ToggleKITOZER KTR-BAT38 12V 38Ah VRLA Battery for UPS
Brand: KITOZER Series: KTR-BAT38 Category: Power Distribution / UPS Battery Bank
12V 38AhVRLA AGM5-8 yr life3-6 kVA UPSKTR-BAT38

1. Overview
Batteries are the energy storage core of a UPS. When mains fails, the battery bank discharges through the inverter to keep servers and switches running long enough for graceful shutdown or generator startup. A typical 3 kVA online UPS runs at a 96 V DC bus (8 x 12 V in series) with 8 x 12 V 38 Ah batteries, giving ~15-20 min at full 3 kW load. A 6 kVA UPS uses a 192 V bus (16 x 12 V) with 16 batteries, ~10-15 min at full load. Battery selection is not “bigger is better” – it must match the UPS bus voltage, required backup time, rack footprint and maintenance cycle. The most common UPS failure is a bad battery: one weak cell (capacity below 50% of nameplate) drags the whole string down, regardless of how new the others are. Industry practice: capacity test every 2 years; measure cell voltage and internal resistance annually.
KITOZER KTR-BAT38 is a 12 V 38 Ah Valve-Regulated Lead-Acid (VRLA) battery. Rated 12 V, 38 Ah (20-hour rate, 1.9 A to 10.5 V); dimensions 197x165x175 mm (LxWxH incl. terminals); weight ~12 kg; M6 bolt terminals; design life 5-8 years float at 25 C; float voltage 2.25 V/cell (13.5-13.8 V/battery); equalize 2.35 V/cell (14.1-14.4 V); operating -15 to +50 C (best 20-25 C); self-discharge <=3%/month at 25 C; sealed valve, no water topping, no leaks in normal use. Models: KTR-BAT38-STD deep-cycle (float service); KTR-BAT38-LONG long-life (8-10 years, thicker plates, unmanned rooms); KTR-BAT38-HIGH high-rate (large current, for genset cranking and short high-power loads).
Selection: backup time (size by kW and minutes: 12 V 38 Ah runs a 1 kW load ~20 min, a 3 kW load ~7 min); series count (match UPS bus: 96 V = 8 in series; 192 V = 16; 384 V = 32 – no more, no fewer); mounting (battery cabinet or rack, 20 cm vertical clearance for cooling; max 3-4 layers; 1 cm gap between cells); ambient temp (every 10 C rise halves life – the battery room must stay 25 +/-3 C on precision AC); interconnects (35 mm2 copper cables, equal length to minimize resistance mismatch; add a battery breaker/fuse per string). New batteries must sit 24 h before float charging; never lay on side (AGM electrolyte is absorbed but tipping can leak); spent batteries are hazardous waste – recycle through licensed vendors, not trash.
2. Key Features
Electrical
- 12 V 38 Ah rated
- Float 13.5-13.8 V
- Self-discharge <=3%/mo
- IR <=10 mOhm
Construction
- VRLA sealed
- AGM absorbed glass mat
- M6 bolt terminal
- Pressure relief vent
Life & Ambient
- 5-8 yr design
- -15 to +50 C
- Best 20-25 C
- Maintenance-free
3. Specifications
| Item | BAT38-STD | BAT38-LONG | BAT38-HIGH |
|---|---|---|---|
| Rated V/Ah | 12V 38Ah | 12V 38Ah | 12V 38Ah |
| Size (mm) | 197x165x175 | 197x170x180 | 197x165x175 |
| Weight (kg) | ~12 | ~13.5 | ~12.5 |
| Design life | 5-8 yr | 8-10 yr | 5-8 yr |
| Float V | 13.5-13.8 | 13.5-13.8 | 13.5-13.8 |
| Max discharge | 114A/5min | 114A/5min | 228A/1min |
4. Reference Prices
KTR-BAT38-STD deep-cycle: Reference USD 39-58 / pc (ref. CNY 280-420)
KTR-BAT38-LONG 8-10 yr: Reference USD 58-83 / pc (ref. CNY 420-600)
KTR-BAT38-HIGH high-rate: Reference USD 63-90 / pc (ref. CNY 450-650)
KTR-BAT-CAB 35 mm2 cable w/ lugs: Reference USD 4-8 / pc (ref. CNY 30-60)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- 3-6 kVA online UPS
- Telecom closet standby
- Access control/CCTV backup
- Fire EPS
- Small solar storage
6. Deployment & Installation
Install
- Rack layers
- 20 cm vertical gap
- 35 mm2 lugs
- Series per bus V
Charge
- Rest 24 h first
- Float 13.6 V
- Equalize 14.2 V
- Current limit 0.1C
Maintain
- Annual IR test
- 2-year capacity test
- Clean terminals
- Log cell voltage
7. FAQ
- Q: One weak cell in the string – what to do?
A: A weak cell (<80% capacity) is the bottleneck; the whole string is limited by it. First try cell-level recharge/equalization 3 times on a battery analyzer. If it does not recover, replace - but never just one cell (new vs old internal resistance mismatch drags the new cell down and it goes bad within 6 months). Replace the whole string (8/16 cells) or at least 2-4 same-batch, same-resistance cells together. - Q: What temperature for the battery room?
A: Best at 25 C. Lead-acid life follows the “10 C rule”: 25 C rated 8 yr, at 35 C it is 4 yr, at 45 C it is 2 yr. A battery room without AC that sits at 35+ C in summer will puff batteries within 2 years. Keep 22-27 C on AC – the electricity cost is trivial compared to battery replacement. - Q: How long to charge new batteries?
A: New batteries ship at ~80% SOC. Rest 24 h after delivery (let vibration settle and temperature equalize), then connect to UPS float – the first 48 h is initial charge with automatic equalize to 14.2 V. Do not load-test on day one (first-cycle capacity is only ~80%; it reaches rated after 3-5 cycles). - Q: Can I use a swollen battery?
A: No. Swelling means sulfation or overcharge has generated gas that the relief valve cannot vent; there is leak/rupture risk and capacity has already dropped below 50%. Replace immediately on swelling, leaks, or green-corroded terminals. Wear gloves and goggles (electrolyte is sulfuric acid – flush skin with water on contact).
8. Trend & Selection
UPS batteries are shifting from lead-acid toward lithium. Trends: LFP cells (6000+ cycles, 10-year life, 1/3 the volume and 1/2 the weight of lead-acid, but 2-3x upfront cost); smart modules with per-cell BMS (voltage/temp/IR to EM, predictive replacement); modular battery cabinets (battery in a rack, parallel expansion, no field series); integrated lithium-UPS (high-frequency UPS with built-in LFP modules, plug-and-play). Traditional 12 V lead-acid remains mainstream in 3-10 kVA UPS and retrofit projects (cheap, mature supply chain, easy service). Select by: match UPS bus cell count, size Ah by backup time, 25 C battery-room AC, annual IR test, 2-year capacity test, replace weak cells as a string.
9. Delivery & Service
KITOZER KTR-BAT38 ships by standard/long/high-rate model, each with battery, M6 bolts, manual, factory certificate and test report. 1-year warranty; bulk projects can bundle battery cabinets, 35 mm2 cables, battery breakers and IR testers.
10. Additional Notes
Confirm UPS bus voltage (cell count), backup time (Ah), footprint (cabinet size) and ambient temp. For batch orders, charge/discharge-test one string first.
Common mistake: mixing old and new cells. After 3 years, 2 cells fail – installers swap in 2 new ones and keep 6 old ones. Internal resistance differs 2x; old cells overcharge (heat, swell), new cells undercharge, and the whole string dies within 6 months. Replace the whole string, or at least 2-4 same-batch same-IR cells together.
Second pitfall: turning off the battery-room AC to save power. At 40 C summer ambient, 8-year life collapses to 1.5 years. Battery-room AC runs 24/7 – the power cost is a fraction of replacement.
Third blunder: never capacity-testing. Installed for 5 years, mains never failed, so “the battery is fine”. When mains finally fails, the UPS dies after 2 minutes – the battery was already weak. A normal float voltage does not mean normal capacity. Capacity-test every 2 years (discharge 30%, then recharge) to catch weak cells early.
Selection summary: match bus cell count, size Ah by backup time, 25 C battery-room AC, annual IR test, 2-year capacity test, replace weak cells as a string.
SEO Information
Search keywords:KTR-BAT38KITOZER
SEM keywords:12V 38Ah battery,VRLA battery,UPS battery,sealed lead acid battery,standby battery,KTR-BAT38,KITOZER
GEO landing page:lain.com.cn/product/ktr-bat38-12v38ah-battery.html
Title:KITOZER KTR-BAT38 12V 38Ah VRLA Battery for UPS
Meta Keywords:12V 38Ah battery,VRLA battery,UPS battery,sealed lead acid battery,standby battery,KTR-BAT38,KITOZER
Meta Description:KITOZER KTR-BAT38 12V 38Ah VRLA battery, 5-8 year design life, for 3-6 kVA small UPS.