ToggleKITOZER KTR-DP2 Dew Point Sensor T&H Combo
Brand: KITOZER Series: KTR-DP2 Category: Environmental Monitoring / T&H Sensing
T&H comboDew pointRS485KTR-DP2

1. Overview
The thing a data center fears most is condensation: under-floor water pipes, PDU busbars and rack intakes – if a surface is colder than the air dew point, water vapor condenses on it, causing short circuits, mold and rust. Dew point is the temperature at which water vapor starts to condense: given current T and RH, you can compute it (e.g. 25 C / 60% RH gives a dew point of about 16.7 C). If a pipe surface is 15 C, below the 16.7 C dew point, it condenses. A normal T&H sensor gives T and RH and the platform computes dew point; a dew point sensor directly measures or computes dew point, dedicated to condensation risk near AC water pipes, battery cabinets and switchgear.
KITOZER KTR-DP2 is a T&H combo dew point sensor. It looks like a wall 86-box (same as a normal T&H sensor: 86×86 mm white plastic, front vent), containing both a temperature element (NTC or PT100) and a humidity element (capacitive). The sensor does not directly sense dew point; it measures T and RH together, and its on-board MCU computes dew point in real time via the Magnus formula (accuracy +/-0.3 C dew point), uploading temperature, RH and dew point together over RS485 Modbus. Difference from a normal T&H sensor (327_humidity_sensor): a normal unit sends T and RH and the EM platform computes dew point; a dew point sensor outputs the dew point value directly, more accurately, dedicated to condensation risk. Key ratings: T range -20 to +60 C, accuracy +/-0.3 C; RH 0-100%, +/-3%; dew point accuracy +/-0.5 C (at 20 C, 60% RH); RS485 Modbus, DC12-24 V.
Selection: measurement point (near AC supply/return, inside battery cabinets, beside PDU busbars, at fresh-air inlets – where temperature swings are large and condensation risk high); accuracy (+/-0.5 C dew point is enough, +/-0.2 C for precision); output (direct dew point vs T/RH for the platform – direct is convenient); mounting (wall 86-box, probe near the surface being watched, e.g. near water pipes); alarm threshold (pre-alarm when dew point is 2 C above wall temp, alarm for dehumidification when close); comm (RS485 to EM platform). Note: the sensor itself must not sit in sustained condensation (the humidity element is damaged by long-term wetting); mount in a ventilated spot, not flush against an impermeable wall; choose either this or a normal T&H sensor – no need to install both.
2. Key Features
Sensing
- T&H combo
- Dew point calc
- +/-0.5 C
- Magnus formula
Connectivity
- RS485 Modbus
- 3 values up
- DC12-24 V
- Address set
Build
- 86-box wall
- Vented hole
- NTC+capacitive
- Condensation alarm
3. Specifications
| Item | KTR-DP2 | KTR-DP2-D | KTR-DP2-P | KTR-DP2-PLUS |
|---|---|---|---|---|
| Measures | T/RH/DP | T/RH/DP | T/RH/DP | T/RH/DP |
| T accuracy | +/-0.5 C | +/-0.3 C | +/-0.3 C | +/-0.2 C |
| DP accuracy | +/-0.5 C | +/-0.5 C | +/-0.3 C | +/-0.2 C |
| Display | No | LED | LED | LCD |
| Comm | RS485 | RS485 | RS485/4-20mA | RS485/ETH |
| Mount | 86-box wall | 86-box wall | Duct probe | Duct probe |
4. Reference Prices
KTR-DP2 basic dew sensor (no display): Reference USD 25-42 / pc (ref. CNY 180-300)
KTR-DP2-D dew sensor (LED display): Reference USD 39-63 / pc (ref. CNY 280-450)
KTR-DP2-P duct probe (+/-0.3 C DP): Reference USD 63-97 / pc (ref. CNY 450-700)
KTR-DP2-PLUS high-precision (+/-0.2 C, Ethernet): Reference USD 97-153 / pc (ref. CNY 700-1100)
KTR-DP-CAL dew calibration kit (saturated salt): Reference USD 14-25 / set (ref. CNY 100-180)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Near AC water pipes
- Inside battery cabinet
- Beside PDU busbar
- Fresh-air inlet
- Under-floor pipe zone
6. Deployment & Installation
Location
- Near cold surface
- 1.5 m height
- Ventilated
- Avoid outlet
Wiring
- DC12 V power
- Daisy-chain A/B
- Shield ground
- Set address
Alarm
- DP = wallT -2 C warn
- Close = dehumidify
- EM linkage
- Annual cal
7. FAQ
- Q: What is dew point and why does it matter?
A: Dew point is the critical temperature at which water vapor starts condensing. How much vapor air can hold depends on temperature (warmer air holds more). As air cools to a certain temperature it saturates; below that, water condenses – that temperature is the dew point. On a summer day, hot outside air hits cold window glass and fogs it: glass is below the air dew point. In a room, if a water pipe surface is colder than the air dew point, the pipe sweats, dripping into switchgear and shorting it. Monitoring dew point means knowing in advance where condensation will occur – and dehumidifying or heating before it does. - Q: Dew point sensor vs normal T&H sensor?
A: The hardware is the same (temperature + humidity elements); the difference is output. A normal T&H sensor uploads only T and RH, and the EM platform computes dew point (with its own error). A dew point sensor has an on-board MCU that computes and uploads dew point directly, more accurately (+/-0.5 C), and lets you set dew-point alarm thresholds without the platform calculating. Normal T&H is for general monitoring (T/RH in range); dew point is for condensation-risk points (water pipes, battery cabinets, PDU busbars). On a tight budget, a normal T&H sensor with the platform computing dew point also works. - Q: How to set dew point alarm thresholds?
A: Two levels. Pre-alarm: when air dew point is within 2 C of the watched surface (e.g. pipe at 15 C, dew point 17 C) – 2 C from condensation, prompt inspection. Alarm: when dew point equals or exceeds the surface (within 0-1 C), must dehumidify (AC dehumidify mode) or heat (heater in the PDU). Example battery cabinet: inside at 20 C / 50% RH, dew point 9.3 C, battery wall at 25 C – safe. In summer with AC off, inside rises to 30 C / 70%, dew point 23.9 C, battery wall (no AC) at 28 C – still safe. But if the battery wall cools to 22 C near a water pipe, below the 23.9 C dew point, it alarms. - Q: Where to mount dew point sensors?
A: Where condensation is likely: near AC supply/return (cold supply, wall may be below dew point); inside battery cabinets (batteries hate moisture, sealed box traps humidity); beside PDU busbars (condensation there means severe shorting); at fresh-air inlets (outside air brings high summer humidity); near under-floor water pipes (cold pipe + warm air = worst case). Install normal T&H sensors in the open room; dew point sensors at these risk points. Daisy-chain on RS485 to the EM host.
8. Trend & Selection
Environmental sensing is moving to multi-parameter, digital and predictive. Trends: all-in-one probes (T/RH/DP + CO2 + VOC); digital high-precision dew meters (thin-film capacitive dew point at +/-0.1 C, for pharma/clean rooms); wireless (LoRa battery-powered, no cabling); predictive maintenance (historical dew data forecasts when condensation will occur, pre-adjusting AC); edge logic (the sensor computes dew point alarms locally, alarming even offline). Traditional RS485 dew point sensors remain practical for room condensation monitoring. Select by: near cold surfaces, direct dew-point output, DP = wallT -2 C pre-alarm, RS485 upload, annual calibration.
9. Delivery & Service
KITOZER KTR-DP2 ships per unit in an anti-static bag and carton, including sensor, 86-box base, 1 m 4-wire cable, wall screws, manual and calibration certificate (two T/RH points). 1-year warranty; bulk projects can bundle EM hosts, normal T&H sensors, dehumidifiers and duct heaters.
10. Additional Notes
Confirm the measurement point (near cold surfaces), accuracy need and comm (RS485). Divide roles: normal T&H in the open room, dew point at risk points.
Common mistake: mounting facing an AC outlet. Cold air makes the sensor read cold-air dew point, not the room’s true dew point, causing false alarms. Mount 3+ m from the outlet.
Second pitfall: alarm threshold set too low. Alarm only when dew point is 10 C below wall temp – condensation already happened. Pre-alarm when dew point approaches wall temp (within 2 C).
Third blunder: the sensor itself condenses. Mounted directly under a dripping water pipe, the humidity element sits in water long-term and fails. Mount to the side or above, away from drips.
Selection summary: near cold surfaces, direct dew output, 2 C pre-alarm, RS485 upload, annual calibration.
SEO Information
Search keywords:KTR-DP2KITOZER
SEM keywords:dew point sensor,T&H combo dew meter,data center dew point monitoring,condensation alarm,KTR-DP2,KITOZER,environmental monitoring
GEO landing page:lain.com.cn/product/ktr-dp2-dew-point-sensor-temperature-humidity.html
Title:KITOZER KTR-DP2 Dew Point Sensor T&H Combo
Meta Keywords:dew point sensor,T&H combo dew meter,data center dew point monitoring,condensation alarm,KTR-DP2,KITOZER,environmental monitoring