Table of Contents
ToggleKITOZER KTR-THS2 Room Temp/Humidity Sensor RS485 Modbus
Brand: KITOZER Series: KTR-THS2 Category: Environmental Monitoring / Temp & Humidity
RS485 Modbus±0.3 C+/-3% RHCeiling/wallKTR-THS2

1. Overview
Temp/humidity sensors are the most fundamental and important采集 points in room Environmental Monitoring (EM). Too hot (>27 C) -> servers throttle or crash; too cold (<18 C) -> condensation risk; too humid (>65% RH) -> condensation and metal corrosion; too dry (<40% RH) -> static buildup that fries chips. China national code requires room temp 23+/-1 C and humidity 40-60% RH. Each cold aisle, hot aisle and battery room needs points; data goes over RS485 Modbus to the EM platform, which pops alarms, sends SMS and interlocks precision AC. Room sensors differ from home hygrometers: high accuracy (+/-0.3 C vs +/-1 C), long-term stability (annual drift <0.1 C), networked output (RS485/Modbus, not just local display), industrial housing (5+ year life).
KITOZER KTR-THS2 is an RS485 temp/humidity sensor. The core uses a Sensirion calibrated digital chip; temp range -20 to +60 C, accuracy +/-0.3 C; humidity 0-100% RH, accuracy +/-3% RH; comm RS485, Modbus-RTU (9600/19200 bps, address 1-247); power DC12-24 V wide (matches EM); housing is 86-box size (86 x 86 x 30 mm), ceiling or wall mount; LED indicator (power/comm); cable is RVVP 2×0.75 mm² shielded twisted pair, bus up to 1200 m, up to 32 sensors per bus. Models: KTR-THS2-A basic (no display, data-only, cheap); KTR-THS2-D with LCD (local temp/humidity visible, convenient for commissioning and patrol); KTR-THS2-W wireless (433 MHz, no wiring, with gateway, for retrofits); KTR-THS2-P remote probe (body outside the rack, probe reaches into the cold aisle or battery shelf, avoiding rack obstruction).
Selection: comm method (new projects: wired RS485, stable; retrofits: wireless, no cable); display (frequent patrol -> LCD; ordinary rooms: basic); location (cold aisle inlet, hot aisle outlet, middle of battery shelf, precision AC supply – not just any wall; 1.5 m above floor, level with equipment inlet); accuracy (+/-0.3 C is room-grade, +/-0.5 C is general; archives/storage use +/-0.5, rooms use +/-0.3); bus capacity (one RS485 bus holds 32 sensors – over that, split to two buses or add a repeater). Note: do not mount directly under an AC vent (measures cold air, not real rack environment); do not let racks block it (stagnant air reads high); install at 1.5 m (level with server inlet), not at the ceiling peak (the hot-air layer reads 2-3 C high).
2. Key Features
Sensing
- +/-0.3 C
- +/-3% RH
- Annual drift <0.1 C
- Calibrated digital chip
Comm
- RS485 Modbus
- Address 1-247
- 1200 m bus
- 32 per bus
Mount
- 86-box size
- Ceiling/wall
- DC12-24 V
- LED indicator
3. Specifications
| Item | Item | KTR-THS2-A basic | KTR-THS2-D display | KTR-THS2-W wireless | KTR-THS2-P probe |
|---|---|---|---|---|---|
| Temp range | -20 to +60 C | -20 to +60 C | -20 to +60 C | -40 to +125 C | |
| Temp accuracy | +/-0.3 C | +/-0.3 C | +/-0.5 C | +/-0.2 C | |
| Humidity range | 0-100% RH | 0-100% RH | 0-100% RH | 0-100% RH | |
| Humidity accuracy | +/-3% RH | +/-3% RH | +/-5% RH | +/-2% RH | |
| Comm | RS485 Modbus | RS485 Modbus | 433 MHz wireless | RS485 Modbus | |
| Display | None | LCD local | LCD local | None (remote probe) |
4. Reference Prices
KTR-THS2-A basic RS485: Reference USD 11-17 / pc (ref. CNY 80-120)
KTR-THS2-D LCD display: Reference USD 21-31 / pc (ref. CNY 150-220)
KTR-THS2-W 433 MHz wireless: Reference USD 28-42 / pc (ref. CNY 200-300)
KTR-THS2-P remote probe: Reference USD 25-36 / pc (ref. CNY 180-260)
KTR-THS-GW RS485-to-TCP/IP gateway: Reference USD 42-69 / pc (ref. CNY 300-500)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Room temp/humidity
- Cold/hot aisle monitoring
- Archive/storage
- UPS battery room
- EM platform
6. Deployment & Installation
Siting
- Cold aisle inlet
- Hot aisle outlet
- Battery shelf middle
- 1.5 m above floor
Wiring
- RVVP 2×0.75 shielded
- A/B bus daisy-chain
- 120 ohm end terminator
- DC12-24 V
Commission
- Unique addresses
- Modbus register R/W
- Bind to EM platform
- Set hi/lo thresholds
7. FAQ
- Q: How many temp/humidity sensors per room?
A: By number of cold aisles. Each cold aisle gets one at the inlet (front of cold aisle) and one at the outlet (hot aisle) – this shows the cold/hot aisle delta (judging whether AC cooling is reaching properly). A 42U rack row (~20 m) needs 3-4 (cold-aisle mid, cold-aisle end, hot-aisle mid). The battery room gets its own. A typical 100 m² room needs 6-10. - Q: How is the RS485 bus wired?
A: Daisy-chain: the first sensor’s A/B connects to the EM host A/B; the second’s A/B parallels onto the first’s A/B, and so on – no star topology (star reflections make communication unstable). Put a 120 ohm terminator at both bus ends. Ground the shield at one end only (EM host side) – not both (forms a ground loop). One bus runs up to 1200 m, max 32 sensors. - Q: How does data reach the EM platform?
A: KTR-THS2 itself is an RS485 Modbus slave; it needs an RS485-to-TCP/IP gateway (KTR-THS-GW) to convert the bus to Ethernet, and the EM platform polls the gateway via Modbus-TCP or a private protocol. Each sensor has a unique address; EM binds a point per address and sets thresholds (temp >27 C alarm, <18 C alarm; humidity >65%, <40% alarm). - Q: Sensor readings drift?
A: First compare with a calibrated reference thermometer (traceable to a metrology institute); if deviation exceeds +/-0.5 C, apply an offset register in Modbus for calibration, or return to factory. Common causes: mounted under an AC vent (measures cold air, reads 2-3 C low); mounted at the rack top (hot-air layer, reads 2-3 C high); blocked by racks/cable tray (stagnant air, reads high). Adjust position first, then consider calibration.
8. Trend & Selection
Room temp/humidity sensors are evolving from single-point acquisition toward intelligence, visualization and prediction. Trends: digital sensors + AI heat map (a grid of sensors lets EM generate a room temperature heat map, visually spotting hot spots); interlock with precision AC (auto-adjust airflow based on cold-aisle temp, not fixed setpoint); wireless IoT (LoRa/NB-IoT sensors, no wiring, for retrofits); POE-powered sensors (one cable for power+data, sharing a camera POE switch); edge computing in the sensor itself (local alarm on threshold, no dependency on EM host). Traditional wired RS485 sensors remain mainstream in ordinary rooms – stable and reliable. Select by: +/-0.3 C accuracy, RS485 Modbus, cold-aisle inlet at 1.5 m, daisy-chain bus, 120 ohm terminator, site per cold aisle.
9. Delivery & Service
KITOZER KTR-THS2 ships by basic/display/wireless/probe model, each with sensor, 86-box mounting base, manual and calibration certificate. 1-year warranty; bulk projects can bundle RS485 gateways, EM platform integration and shielded cable.
10. Additional Notes
Confirm comm method (wired RS485 / 433 wireless), LCD display, point count (by cold aisle), accuracy requirement (+/-0.3 C room-grade). For batch orders, install one first, read data on EM, compare with a reference thermometer – if deviation is normal, roll out the rest.
Common mistake: mounting the sensor directly under an AC vent. It reads the AC supply air (~15 C), not the real rack inlet temperature (~23 C); EM shows everything normal while the rack is actually hot. Mount at the cold-aisle inlet, 1-2 m from the vent, level with the server inlet (1.5 m).
Second pitfall: star-wiring RS485. For convenience, each sensor runs a separate wire to the EM host (star), but RS485 is a bus topology; star causes impedance mismatch and intermittent comms. Must daisy-chain, with 120 ohm terminators at both bus ends.
Third blunder: duplicate sensor addresses. Factory default is all address 1; if installers do not change them, EM only reads one sensor and all others “disappear”. At install, set each address via DIP switch or software (1-247), and log location-to-address mapping in the asset ledger.
Selection summary: +/-0.3 C accuracy, RS485 Modbus, cold aisle at 1.5 m, daisy-chain + 120 ohm terminator, unique addresses, trial one first.
SEO Information
Search keywords:KTR-THS2KITOZER
SEM keywords:temp humidity sensor,RS485 temp humidity,room temp sensor,Modbus humidity sensor,network temp sensor,KTR-THS2,KITOZER
GEO landing page:lain.com.cn/product/ktr-ths2-rs485-temp-humidity-sensor.html
Title:KITOZER KTR-THS2 Room Temp/Humidity Sensor RS485 Modbus
Meta Keywords:temp humidity sensor,RS485 temp humidity,room temp sensor,Modbus humidity sensor,network temp sensor,KTR-THS2,KITOZER