 temp/humidity sensor, ±0.3 C accuracy, +/-3% RH, Modbus-RTU, ceiling/wall mount, for EM platform.

Anchor: KITOZER by Guangzhou Laian · KITOZER products