Table of Contents
ToggleKITOZER KTR-TEV2 Thermal Expansion Valve & Capillary Tube
Brand: KITOZER Series: KTR-TEV2 Category: Data Center Engineering / Precision AC Parts
Thermal expansion valveCapillary throttleExternal equalizerSuperheat controlKTR-TEV2

1. Overview
Thermal expansion valves (TEV) and capillary tubes are the throttling devices in a refrigeration cycle, installed between the condenser liquid line and the evaporator inlet. High-pressure liquid refrigerant passes through them, pressure and boiling point drop sharply, part of the liquid flashes into a low-pressure low-temperature gas-liquid mix, and it enters the evaporator to absorb heat. The TEV does more than throttle: it modulates opening based on evaporator superheat. A bulb strapped to the suction line senses return-gas temperature; high superheat means under-feed, so the valve opens; near-saturated means over-feed, so it closes, preventing liquid flood-back into the compressor. A capillary tube is a long thin copper tube (ID 0.6-2 mm, length 1-3 m) with a fixed bore and no moving parts – simple and cheap, but it cannot adjust to load swings and only suits small, stable-duty units.
KITOZER KTR-TEV2 is a thermal expansion valve series for precision AC, covering 3/5/8 nominal tons (10.5/17.6/28 kW) for small-to-mid precision units. The forged-brass body has brazed ports and an external equalizer line (a small tube from the evaporator outlet to the diaphragm chamber, compensating evaporator pressure drop for more accurate modulation). The bulb is charged with R134a, strapped to a horizontal suction run and insulated to shield it from ambient temperature. It works with R22/R410A at -10 to +10 C evaporating. KTR-CAP2 is capillary tubing, cut by ID (0.6/0.8/1.0/1.2 mm) and length, used with a drier inlet strainer. Match capacity to the unit: too small under-feeds and chills inadequately; too large hunts and cycles, causing superheat swings and flood risk. Typically take 1.0-1.2x the unit nominal capacity.
Selection: capacity match (pick the TEV rating close to the unit, do not oversize); internal vs external equalizer (external for high evaporator drop or multi-circuit coils; internal for small single-circuit units); refrigerant type (R410A runs high pressure – use the high-pressure body class); bulb position (strap to the top of a horizontal suction run, not a U-bend sump, insulate it); reserve capillary for small stable-duty units (rack rear-door coolers, small constant-humidity machines) – large precision ACs must use a TEV. Note: after replacing a TEV, evacuate and commission by superheat (typically 5-8 C); a blocked capillary must be replaced wholesale, not cleaned and reused.
2. Key Features
Throttling
- External equalizer
- Auto superheat trim
- R134a charged bulb
- Flood-back protection
Body
- Forged brass
- Brazed ports
- R22/R410A compatible
- Multiple capacities
Capillary
- Fixed bore
- No moving parts
- Cut to length
- Low cost
3. Specifications
| Item | Item | KTR-TEV2-3 | KTR-TEV2-5 | KTR-TEV2-8 | KTR-CAP2 |
|---|---|---|---|---|---|
| Type | Thermal expansion valve | Thermal expansion valve | Thermal expansion valve | Capillary (fixed bore) | |
| Nominal capacity | 3 RT (10.5 kW) | 5 RT (17.6 kW) | 8 RT (28 kW) | By tube ID/length | |
| Equalizer | External | External | External | None (fixed) | |
| Refrigerant | R22/R410A | R22/R410A | R22/R410A | R22/R410A | |
| Evap. temp range | -10 to +10 C | -10 to +10 C | -10 to +10 C | Fixed duty | |
| Bulb charge | R134a charge | R134a charge | R134a charge | None |
4. Reference Prices
KTR-TEV2-3 (3 RT ext. equalizer): Reference USD 17-25 / pc (ref. CNY 120-180)
KTR-TEV2-5 (5 RT ext. equalizer): Reference USD 22-33 / pc (ref. CNY 160-240)
KTR-TEV2-8 (8 RT ext. equalizer): Reference USD 31-44 / pc (ref. CNY 220-320)
KTR-CAP2 capillary (cut to size): Reference USD 2-4 / pc (ref. CNY 15-30)
KTR-TEV2-BULB bulb clamp kit: Reference USD 1.5-3 / set (ref. CNY 10-20)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Precision AC evaporator inlet
- Chiller throttle
- Constant-temp/humidity AC
- Rack rear-door heat exchanger
- Small condenser units
6. Deployment & Installation
Location
- After drier filter
- Before evaporator
- Bulb on suction line
- Valve upright
Brazing
- Nitrogen purge
- Cool the body
- Remove element first
- Pressure test after
Commission
- Vacuum 4 hours
- Superheat 5-8 C
- Adjust superheat screw
- Log charge weight
7. FAQ
- Q: Heavy frosting on the TEV – is it broken?
A: Not necessarily. A light frost from the valve body to the evaporator is normal. But thick frost or ice covering the inlet side (between the inlet and the bulb) indicates a blockage ahead – a clogged drier filter or strainer. Check whether the drier is hot or cold to locate the blockage, then decide whether to replace the valve or the filter. - Q: How do I measure superheat?
A: Read suction pressure on the gauge, look up the corresponding saturated temperature for the refrigerant, then measure suction-line temperature at the bulb with a thermometer. Suction temp minus saturated temp = superheat. 5-8 C is typical. High superheat means under-feed (valve too small or blocked); low superheat means over-feed (valve too large or bulb strapped wrong) – flood-back risk. - Q: Can capillary and TEV be swapped?
A: Not directly. A capillary is a fixed throttle matched to one capacity and duty; a TEV is modifiable. Small units (under 3 kW) designed for a capillary need re-piping and superheat commissioning to switch to a TEV. Large TEV-designed units cannot take a capillary – at varying loads the fixed bore cannot adjust, causing flood-back or insufficient cooling. - Q: Why insulate the bulb?
A: The bulb must sense the true refrigerant temperature at the evaporator outlet. Without insulation, ambient air (~25 C in the room) fools the bulb into reading high superheat, keeps the valve wide open, and liquid refrigerant rushes into the compressor. Wrap the bulb and its suction-line section in closed-cell foam to shield it from ambient heat.
8. Trend & Selection
Throttling devices are evolving from mechanical TEVs toward electronic expansion valves (EEVs). Trends: EEVs replacing TEVs (stepper-motor driven, modulated by a controller on superheat and load, raising efficiency 10-20%); EEV linked with inverter compressors (valve opening tracks compressor frequency for better part-load efficiency); high-pressure bodies for eco-refrigerants (R32/R454B); capillary matched to micro-channel heat exchangers (compact rack rear-door coolers). Traditional TEVs remain mainstream in fixed-speed, small-to-mid precision units and will not be fully replaced within 5 years. Select by: capacity 1.0-1.2x, external equalizer, bulb on horizontal suction line insulated, 5-8 C superheat, capillary only for small stable duty.
9. Delivery & Service
KITOZER KTR-TEV2 ships by capacity (3/5/8 RT), each with valve body, bulb, equalizer fitting, insulation and manual. 1-year warranty; bulk projects can bundle drier filters, sight glasses and refrigerant.
10. Additional Notes
Confirm unit nominal capacity, refrigerant (R22/R410A), internal vs external equalizer, and evaporator circuit count. For batch orders, fit one first, evacuate and charge, measure 5-8 C superheat, and verify the valve modulates smoothly before rolling out.
Common mistake: oversizing the TEV. A larger valve seems safer, but it hunts badly at small openings, cycles the compressor and risks flood-back. Better slightly undersized than oversized – pick 1.0x the unit capacity.
Second pitfall: strapping the bulb at the bottom of the suction line. Oil film and liquid pooled at the bottom give false temperature readings. Strap the bulb to the top (12 o’clock) of a horizontal run with a copper clamp, then insulate.
Third blunder: replacing the valve without evacuating. Recharging immediately leaves air and moisture in the system, causing quick ice-up and oxidation. After valve replacement, evacuate to -0.1 MPa and hold for 2+ hours.
Selection summary: 1.0x capacity, external equalizer, bulb on top + insulated, 5-8 C superheat, always evacuate after replacement.
SEO Information
Search keywords:KTR-TEV2KITOZER
SEM keywords:thermal expansion valve,capillary tube,precision AC expansion valve,TEV valve,expansion valve selection,KTR-TEV2,KITOZER
GEO landing page:lain.com.cn/product/ktr-tev2-thermal-expansion-valve-capillary.html
Title:KITOZER KTR-TEV2 Thermal Expansion Valve & Capillary Tube
Meta Keywords:thermal expansion valve,capillary tube,precision AC expansion valve,TEV valve,expansion valve selection,KTR-TEV2,KITOZER
Meta Description:KITOZER KTR-TEV2 thermal expansion valve and capillary tube, external equalizer, R22/R410A compatible, for precision AC refrigerant throttling and superheat control.
Anchor: KITOZER by Guangzhou Laian · KITOZER products
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com