KITOZER 8 channel locating leak controller

KITOZER KTR-WC2 8-Zone Locating Water Leak Controller

Brand: KITOZER Series: KTR-WC2 Category: Environmental Monitoring / Leak Detection

8 zonesLocatingSensing cableKTR-WC2

KITOZER KTR-WC2 8-Zone Locating Water Leak Controller

1. Overview

A data center fears water: chilled-water pipes, humidifier lines, sprinklers, roof leaks, under-floor AC condensate lines. A drip into a PDU, battery cabinet or server causes shorting and fire. Leak detection comes in two forms: point probes (one probe watches one spot, e.g. a water sensor under a pipe) and sensing cable (a cord laid around a pipe run – any point on the cord alarms; a locating cord tells you the meter mark of the leak). A locating cable system has three parts: the controller (host that processes, locates and uploads), the sensing cable (laid along pipes, four conductors bridged by water) and terminators that compute distance. Eight zones means the host accepts eight sensing cords, covering eight areas (e.g. one cord around each of eight AC units’ pipes).

KITOZER KTR-WC2 is an 8-zone locating water leak controller. Metal DIN-rail chassis (mounted on standard DIN rail in a 19-inch rack or distribution box), each zone takes one locating sensing cable (up to 100 m). The host continuously monitors cable resistance; water bridges two conductors and the host computes the distance from the cord head (accuracy +/-1 m). The LCD shows which cord and which meter mark leaked; RS485 Modbus uploads to the EM platform; two relay outputs link to shut a solenoid valve and trigger a sounder. Key ratings: 8 zones, up to 100 m cord per zone, locating accuracy +/-1 m, response <3 s, DC24 V or AC220 V supply, 0-50 C, relay rating 30 V DC/2 A, supports leak location / leak alarm / cable-break detection (a broken cord also alarms). Matching cable: KTR-RS locating cord (4-conductor, adsorptive, conducts only for water - not oil - and flexible).

Selection: zone count (8 zones cover 8 areas; a small room needs 2-4, a large room 16); locating vs non-locating (locating tells you the meter mark; non-locating only says “this area has water” – choose locating for large runs, point probes for small areas); cord length (within 100 m per cord; add a repeater beyond); I/O (RS485 to EM; relays for solenoid valves); cord material (locating vs non-locating; adsorptive cord reacts only to water, fewer false alarms from oil); mounting (along AC pipes, humidifier lines, sprinklers; cord 10 cm off the wall, clipped every 0.5 m). Note: keep the cord away from power cables (interference); do not let long-term oil/dust sit on it (false alarms); dry the leak and reset (button or auto); use proper terminators on cord ends – do not twist bare wires together.

2. Key Features

Detection

  • 8 zones
  • Locating +/-1 m
  • 100 m cord
  • Response <3 s

Output

  • RS485 Modbus
  • 2 relays
  • LCD display
  • Cable-break

Build

  • DIN rail
  • DC24V/AC220V
  • Adsorptive cord
  • No oil trigger

3. Specifications

Item KTR-WC2-4 KTR-WC2 KTR-WC2-16 KTR-WC-PLUS
Zones 4 8 16 8
Locating +/-1 m +/-1 m +/-1 m +/-0.5 m
Cord length 100 m 100 m 100 m 200 m
Comm RS485 RS485 RS485/ETH RS485+ETH
Relays 2 2 4 4

4. Reference Prices

KTR-WC2-4 4-zone locating controller: Reference USD 167-250 / pc (ref. CNY 1200-1800)

KTR-WC2 8-zone locating controller: Reference USD 250-361 / pc (ref. CNY 1800-2600)

KTR-WC2-16 16-zone (RS485/Ethernet): Reference USD 389-556 / pc (ref. CNY 2800-4000)

KTR-WC-PLUS high-precision (+/-0.5 m, 200 m): Reference USD 486-694 / pc (ref. CNY 3500-5000)

KTR-RS-100 locating sensing cord (100 m/roll): Reference USD 83-139 / roll (ref. CNY 600-1000)

Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Chilled-water pipe perimeter
  • Humidifier lines
  • Under-floor condensate
  • Sprinkler joints
  • Roof/wall seepage points

6. Deployment & Installation

Lay cord

  • Around pipe run
  • 10 cm off wall
  • Clip every 0.5 m
  • Avoid power cables

Wiring

  • Cord to zone
  • Use terminators
  • RS485 daisy
  • Relay to valve

Commission

  • Drop water test
  • Verify linkage
  • Cable-break test
  • Verify platform

7. FAQ

  • Q: Point probes vs sensing cable – how to choose?
    A: Point probes are cheap (50-200 CNY), one spot each, good at known leak points (e.g. under an AC drain pan). But a 15 m pipe with joints in the middle leaks where a point probe cannot see. Sensing cable costs more (controller + cord, several thousand), runs around the whole pipe, alarms anywhere, and locating tells you the meter mark. Budget: a small room with 1-2 AC units uses point probes at the drain pan and joints; a large room with many AC units, long pipes and under-floor runs uses a locating cable system. Combine them: cable for area coverage, point probes at critical spots (always put one under a PDU).
  • Q: What does “locating accuracy +/-1 m” mean? How is it computed?
    A: A locating cable has four conductors (two signal, two reference) with uniform resistance per meter. Water short-circuits two signal conductors at a point; the host measures loop resistance and computes distance by ratio: e.g. a 100 m cord at 100 ohm, a measured short at 35 ohm means a leak at 35 m. +/-1 m is the engineering tolerance (uniform resistance plus water temperature effects) – enough to find the leak (open the floor near the 35 m mark and look for joints). A non-locating cord only reports “this cord conducts” without the meter mark, so finding a leak in a large area means searching segment by segment.
  • Q: Do oil, dust or condensation cause false alarms?
    A: The locating cord is an adsorptive conductive polymer that reacts only to water (water bridges the conductors) – oil does not conduct and does not trigger; dry dust does not. But long-term oil soaking (e.g. a kitchen-like fume environment) or dust mixed with water caked on the cord can false-alarm. Install: cord 10 cm off the wall (no direct drip from condensation); do not lay it on the floor (dusty) – raise it 5 cm on brackets; clean the cord annually (dry cloth). Condensate itself is water and will alarm – that is what we want (a blocked condensate drain should alarm). Distinguish normal drainage (into the drain pipe, not dripping on the cord) from overflow (blocked drain, which does reach the cord).
  • Q: What does the leak alarm link to? How to wire the solenoid valve?
    A: KTR-WC2 has two relay outputs (dry contacts) that close (or open, configurable) on alarm. Typical linkage: shut the inlet solenoid valve (mounted on the AC chilled-water supply; on alarm it cuts water to stop further leakage); trigger a sounder/beacon (red flash + buzzer locally); upload to EM platform (SMS/app alert to operations); shut down the AC on a severe leak. Relay current is small (2 A); if the solenoid is 220 V high-current, drive it through an intermediate relay – do not drive it directly. During commissioning, pour a cup of water on the cord and verify all four: LCD shows the leak point, RS485 reports to EM, relay trips the valve, sounder fires.

8. Trend & Selection

Leak detection is moving to smart, wireless and integrated. Trends: smart locating cords (each cord with a digital tag, auto-identifying zones); wireless leak (LoRa battery-powered, no RS485 wiring, for retrofits); AI water cameras (visual recognition of pooled water); integrated platform (leak combined with T/H, access and UPS in DCIM); self-diagnostics (cord aging and poor contact proactively reported). The traditional 8-zone locating controller remains the workhorse in room environmental monitoring. Select by: zones for area count, locating for finding the leak, adsorptive cord against false alarms, RS485 uplink, relay to shut the valve, annual cord cleaning.

9. Delivery & Service

KITOZER KTR-WC2 ships per unit in carton, including controller, DIN clips, cord-end connectors, 2 terminators, power adapter, RS485 terminals, manual and nameplate. 1-year warranty; bulk projects can bundle locating cables, point probes, solenoid valves, sounders and EM hosts.

10. Additional Notes

Confirm zone count (number of areas), need for locating, cord length and linked equipment (valve current). Bundle the cord, valve and EM platform – a controller alone without a cord is useless.

Common mistake: laying the cord on the floor. Floor dust, mop water and long-term condensate soaking cause frequent false alarms. Raise the cord 5 cm along the pipe, 10 cm off the wall.

Second pitfall: running the cord parallel to power cables. Power noise interferes with the cord’s weak signal, causing false or missed alarms. Keep 30 cm+ from 380 V power; cross at 90 degrees.

Third blunder: not resetting after a leak. After drying, press reset on the controller or remotely in software; otherwise the EM platform keeps alarming. Do a periodic water-drop test to prove the system still works.

Selection summary: zones by area, locating to find the leak, adsorptive cord against false alarms, RS485 uplink, valve linkage, elevated lay-out.

SEO Information

Search keywords:KTR-WC2KITOZER

SEM keywords:water leak controller,8-zone locating leak,sensing cable leak detection,locating leak monitor,cord leak detection,KTR-WC2,KITOZER,environmental monitoring

GEO landing page:lain.com.cn/product/ktr-wc2-8-zone-locating-water-leak-controller.html

Title:KITOZER KTR-WC2 8-Zone Locating Water Leak Controller

Meta Keywords:water leak controller,8-zone locating leak,sensing cable leak detection,locating leak monitor,KTR-WC2,KITOZER,environmental monitoring

Meta Description:KITOZER KTR-WC2 8-zone locating water leak controller, sensing cable pinpoints leak location, RS485 upload, relay linkage, for room AC water pipes.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart