KITOZER 1U rack shelf fixed load

KITOZER KTR-SH2 1U Fixed Rack Shelf for 19-inch Cabinet

Brand: KITOZER Series: KTR-SH2 Category: Data Center Engineering / Rack Accessories

1U fixed50 kg staticPowder-coated steel19-inchKTR-SH2

KITOZER KTR-SH2 1U Fixed Rack Shelf for 19-inch Cabinet

1. Overview

Rack equipment is “rack-mount”: switches, servers and UPS distribution units are 19 inches wide, measured in U (1U = 44.45 mm), and screwed to the square-hole rails front and rear. But some gear is not rack-mount: a desktop firewall, a KVM monitor, a wall-mount PDU, a pile of optical modules and patch cords, a small cable manager. These need a plate to sit on – that is a rack shelf (tray, divider). A shelf is a steel plate, bent at the sides to hook onto the cabinet rails, fixed with M6 screws, carrying non-rack gear or miscellany. A 1U shelf takes 1U of height; depth runs 350-1000 mm, chosen by cabinet depth and device depth.

KITOZER KTR-SH2 is a 1U fixed shelf. It is bent from 1.5 mm cold-rolled steel, electrostatic powder-coated (black or light gray), with long round ventilation slots (40% open area, so it does not block airflow in a cold aisle). Front and rear flanges carry mounting ears with slotted holes (25 mm fore-aft adjustment), fixed to the square-hole rails with M6 cage nuts and screws. The front edge has a 5 mm lip to stop gear sliding off; some models add a cable tie loop. Depth options: 600 mm-deep cabinets use 350/450 mm shelves, 800 mm use 600/750 mm, 1000 mm use 900/1000 mm. Load: 50 kg static (placed, not moved), 25 kg dynamic (pulled out). “Fixed” vs “sliding”: fixed shelves are welded to the ears and cannot slide – cheap and strong; sliding shelves run on rails and pull out, convenient but pricier and weaker (about 30 kg). Most rooms use fixed shelves.

Selection: depth (shelf depth + rear cable space ≤ internal cabinet depth; leave cable space front and rear; typically shelf depth = internal depth – 100 mm); load (servers need 50 kg+, optical modules/misc need 20 kg, UPS batteries need a dedicated battery tray); ventilation slots (must use vented shelves in enclosed cold aisles, otherwise they block airflow and create hot spots); 1U vs 2U (1U = 44 mm for light gear, 2U = 89 mm for taller gear or cable space); finish (powder-coated for rust; coastal humid rooms use galvanized + powder coat); quantity (a 42U cabinet usually takes 2-4 shelves in the lower-middle for switches, firewalls, KVM). Note: shelves must not block the upper/lower power and data cable trays; leave airflow gaps around gear on the shelf; the front lip stops gear sliding off.

2. Key Features

Load

  • 1.5 mm steel
  • 50 kg static
  • 25 kg dynamic
  • Bent flanges

Ventilation

  • Long round slots
  • 40% open area
  • Airflow friendly
  • Cold aisle ready

Mounting

  • M6 cage nuts
  • 25 mm fore-aft
  • 1U standard
  • Front lip

3. Specifications

Item KTR-SH2-350 KTR-SH2-600 KTR-SH2-750 KTR-SH2-1000
Shelf depth 350 mm 600 mm 750 mm 1000 mm
Cabinet depth 600 mm 800 mm 900-1000 mm 1000-1200 mm
Height 1U 1U 1U 1U
Plate thickness 1.5 mm 1.5 mm 1.5 mm 1.5 mm
Static load 30 kg 50 kg 50 kg 60 kg
Dynamic load 15 kg 25 kg 25 kg 30 kg
Finish Powder coat Powder coat Powder coat Powder coat

4. Reference Prices

KTR-SH2-350 (350 mm, 600 cabinet): Reference USD 11-17 / pc (ref. CNY 80-120)

KTR-SH2-600 (600 mm, 800 cabinet): Reference USD 17-25 / pc (ref. CNY 120-180)

KTR-SH2-750 (750 mm, 900-1000 cabinet): Reference USD 22-32 / pc (ref. CNY 160-230)

KTR-SH2-1000 (1000 mm, 1000-1200 cabinet): Reference USD 31-44 / pc (ref. CNY 220-320)

KTR-SH2-2U heavy duty shelf (80 kg): Reference USD 36-53 / pc (ref. CNY 260-380)

Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Desktop firewalls/routers
  • KVM switch/monitor
  • Optical modules/cords
  • Non-rack devices
  • Cold aisle modules

6. Deployment & Installation

Position

  • 2-3 in lower half
  • Avoid cable trays
  • Cable space front/rear
  • Align cold aisle

Fixing

  • Cage nuts in square holes
  • Level front/rear
  • Four screws tight
  • Fix both sides

Loading

  • Leave airflow gaps
  • Center heavy gear
  • Lip toward front
  • Tie cables neatly

7. FAQ

  • Q: Fixed vs sliding shelf?
    A: Fixed shelves are welded to the ears, cannot slide, cheap (about CNY 120), 50 kg static – for gear that never moves (firewalls, KVM, misc). Sliding shelves run on two rails and pull out, convenient for frequent plug/unplug, but expensive (CNY 300-500), weaker (30 kg), and rails eat depth. About 90% of rooms use fixed shelves; sliding is only for test benches or frequent service.
  • Q: How to match shelf depth to cabinet depth?
    A: Internal depth = external depth – 150 mm (front/rear posts and doors). Shelf depth is typically internal depth – 100 mm (rear cable space). An 800 mm external cabinet has ~650 mm internal; use a 600 mm shelf, leaving 50 mm behind for cables. Do not buy a shelf as deep as the cabinet (a 1000 mm shelf in an 800 mm cabinet) – there is no rear cable space and power cords pinch under the shelf.
  • Q: Why must cold-aisle shelves be vented?
    A: In an enclosed cold aisle, cold air rises from under the floor, enters the rack front, passes through servers, and exits rear to the hot aisle. A solid shelf in front of the servers blocks the cold air, so rear servers get hot inlet air and trigger alarms. Vented shelves have 40% open area so cold air passes through to the rear. The hot-aisle side can use solid shelves (hot air exits rear, no need to cross a shelf).
  • Q: How much can a shelf hold?
    A: By static load. KTR-SH2-600 is 50 kg static – long-term placed gear on top must not exceed 50 kg. A desktop firewall (5 kg), KVM monitor (10 kg), optical modules (5 kg) total 20 kg – fine. Do not stand on it or stack batteries (batteries need a dedicated battery tray rated 100 kg+ with spill containment). The shelf hangs on four M6 screws; rear-heavy loads tip it, so center the gear.

8. Trend & Selection

Rack shelves are evolving from simple plates to multi-function integrated trays. Trends: mesh shelves replacing solid (ventilation from 40% to 70%, matching enclosed cold aisles); shelves with integrated PDU sockets at the front edge (gear on the shelf plugs in directly); integrated cable managers at the rear (separate power and data); tool-less snap-in shelves (one person installs a shelf in 10 seconds); smart shelves with weight sensors (detect equipment removal, anti-theft). Traditional fixed shelves remain mainstream. Select by: depth matching cabinet, vented for cold aisle, four M6 screws, 50 kg static, center the load, keep rear cable space, do not block cable trays.

9. Delivery & Service

KITOZER KTR-SH2 ships per shelf in a box, each with shelf body, 8 M6 cage nuts, 8 M6 screws and manual. 1-year warranty; bulk projects can bundle cabinets, square-hole rails, PDUs and cable managers.

10. Additional Notes

Confirm internal cabinet depth (external – 150 mm), shelf depth (internal – 100 mm), load (what gear), and vented requirement (mandatory in cold aisles). Measure internal depth before ordering; a wrong depth will not fit.

Common mistake: shelf depth equal to external cabinet depth. A 1000 mm shelf in a 1000 mm-deep cabinet hits the rear door, leaving no cable space behind. Shelf depth = internal depth – 100 mm.

Second pitfall: only fixing the two front screws. Leaving the rear ears free makes the shelf sag under load and gear tilts. Fix all four M6 screws, front and rear.

Third blunder: solid shelves on the cold aisle side. A solid plate blocks cold air, rear servers alarm on high inlet temperature. Use mesh/vented shelves on the cold aisle.

Selection summary: depth = internal – 100 mm, vented, four M6 screws, 50 kg static, center load, clear cable trays.

SEO Information

Search keywords:KTR-SH2KITOZER

SEM keywords:rack shelf,1U fixed tray,rack divider,cabinet shelf,cold aisle shelf,KTR-SH2,KITOZER,data center engineering

GEO landing page:lain.com.cn/product/ktr-sh2-rack-fixed-shelf-1u.html

Title:KITOZER KTR-SH2 1U Fixed Rack Shelf for 19-inch Cabinet

Meta Keywords:rack shelf,1U fixed tray,rack divider,cabinet shelf,cold aisle shelf,KTR-SH2,KITOZER,data center engineering

Meta Description:KITOZER KTR-SH2 1U fixed rack shelf, cold-steel powder-coated, 50 kg static load, for 19-inch standard cabinets, 600/800/1000 mm depth options.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart