KITOZER 2V 1000Ah battery

KITOZER KTR-2V1000 2V1000Ah VRLA Battery UPS DC Bus

Brand: KITOZER Series: KTR-2V1000 Category: Power Distribution / UPS Battery

2V1000AhVRLA sealedAGM10-15 yr floatKTR-2V1000

KITOZER KTR-2V1000 2V1000Ah VRLA Battery UPS DC Bus

1. Overview

2V1000Ah is a large VRLA (valve-regulated lead-acid) cell, 2 V nominal and 1000 Ah capacity. Unlike the 12V100Ah blocks common in rooms, 2V large cells are strung into batteries (24 cells for -48 V telecom, 192 cells for a 384 V UPS DC bus). When mains fails, it instantly carries the load (UPS inverter or DC/DC converter) until the diesel genset starts (seconds to tens of seconds) – the last capacitor in the data center standby chain. The 1000Ah large cell serves high-power UPS (200 kVA+) and long runtime (30 min+ at full load). VRLA cells are valve-regulated and sealed (electrolyte absorbed in AGM mats, no spill, no acid mist, no dedicated battery-room ventilation needed), maintenance-free (no watering), and float-charged (always on charger, fully charged on standby).

KITOZER KTR-2V1000 is a 2V large VRLA series. Models: KTR-2V1000 (1000 Ah, AGM absorbed electrolyte, 12-year float design at 25 C); KTR-2V800 (800 Ah, one size down); KTR-2V1500 (1500 Ah, larger); KTR-OPzV1000 (gel, electrolyte is silica gel, better deep-discharge recovery and wider temperature tolerance, 15-year design, for rooms with temperature swings or deep cycles). Key specs: 2 V nominal, 10-hour rate 1000 Ah; float 2.25-2.27 V/cell at 25 C; equalize 2.30-2.35 V/cell; operating -15 to +50 C (optimal 20-25 C); rectangular jar (~200x200x700 mm), ~300 kg/cell (use a pallet jack); copper-core lead-plated terminals with inter-cell links. Runtime math: runtime = total energy (cells x 2 V x 1000 Ah) / load power, derated 0.8 efficiency, cutoff at 1.8 V/cell.

Selection: capacity (by UPS power and required runtime – one 1000Ah cell stores 2 kWh; a 200 kVA UPS at ~160 kW needs 80 kWh for 30 min, i.e. 40 cells in series); AGM vs gel (constant-temperature rooms use cheaper AGM; battery rooms with temperature swings or frequent deep cycles use gel); cell count (set by UPS DC bus – 384 V bus = 192 x 2 V cells); racks (2V cells are heavy, use steel racks rated >=500 kg/shelf, layered, not stacked high); temperature (every 10 C above 25 C halves life – hold 20-25 C with AC). Note: new strings need initial charging (equalize 24-48 h); annual capacity test (discharge 30-40% to gauge health); end-of-life cells are hazardous waste, not trash.

2. Key Features

Performance

  • 2V 1000 Ah
  • AGM sealed
  • 12-year float
  • High discharge current

Build

  • Copper lead-plated post
  • Safety vent
  • Steel jar
  • Inter-cell links

Options

  • 800/1000/1500 Ah
  • AGM/Gel
  • -48 V/384 V strings
  • Rack matched

3. Specifications

Item Item KTR-2V1000 KTR-2V800 KTR-2V1500 KTR-OPzV1000
Nominal V 2 V 2 V 2 V 2 V
Capacity 1000 Ah 800 Ah 1500 Ah 1000 Ah
Type AGM VRLA AGM VRLA AGM VRLA Gel
Float life 12 yr (25 C) 12 yr (25 C) 12 yr (25 C) 15 yr (25 C)
Float voltage 2.25-2.27 V/cell 2.25-2.27 V/cell 2.25-2.27 V/cell 2.23-2.27 V/cell
EQ voltage 2.30-2.35 V/cell 2.30-2.35 V/cell 2.30-2.35 V/cell 2.30-2.35 V/cell

4. Reference Prices

KTR-2V1000 2V1000Ah AGM: Reference USD 250-361 / pc (ref. CNY 1800-2600)

KTR-2V800 2V800Ah AGM: Reference USD 208-306 / pc (ref. CNY 1500-2200)

KTR-2V1500 2V1500Ah AGM: Reference USD 361-528 / pc (ref. CNY 2600-3800)

KTR-OPzV1000 2V1000Ah Gel: Reference USD 389-556 / pc (ref. CNY 2800-4000)

KTR-BAT-CABLE inter-cell link (incl.): Reference USD 4-8 / pc (ref. CNY 30-60)

Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • UPS backup bank
  • Telecom DC (-48 V)
  • Substation control power
  • PV storage backup
  • Data center standby

6. Deployment & Installation

Install

  • Weight-rated layered racks
  • Torque inter-cell links
  • Use torque wrench
  • Polarity correct

Charge

  • Initial EQ 24-48 h
  • Float 2.25-2.27 V
  • Ambient 20-25 C
  • Battery-room AC

Maintain

  • Annual discharge test
  • Measure cell V/internal R
  • Petroleum jelly on terminals
  • Battery log

7. FAQ

  • Q: How do I calculate backup time?
    A: Example: 100 kVA UPS at 0.9 PF = 90 kW load. Use 100 x 2V1000Ah cells in series (200 V total, 200 V x 1000 Ah = 200 kWh). At 0.8 efficiency and 0.9 usable (down to 1.8 V cutoff, 90% available): usable energy = 200 x 0.8 x 0.9 = 144 kWh. Runtime = 144 kWh / 90 kW = 1.6 hours. Note: high-rate discharge derates capacity (1-hour rate delivers only ~55% of nameplate), so real runtime is shorter – add margin.
  • Q: AGM or gel?
    A: Constant-temperature rooms (20-25 C) with occasional discharge (a few outages a year): AGM, 20-30% cheaper. Rooms running warm (30 C+) or with frequent discharge (off-grid PV, frequent outages): gel, better deep-cycle recovery and longer life. The gel KTR-OPzV costs ~50% more but lasts 15 years vs 12.
  • Q: Why temperature-control the battery room?
    A: Lead-acid life is highly temperature-sensitive: designed for 12 years at 25 C, every 10 C halves it. At 35 C it lasts 6 years; at 45 C, 3. Cells do not dissipate much heat, but charging warms them and rooms easily climb above 35 C in summer. Run dedicated AC holding 20-25 C, separate from room AC.
  • Q: When to replace the battery?
    A: Designed for 12 years float at 25 C, but real-world replacement is at 8-10 years. Trigger: during the annual discharge test, if string capacity drops below 80% of nameplate, or any cell’s internal resistance rises 50% over new, replace the whole string. Do not swap only a few bad cells – mixing old and new drags the new cells down. Replace all at once.

8. Trend & Selection

Data center standby power is shifting from lead-acid to LFP lithium. Trends: lithium replacing lead-acid (LFP energy density is 3x, footprint cuts 2/3, cycle life 6000+, ~2-3x up-front cost but lower lifecycle cost; new large data centers standardize on lithium UPS); 2V lead-acid evolving toward longer life and safety (gel, lead-carbon, doubled deep-cycle life); smart BMS (per-cell voltage/internal-resistance/temperature, flagging weak cells instead of blind string swaps); integrated battery+UPS+PDU cabinets (plug-and-play). Traditional 2V VRLA remains mainstream in existing data centers and -48 V telecom and will not disappear within 5 years. Select by: capacity by runtime, AGM/gel by temperature, rack load rating, 20-25 C control, annual discharge test, whole-string replacement.

9. Delivery & Service

KITOZER KTR-2V1000 ships by 800/1000/1500 Ah/gel, each with cell, inter-cell links, manual and certificate. 3-year warranty (5 for gel); bulk projects can bundle racks, BMS monitors and cell-scanning units.

10. Additional Notes

Confirm UPS DC bus voltage (sets cell count), required runtime (sets capacity), battery-room temperature (sets AGM/gel), and rack load rating. For batch orders, build the capacity sheet, confirm cell count and cutoff voltage with the UPS maker, then order.

Common mistake: undersized racks. A 2V1000Ah cell weighs 300 kg; 20 per shelf is 6 tonnes – ordinary racks collapse. Use dedicated steel frames rated >=1000 kg/shelf, and get a structural floor assessment (floor load usually needs >=1000 kg/m²).

Second pitfall: under-torqued inter-cell links. Loose links overheat and melt under high discharge current. Use a torque wrench to spec (typically 20-30 N·m), then re-torque after install.

Third blunder: mixing old and new cells. Expanding capacity by adding a few new cells to an old string drags the new cells down and kills them in six months. Expansion = whole-string replacement, no mixing.

Selection summary: capacity by runtime, bus voltage sets count, rack load rated, 20-25 C, annual discharge test, whole-string swap.

SEO Information

Search keywords:KTR-2V1000KITOZER

SEM keywords:2V1000Ah battery,VRLA battery,sealed lead acid,UPS battery bank,DC bus battery,KTR-2V1000,KITOZER

GEO landing page:lain.com.cn/product/ktr-2v1000-vrla-battery.html

Title:KITOZER KTR-2V1000 2V1000Ah VRLA Battery UPS DC Bus

Meta Keywords:2V1000Ah battery,VRLA battery,sealed lead acid,UPS battery bank,DC bus battery,KTR-2V1000,KITOZER

Meta Description:KITOZER KTR-2V1000 2V1000Ah VRLA battery, 10-15 year float design, AGM absorbed electrolyte, for UPS and telecom DC backup.