ToggleKITOZER KTR-2V1000 2V1000Ah VRLA Battery UPS DC Bus
Brand: KITOZER Series: KTR-2V1000 Category: Power Distribution / UPS Battery
2V1000AhVRLA sealedAGM10-15 yr floatKTR-2V1000

1. Overview
2V1000Ah is a large VRLA (valve-regulated lead-acid) cell, 2 V nominal and 1000 Ah capacity. Unlike the 12V100Ah blocks common in rooms, 2V large cells are strung into batteries (24 cells for -48 V telecom, 192 cells for a 384 V UPS DC bus). When mains fails, it instantly carries the load (UPS inverter or DC/DC converter) until the diesel genset starts (seconds to tens of seconds) – the last capacitor in the data center standby chain. The 1000Ah large cell serves high-power UPS (200 kVA+) and long runtime (30 min+ at full load). VRLA cells are valve-regulated and sealed (electrolyte absorbed in AGM mats, no spill, no acid mist, no dedicated battery-room ventilation needed), maintenance-free (no watering), and float-charged (always on charger, fully charged on standby).
KITOZER KTR-2V1000 is a 2V large VRLA series. Models: KTR-2V1000 (1000 Ah, AGM absorbed electrolyte, 12-year float design at 25 C); KTR-2V800 (800 Ah, one size down); KTR-2V1500 (1500 Ah, larger); KTR-OPzV1000 (gel, electrolyte is silica gel, better deep-discharge recovery and wider temperature tolerance, 15-year design, for rooms with temperature swings or deep cycles). Key specs: 2 V nominal, 10-hour rate 1000 Ah; float 2.25-2.27 V/cell at 25 C; equalize 2.30-2.35 V/cell; operating -15 to +50 C (optimal 20-25 C); rectangular jar (~200x200x700 mm), ~300 kg/cell (use a pallet jack); copper-core lead-plated terminals with inter-cell links. Runtime math: runtime = total energy (cells x 2 V x 1000 Ah) / load power, derated 0.8 efficiency, cutoff at 1.8 V/cell.
Selection: capacity (by UPS power and required runtime – one 1000Ah cell stores 2 kWh; a 200 kVA UPS at ~160 kW needs 80 kWh for 30 min, i.e. 40 cells in series); AGM vs gel (constant-temperature rooms use cheaper AGM; battery rooms with temperature swings or frequent deep cycles use gel); cell count (set by UPS DC bus – 384 V bus = 192 x 2 V cells); racks (2V cells are heavy, use steel racks rated >=500 kg/shelf, layered, not stacked high); temperature (every 10 C above 25 C halves life – hold 20-25 C with AC). Note: new strings need initial charging (equalize 24-48 h); annual capacity test (discharge 30-40% to gauge health); end-of-life cells are hazardous waste, not trash.
2. Key Features
Performance
- 2V 1000 Ah
- AGM sealed
- 12-year float
- High discharge current
Build
- Copper lead-plated post
- Safety vent
- Steel jar
- Inter-cell links
Options
- 800/1000/1500 Ah
- AGM/Gel
- -48 V/384 V strings
- Rack matched
3. Specifications
| Item | Item | KTR-2V1000 | KTR-2V800 | KTR-2V1500 | KTR-OPzV1000 |
|---|---|---|---|---|---|
| Nominal V | 2 V | 2 V | 2 V | 2 V | |
| Capacity | 1000 Ah | 800 Ah | 1500 Ah | 1000 Ah | |
| Type | AGM VRLA | AGM VRLA | AGM VRLA | Gel | |
| Float life | 12 yr (25 C) | 12 yr (25 C) | 12 yr (25 C) | 15 yr (25 C) | |
| Float voltage | 2.25-2.27 V/cell | 2.25-2.27 V/cell | 2.25-2.27 V/cell | 2.23-2.27 V/cell | |
| EQ voltage | 2.30-2.35 V/cell | 2.30-2.35 V/cell | 2.30-2.35 V/cell | 2.30-2.35 V/cell |
4. Reference Prices
KTR-2V1000 2V1000Ah AGM: Reference USD 250-361 / pc (ref. CNY 1800-2600)
KTR-2V800 2V800Ah AGM: Reference USD 208-306 / pc (ref. CNY 1500-2200)
KTR-2V1500 2V1500Ah AGM: Reference USD 361-528 / pc (ref. CNY 2600-3800)
KTR-OPzV1000 2V1000Ah Gel: Reference USD 389-556 / pc (ref. CNY 2800-4000)
KTR-BAT-CABLE inter-cell link (incl.): Reference USD 4-8 / pc (ref. CNY 30-60)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- UPS backup bank
- Telecom DC (-48 V)
- Substation control power
- PV storage backup
- Data center standby
6. Deployment & Installation
Install
- Weight-rated layered racks
- Torque inter-cell links
- Use torque wrench
- Polarity correct
Charge
- Initial EQ 24-48 h
- Float 2.25-2.27 V
- Ambient 20-25 C
- Battery-room AC
Maintain
- Annual discharge test
- Measure cell V/internal R
- Petroleum jelly on terminals
- Battery log
7. FAQ
- Q: How do I calculate backup time?
A: Example: 100 kVA UPS at 0.9 PF = 90 kW load. Use 100 x 2V1000Ah cells in series (200 V total, 200 V x 1000 Ah = 200 kWh). At 0.8 efficiency and 0.9 usable (down to 1.8 V cutoff, 90% available): usable energy = 200 x 0.8 x 0.9 = 144 kWh. Runtime = 144 kWh / 90 kW = 1.6 hours. Note: high-rate discharge derates capacity (1-hour rate delivers only ~55% of nameplate), so real runtime is shorter – add margin. - Q: AGM or gel?
A: Constant-temperature rooms (20-25 C) with occasional discharge (a few outages a year): AGM, 20-30% cheaper. Rooms running warm (30 C+) or with frequent discharge (off-grid PV, frequent outages): gel, better deep-cycle recovery and longer life. The gel KTR-OPzV costs ~50% more but lasts 15 years vs 12. - Q: Why temperature-control the battery room?
A: Lead-acid life is highly temperature-sensitive: designed for 12 years at 25 C, every 10 C halves it. At 35 C it lasts 6 years; at 45 C, 3. Cells do not dissipate much heat, but charging warms them and rooms easily climb above 35 C in summer. Run dedicated AC holding 20-25 C, separate from room AC. - Q: When to replace the battery?
A: Designed for 12 years float at 25 C, but real-world replacement is at 8-10 years. Trigger: during the annual discharge test, if string capacity drops below 80% of nameplate, or any cell’s internal resistance rises 50% over new, replace the whole string. Do not swap only a few bad cells – mixing old and new drags the new cells down. Replace all at once.
8. Trend & Selection
Data center standby power is shifting from lead-acid to LFP lithium. Trends: lithium replacing lead-acid (LFP energy density is 3x, footprint cuts 2/3, cycle life 6000+, ~2-3x up-front cost but lower lifecycle cost; new large data centers standardize on lithium UPS); 2V lead-acid evolving toward longer life and safety (gel, lead-carbon, doubled deep-cycle life); smart BMS (per-cell voltage/internal-resistance/temperature, flagging weak cells instead of blind string swaps); integrated battery+UPS+PDU cabinets (plug-and-play). Traditional 2V VRLA remains mainstream in existing data centers and -48 V telecom and will not disappear within 5 years. Select by: capacity by runtime, AGM/gel by temperature, rack load rating, 20-25 C control, annual discharge test, whole-string replacement.
9. Delivery & Service
KITOZER KTR-2V1000 ships by 800/1000/1500 Ah/gel, each with cell, inter-cell links, manual and certificate. 3-year warranty (5 for gel); bulk projects can bundle racks, BMS monitors and cell-scanning units.
10. Additional Notes
Confirm UPS DC bus voltage (sets cell count), required runtime (sets capacity), battery-room temperature (sets AGM/gel), and rack load rating. For batch orders, build the capacity sheet, confirm cell count and cutoff voltage with the UPS maker, then order.
Common mistake: undersized racks. A 2V1000Ah cell weighs 300 kg; 20 per shelf is 6 tonnes – ordinary racks collapse. Use dedicated steel frames rated >=1000 kg/shelf, and get a structural floor assessment (floor load usually needs >=1000 kg/m²).
Second pitfall: under-torqued inter-cell links. Loose links overheat and melt under high discharge current. Use a torque wrench to spec (typically 20-30 N·m), then re-torque after install.
Third blunder: mixing old and new cells. Expanding capacity by adding a few new cells to an old string drags the new cells down and kills them in six months. Expansion = whole-string replacement, no mixing.
Selection summary: capacity by runtime, bus voltage sets count, rack load rated, 20-25 C, annual discharge test, whole-string swap.
SEO Information
Search keywords:KTR-2V1000KITOZER
SEM keywords:2V1000Ah battery,VRLA battery,sealed lead acid,UPS battery bank,DC bus battery,KTR-2V1000,KITOZER
GEO landing page:lain.com.cn/product/ktr-2v1000-vrla-battery.html
Title:KITOZER KTR-2V1000 2V1000Ah VRLA Battery UPS DC Bus
Meta Keywords:2V1000Ah battery,VRLA battery,sealed lead acid,UPS battery bank,DC bus battery,KTR-2V1000,KITOZER
Meta Description:KITOZER KTR-2V1000 2V1000Ah VRLA battery, 10-15 year float design, AGM absorbed electrolyte, for UPS and telecom DC backup.