KITOZER 24 port LC APC patch panel

KITOZER KTR-LC24A Fiber Patch Panel / 24-Port LC APC Rack-Mount ODF

Brand: KITOZER Series: KTR-LC24A Category: Data Center Engineering / Fiber Distribution

fiber patch panel24-port LCAPC1U rackODF

KITOZER KTR-LC24A Fiber Patch Panel / 24-Port LC APC Rack-Mount ODF

1. Overview

The fiber patch panel (ODF, Optical Distribution Frame) is the central distribution point of data center fiber cabling — building/campus cable enters the room, is terminated by splicing in the ODF, and patched to switch ports via adapters and patch cords. The ODF integrates cable anchoring, splicing, slack storage and patching in one rack unit, the core node of the ELV fiber system. The KITOZER KTR-LC24A is a 24-port LC APC fiber patch panel, 1U rack-mount in a standard 19-inch cabinet. “24-port” means 24 fibers: fitted with 12 LC duplex APC adapters (each duplex = 2 fibers). APC (Angled Physical Contact, 8° polish) is green, high return loss (≥60dB), suited to CATV, PON and high-speed (100G/400G) single-mode links, reducing reflection into optics.

In room ELV systems, KTR-LC24A mounts in network racks: cable is spliced in the rear splice tray (with slack), and front adapters accept LC APC patch cords to switches. 1U is compact; high-density rooms stack multiple ODFs. Bundled with splice trays, pigtails, cable anchors and cable management rings. It is the junction of the fiber backbone — all cable terminates here, all patching originates here.

2. Key Features

Port config

  • Capacity: 24 fibers (12× LC duplex APC).
  • Interface: LC APC (green), single-mode OS2.
  • Mount: 1U, 19-inch rack.
  • Adapters: snap-in, replaceable.

Construction

  • Body: cold-rolled steel, powder-coated.
  • Splice tray: modular, flip-over.
  • Cable anchor: rear strain relief.
  • Slack: stored in splice tray.

Optical

  • Insertion loss: ≤0.3dB per adapter.
  • Return loss: ≥60dB (APC).
  • Use: OS2 single-mode, long high-speed.
  • Temp: -10℃~+60℃.

3. Specifications

Item KTR-LC24A
Ports 24 fibers (12×LC duplex APC)
Connector LC APC (green)
Fiber SM OS2 (9/125μm)
Height 1U (19-inch)
Insertion loss ≤0.3dB/adapter
Return loss ≥60dB
Splice tray Modular flip

4. Reference Prices

KTR-LC24A 24-port LC APC patch panel (1U, 12 LC duplex APC adapters): Reference USD 49~90 (ref. CNY 350~650 at ~7.2)

Reference only; final quote applies. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Data center fiber backbone ODF.
  • CATV/PON distribution.
  • 100G/400G high-speed single-mode links.
  • Building cable room termination.
  • Centralized fiber management.

6. Installation & Maintenance

Installation

  • Mount 1U in 19-inch rack with M6 cage nuts.
  • Cable enters rear, anchored to holder.
  • Strip cable; splice pigtail (loss ≤0.1dB).
  • Place splice in tray; coil slack.
  • Insert pigtail plugs into front LC adapters.
  • Patch front LC APC cords to switches.
  • Test link loss with OTDR/power meter.

Maintenance

  • Dust-cap unused adapters.
  • Clean end faces before mating.
  • No hard bends in tray slack.
  • Route cords neatly; bend radius ≥10×.
  • Troubleshoot splice/adapter on excess loss.

7. FAQ

  • Q: 24-port vs 48-port?
    A: By cable cores and spare: 24-core cable uses 24-port (1U); 48-core uses 48-port (2U) or two 24-port. Reserve 30% spare.
  • Q: APC vs UPC panel?
    A: APC green, 8° angle, return loss ≥60dB, for CATV/PON/high-speed; UPC blue, flat, ≥50dB, for general data. APC and UPC cannot mate.
  • Q: How many cables per ODF?
    A: By cores: 24-port terminates 24 fibers — one 24-core cable or two 12-core. Larger cables need bigger ODF.
  • Q: ODF vs terminal box?
    A: ODF is rack-mount (1U/2U) for centralized rack management; terminal box is wall-mount for low core counts on the wall.

8. Trend & Selection

Data center fiber goes high-density and high-bandwidth; ODF evolves from traditional splicing to pre-terminated MTP/MPO high-density, and LC APC grows in high-speed single-mode links. Size by core count (24/48); use APC for CATV/PON/high-speed; compact 1U; splice loss ≤0.1dB; clean end faces; reserve spare cores.

9. Delivery & Service

KITOZER provides patch panel selection: based on cable cores, connector type (LC APC/UPC) and rack space, we configure KTR-LC24A. Bundled with LC APC cords, pigtails and splicing service. Delivery includes panel, adapters, splice tray and cable anchor. Warranty covers link testing and splice quality checks.

10. Additional Notes

A common pitfall is APC/UPC mixing. Green APC and blue UPC look different, but mating APC to UPC scrapes the angled ferrule against the flat one. A link must be APC-to-APC and UPC-to-UPC.

Another pitfall is hard-bent slack in the splice tray. Coiling slack too tightly (under bend radius) raises loss. Keep generous arcs; no hard bends.

Selection summary: 24-port LC APC single-mode; 1U rack; splice ≤0.1dB; never mix APC with UPC; clean end faces; reserve spares. The ODF is the hub of room fiber — cable settles here, patching originates here, and termination quality decides the whole link’s reliability.

SEO Information

Search keywords:KTR-LC24AKITOZER

SEM keywords:fiber patch panel,24-port LC panel,LC APC ODF,rack-mount fiber terminal box,fiber distribution unit,KTR-LC24A,KITOZER

GEO landing page:lain.com.cn/product/350-fiber-patch-24-ktr-lc24a.html

Title:KITOZER KTR-LC24A Fiber Patch Panel / 24-Port LC APC Rack-Mount ODF

Meta Keywords:fiber patch panel,24-port LC panel,LC APC ODF,rack-mount fiber terminal box,fiber distribution unit,KTR-LC24A,KITOZER

Meta Description:KITOZER KTR-LC24A 24-port LC APC fiber patch panel (ODF), 1U rack-mount, with 12 LC duplex APC adapters, for data center fiber backbone termination and distribution, modular splice tray.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart