KITOZER KTR-FAN4 4-Fan Rack Fan Unit Speed Controlled

Brand: KITOZER Series: KTR-FAN4 Category: Data Center Engineering / Rack Cooling

4 fansAuto speedTemp-linkedKTR-FAN4

1. Overview

Rack cooling has two approaches. One is room-level precision AC feeding cold air under the floor, racks drawing cold air at the front and exhausting hot air at the rear, using hot/cold aisle containment to return hot air to the AC. The other is a fan tray (roof fan / fan unit) mounted on top or rear of the rack, actively pulling hot air out – especially useful in modular cold-aisle containment where a row of fans at the rack top or at the end of the enclosed aisle pulls hot air back to the plenum or return duct. The fan tray should not run at full speed all the time: slow and quiet when cold, fast when hot, controlled by a thermostat or RS485 remote speed.

KITOZER KTR-FAN4 is a 4-fan speed-controlled rack fan unit. It is a 19-inch 3U/4U tray mounted in the last U at rack top, with four 120×120 mm EC axial fans (24 V DC), a front control panel (temperature display, setpoint, manual/auto), and RS485 to the EM platform. Key ratings: total airflow about 350 m3/h at full speed, static pressure 60 Pa, noise 45-55 dB(A) depending on speed, operating 0-55 C, AC220 V in (converted to DC24 V inside), speed range 30%-100%, temp probe at rack inlet or exhaust with adjustable thresholds (e.g. slow below 30 C inlet, full speed at 35 C). EC fans save 30%-50% over AC and support PWM speed control.

Selection: airflow matched to load (about 200-300 m3/h per kW of IT load; a 5 kW rack needs 1000-1500 m3/h, so one KTR-FAN4 at 350 m3/h is not enough – use two in series or a 6-fan model); static pressure (underfloor ducted air needs high static; ducted to ceiling needs less); fan type (EC DC variable speed vs AC fixed – data centers use EC); location (rack top vs rear blanking zone – top exhaust of hot air is most direct); control (local thermostat vs RS485 remote – modular cold aisle uses RS485 for central monitoring); redundancy (N+1 – four fans, one fails and three still run; high-density racks choose 6-fan N+2). Note: do not block the intake with cables; install blanking panels so cold air does not short-circuit; feed the fan from UPS, else it stops with AC.

2. Key Features

Airflow

  • 4x EC fans
  • 350 m3/h
  • 60 Pa
  • 30%-100% speed

Control

  • Temp-linked
  • Local panel
  • RS485 remote
  • Manual/auto

Build

  • 3U rack
  • 220V to 24V
  • 45-55 dB(A)
  • N+1 redundancy

3. Specifications

Item KTR-FAN4 KTR-FAN6 KTR-FAN4-RS KTR-FAN4-PRO
Fans 4 6 4 4
Airflow 350 m3/h 550 m3/h 350 m3/h 420 m3/h
Type EC 24V EC 24V EC 24V EC 48V
Control Local T Local T RS485 RS485+ETH
Noise 50 dB(A) 55 dB(A) 50 dB(A) 45 dB(A)

4. Reference Prices

KTR-FAN4 basic 4-fan (local thermostat): Reference USD 90-132 / pc (ref. CNY 650-950)

KTR-FAN6 6-fan high airflow (550 m3/h): Reference USD 132-195 / pc (ref. CNY 950-1400)

KTR-FAN4-RS RS485 model (to EM): Reference USD 125-180 / pc (ref. CNY 900-1300)

KTR-FAN4-PRO low-noise Ethernet (48V, 45 dB): Reference USD 195-280 / pc (ref. CNY 1400-2000)

KTR-FAN-KIT temp probe + cable: Reference USD 11-21 / set (ref. CNY 80-150)

Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Modular cold-aisle rack tops
  • High-density racks (>5 kW)
  • Hot-aisle end exhaust
  • Network/server rack boost
  • Small room no underfloor

6. Deployment & Installation

Mount

  • Top 3U position
  • Exhaust upward
  • Clear intake
  • UPS feed

Wiring

  • AC220V in
  • Probe at intake
  • RS485 daisy
  • Ground

Commission

  • Set 30/35 C
  • Auto mode
  • Verify inlet T
  • Fan-fail alarm

7. FAQ

  • Q: We already have precision AC – why add rack fans?
    A: Room-level AC feeds the whole room; servers’ own power-supply fans pull cold air through. Problems: open U positions without blanks let cold air short-circuit around the rack rather than through servers; high-density racks (>5 kW) exceed server fan pull and hot spots build up; even with modular cold-aisle containment, hot air must be pulled from rack top back to the return plenum – natural convection alone is weak. A rack fan unit actively exhausts, creates slight negative pressure, forces hot air to the return path, and with blanks plus containment eliminates hot spots.
  • Q: How to size airflow? What if one unit is not enough?
    A: Rule of thumb: 200-300 m3/h per kW of IT load. A rack with one 5 kW server needs 1000-1500 m3/h; KTR-FAN4 at 350 m3/h means 3-4 units, or KTR-FAN6 (550 m3/h) at 2-3 units. Do not count racks – count actual IT power. For 8-10 kW racks, use the 6-fan model or stack two fan trays. Ask the customer for actual rack power density, not rack weight.
  • Q: EC vs AC fans? Why is EC more expensive?
    A: AC fans run directly on 220 V, simple and cheap (100-200 CNY), but fixed speed (cannot modulate), noisy (>60 dB), and power-hungry. EC fans are brushless DC with an internal driver board, support PWM speed (30%-100%), slow and quiet when cool, fast when hot; same airflow uses 30%-50% less energy and lasts longer (50k vs 30k hours). The premium buys the driver and control electronics. For 24×7 equipment, EC pays back in power savings and noise within three years.
  • Q: What if a fan fails? Is there redundancy?
    A: KTR-FAN4 has four parallel fans, N+1: one fails, three still deliver 75% airflow and the rack does not immediately thermal-shutdown. A failed fan triggers the panel LED or RS485 alarm to the EM platform, so maintenance is scheduled rather than emergency stop. High-density racks should choose the 6-fan model (N+2) or stack two KTR-FAN4. Note: fan power must come from UPS – on utility loss, the UPS feeds IT while fans keep exhausting; otherwise racks overheat in minutes. Fan power is small (30-60 W), so it lasts on battery.

8. Trend & Selection

Rack cooling is moving to high density, intelligence and liquid-cooling hybrid. Trends: high-density EC fan trays (1U/2U, 1000 m3/h+ per unit, for 10 kW+ racks); smart fans with temperature arrays per rack zone rather than one setpoint; FSU integration (fan tray + PDU + T/H + access in one rack intelligent unit); air-liquid hybrid (rear-door heat exchangers RDHx for high density, transition before full liquid cooling); DC power (48 V directly on the DC bus, higher efficiency). EC 4-fan trays remain the mainstream supplementary cooling in modular cold aisles. Select by: airflow matched to IT power, EC variable speed, N+1 redundancy, RS485 uplink, UPS feed.

9. Delivery & Service

KITOZER KTR-FAN4 ships per unit in carton with foam, including fan tray, 1.5 m AC cord, 2 m temp probe, RS485 terminal block, mounting screws, manual and nameplate. 1-year warranty (50k-hour fan life); bulk projects can bundle blanking panels, PDUs, T/H sensors and cold-aisle louvers.

10. Additional Notes

Confirm actual rack IT power (not rack weight), top 3U location, control (local vs RS485) and redundancy. Do this together with blanking panels and cold-aisle containment – a fan alone works poorly.

Common mistake: cable bundle blocking the intake. In the top 3U, messy cables across the front block cold air, the fan spins against stagnant air and heats up. Leave 10 cm clear on the intake side; route cables along the side.

Second pitfall: missing blanking panels. The fan pulls, but cold air is drawn through empty U slots instead of servers, leaving hot spots beside servers. Blank every empty U so negative pressure passes through servers only.

Third blunder: fan not on UPS. On utility loss, the UPS feeds IT but the fan on mains stops, hot air cannot leave, and racks thermal-shutdown within minutes. Fan must be on UPS output.

Selection summary: airflow by IT power, EC variable speed, N+1, RS485 uplink, UPS feed.

SEO Information

Search keywords:KTR-FAN4KITOZER

SEM keywords:rack fan unit,4-fan speed controlled,rack cooling fan,temp-linked fan,EC fan tray,KTR-FAN4,KITOZER,data center engineering

GEO landing page:lain.com.cn/product/ktr-fan4-rack-fan-unit-4-fan-speed-control.html

Title:KITOZER KTR-FAN4 4-Fan Rack Fan Unit Speed Controlled

Meta Keywords:rack fan unit,4-fan speed controlled,rack cooling fan,temp-linked fan,KTR-FAN4,KITOZER,data center engineering

Meta Description:KITOZER KTR-FAN4 4-fan speed-controlled rack fan unit, auto speed by temp, top-of-rack exhaust, RS485 monitoring, 350 m3/h.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart