Brand: KITOZER Series: KTR-DR3 Category: Data Center Engineering / Precision AC Refrigeration Parts
Shell typeReceiver+drier+filterR22/R410A/R134aBrazedKTR-DR3

1. Overview
A precision air-conditioning refrigeration loop is a closed cycle: the compressor squeezes gaseous refrigerant into hot high-pressure gas, the condenser rejects heat and turns it to liquid, the liquid passes through an expansion valve that drops its pressure and temperature before it absorbs heat in the evaporator and returns to the compressor. Between the condenser outlet and the expansion valve inlet, the liquid line needs a buffer: it stores surplus liquid (load changes demand different charge volumes), absorbs residual moisture (water freezes at the expansion valve orifice and blocks it, known as “ice block”), and filters welding slag, copper chips and oxide scale that can jam the expansion valve or score the compressor. The receiver drier is plumbed into the liquid line between condenser and expansion valve.
KITOZER KTR-DR3 is a shell-type receiver drier: a steel pressure-vessel cylinder with copper brazed connections at both ends. Inside, three layers stack from top to bottom: an inlet metal-mesh screen (large debris), a desiccant core (molecular sieve + silica gel, 80-400 g depending on size), and a liquid pick-up tube (draws liquid from the bottom outlet, ensuring no vapor bubbles leave). The top has a sight glass (to observe refrigerant flow; bubbles indicate low charge) and some models add a pressure relief valve. Shell-type differs from coaxial tube type: shell volume is larger (0.5-5 L liquid charge), for 5 kW and above; smaller units below 5 kW use a coaxial tube drier (a copper tube packed with desiccant, no storage). Room precision ACs are typically 12-50 kW and always use shell type.
Selection: connection size (match the liquid line, common 1/2, 5/8, 3/4, 7/8 inch copper tube, brazed); refrigerant type (R22 uses standard desiccant, R410A/R32 needs a larger molecular sieve because POE ester oil is highly hygroscopic); storage volume (15%-25% of system charge, e.g. 1.5-2 L for a 20 kW unit); sight glass (recommended for room ACs – daily inspection for bubbles signals low charge); mounting (vertical, inlet above, outlet below; never horizontal or upside-down); replacement interval (desiccant is saturated after 3-5 years, or whenever the system was opened for service – moisture enters with air, saturating the desiccant quickly). Note: receiver driers are disposable – the desiccant cannot be regenerated, replace the whole unit; when brazing, wrap the shell with a wet towel so heat does not bake the desiccant.
2. Key Features
Storage
- Steel pressure vessel
- 0.5-5 L charge
- Vertical shell
- Bottom outlet
Drying
- Molecular sieve + silica
- ≥3 g water uptake
- R22/R410A/R134a
- Disposable core
Filtering
- Inlet metal mesh
- Removes slag/chips
- Pick-up tube
- Sight glass
3. Specifications
| Item | KTR-DR3-05 | KTR-DR3-10 | KTR-DR3-20 | KTR-DR3-30 |
|---|---|---|---|---|
| Cooling capacity | 5-10 kW | 10-20 kW | 20-35 kW | 35-50 kW |
| Shell volume | 0.5 L | 1.0 L | 2.0 L | 3.0 L |
| Connection | 1/2 inch | 5/8 inch | 3/4 inch | 7/8 inch |
| Desiccant weight | 80 g | 150 g | 250 g | 400 g |
| Refrigerant | R22/R134a | R22/R410A | R22/R410A/R32 | R410A/R32 |
| Sight glass | Optional | Standard | Standard | Standard |
| Working pressure | 4.5 MPa | 4.5 MPa | 4.5 MPa | 4.5 MPa |
4. Reference Prices
KTR-DR3-05 (5-10 kW): Reference USD 25-36 / pc (ref. CNY 180-260)
KTR-DR3-10 (10-20 kW): Reference USD 39-56 / pc (ref. CNY 280-400)
KTR-DR3-20 (20-35 kW): Reference USD 63-90 / pc (ref. CNY 450-650)
KTR-DR3-30 (35-50 kW): Reference USD 90-125 / pc (ref. CNY 650-900)
KTR-DR3-VM sight glass (moisture indicator): Reference USD 6-11 / pc (ref. CNY 40-80)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Precision AC outdoor units
- Condenser to expansion valve liquid line
- Rack-mounted precision AC
- Chilled-water plant stations
- Industrial chiller liquid lines
6. Deployment & Installation
Selection
- Match cooling capacity
- Match line diameter
- Match refrigerant
- R410A specific
Mounting
- Vertical orientation
- Inlet top, outlet bottom
- Wet towel when brazing
- Near expansion valve
Evacuation
- Pull vacuum after brazing
- Hold 24 h pressure test
- Charge by nameplate
- No bubbles in sight glass
7. FAQ
- Q: How often to replace the receiver drier?
A: In a sealed system, every 3-5 years. But whenever the system was opened (service, compressor change, expansion valve change, top-up), air and moisture entered and the desiccant is near saturated – replace it. Tell-tale signs: the sight glass moisture indicator turns from green to yellow/red, or the expansion valve shows “ice block” (cooling works for half an hour then fades; after a warm-up it works again briefly). Ice block means the desiccant is dead and water is freezing at the orifice. - Q: Can R410A and R22 driers be swapped?
A: No. R410A uses POE ester oil, which is extremely hygroscopic (POE exposed to air for one hour absorbs hundreds of ppm of water). It needs a larger desiccant charge and a different sieve (XH-9/XH-11 vs XH-7 for R22). Specify the refrigerant when ordering; the KTR-DR3 line is split by refrigerant type. Using the wrong one saturates quickly and causes ice block. - Q: Where in the liquid line does it go?
A: After the condenser outlet, before the expansion valve, as close to the expansion valve as possible (a short liquid column gives stable subcooling and better throttling). Ahead of it, add a solenoid valve (closes on shutdown to prevent liquid migrating to the evaporator and causing liquid slug on restart). The order is: condenser → receiver → drier filter → sight glass → solenoid → expansion valve. Mount vertical, inlet on top (side or top), outlet at bottom; never horizontal. - Q: Why wrap a wet towel when brazing?
A: Brazing runs at 600-800 °C. Direct heat on the drier fitting travels into the shell and bakes the desiccant (molecular sieve structure breaks down; silica gel releases its crystallization water and contaminates the system). Wrap a wet rag near both fittings, or use a copper water-cooled clamp, and let it cool naturally. Keep each braze under 30 seconds.
8. Trend & Selection
Precision AC refrigeration parts are moving toward integration and digitalization. Trends: integrated refrigerant line modules (receiver, sight glass, solenoid and expansion valve in one pre-assembled skid – fewer field braze joints, fewer leak points); digital sight glasses (moisture and subcooling sensors on RS485 to the EM platform, no manual inspection); low-GWP refrigerant transition (R32, R454B, R290 replacing R410A, requiring matching desiccant types); VRF/variable-speed compressor systems (storage volume must be checked at minimum-load conditions, wider modulation demands more receiver margin). Select by: cooling capacity, line size, refrigerant type, vertical top-in/bottom-out, braze cooling, replace after any system opening, watch the sight glass moisture color.
9. Delivery & Service
KITOZER KTR-DR3 ships by model in individual boxes, each with the shell drier, copper braze adapters, sight glass (on standard models) and manual. 1-year warranty; bulk projects can bundle solenoid valves, sight glass kits, expansion valves and brazing materials.
10. Additional Notes
Confirm cooling capacity (kW), refrigerant type (R22/R410A/R32), liquid line diameter (inch), and vertical clearance. For batch orders, double-check fittings and refrigerant before dispatch to avoid wrong shipments.
Common mistake: horizontal or upside-down mounting. A horizontal shell puts the bottom pick-up tube out of position, so the outlet carries bubbles, the expansion valve feed is unstable, and cooling capacity fluctuates. Mount vertical, top inlet and bottom outlet.
Second pitfall: charging without evacuation after brazing. Air and moisture inside the new joints cause non-condensable gas (N2 takes up condenser volume) and direct water into the system, saturating the desiccant fast. Pull vacuum to -0.1 MPa, hold 24 h without pressure loss, then charge by nameplate weight.
Third blunder: reusing a saturated drier. Once saturated, the desiccant becomes a moisture source (it releases water back into the system), and ice block recurs. When the sight glass moisture core turns yellow/red, or ice block appears, replace the drier immediately.
Selection summary: vertical shell, match capacity and refrigerant, top-in bottom-out, cool when brazing, replace after opening, watch sight glass moisture.
SEO Information
Search keywords:KTR-DR3KITOZER
SEM keywords:receiver drier,shell type drier filter,precision AC receiver,refrigeration drier,data center AC parts,KTR-DR3,KITOZER,data center engineering
GEO landing page:lain.com.cn/product/ktr-dr3-receiver-drier-shell-type.html
Title:KITOZER KTR-DR3 Receiver Drier Shell Type for Precision AC
Meta Keywords:receiver drier,shell type drier filter,precision AC receiver,refrigeration drier,KTR-DR3,KITOZER,data center engineering
Meta Description:KITOZER KTR-DR3 shell-type receiver drier for data center precision AC, stores liquid refrigerant, absorbs moisture, filters debris, 1/2 to 7/8 inch connections.
Anchor: KITOZER by Guangzhou Laian · KITOZER products
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com