KITOZER photoelectric ceiling smoke detector

KITOZER KTR-SD3 Photoelectric Ceiling Smoke Detector

Brand: KITOZER Series: KTR-SD3 Category: Environmental Monitoring / Fire Alarm

photoelectricceiling smokefire alarmRS485DCIM

1. Overview

The most expensive gear in a data center is the equipment, and its worst hidden risk is fire. Electrical fires often start with an overheating terminal or a failed power board, smoldering invisibly at first. By the time flames show, the damage is done. A smoke detector alarms during the smoldering stage, giving staff a golden 10+ minutes to act. A photoelectric detector uses light scattering: with no smoke, IR light travels straight and is not received; smoke entering the chamber scatters light onto the receiver, triggering the alarm. It is very sensitive to the gray smoke of smoldering fires, suiting rooms that cannot be flooded with water – data halls, substations, archives.

The KITOZER KTR-SD3 is a photoelectric ceiling smoke detector. Round white housing, ceiling-mounted, one per 60-80 m² at heights up to 12 m. On smoke, the local red LED flashes and the sounder beeps, while a relay dry contact (NO/NC) uploads to the DCIM or fire panel. RS485 Modbus reports alarm and fault states to the central platform. Power is DC 12V/24V; a dust/insect mesh prevents false alarms from bugs and dust. The chamber rinses clean; a test button lets crews verify the loop monthly.

In environmental and fire works, smoke detectors are not standalone alarms – they link with DCIM, access control, video and gas suppression. On alarm, the platform pops up, sounds the siren, sends SMS, opens the nearest camera, and on confirmed fire releases clean-agent suppression (FK-5-112 etc.). Points: main hall, power room, UPS room, battery room and archive; battery rooms need extra reliability due to hydrogen risk. Choose by sensing principle (photoelectric/ionization), output (relay/RS485), power, rated height and certification (CCC).

2. Key Features

Sensing

  • Photoelectric scatter, sensitive to gray smoke.
  • Dust/insect mesh on the chamber.
  • Ceiling mount, height ≤12 m.
  • Local red LED + sounder.

Output & comms

  • Relay NO/NC contact out.
  • RS485 Modbus alarm/float upload.
  • DC 12V/24V power.
  • Configurable address, hand-in-hand bus.

Build & care

  • Round ABS, ceiling base.
  • Washable chamber.
  • Test button, monthly check.
  • Status and fault LEDs.

3. Specifications

Item KTR-SD3 Photoelectric Detector
Principle Photoelectric scatter
Coverage ~60-80 m² each (height ≤12 m)
Output Relay contact + RS485
Comms RS485 Modbus-RTU
Power DC 12V/24V
Indication Red LED + local buzzer
Mounting Ceiling, base + twist-on head
Protection Insect mesh, washable chamber
Certification CCC fire certification
Use Hall / power / UPS / battery room

4. Reference Prices

KTR-SD3 photoelectric detector (relay out): Reference USD 8~17 (ref. CNY 60~120 at ~7.2)

KTR-SD3 photoelectric detector (RS485 Modbus): Reference USD 17~31 (ref. CNY 120~220 at ~7.2)

Reference only; detectors sized by room area. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Data-center hall smoke monitoring.
  • Power/UPS/battery room early warning.
  • Archives, libraries, storerooms.
  • Link to gas suppression.
  • Central DCIM fire monitoring.

6. Installation & Maintenance

Installation

  • One per 60-80 m², away from diffusers and lights.
  • Fix the ceiling base; wire power and signal.
  • Twist the head on; set the RS485 address.
  • Wire NO/NC to the DCIM DI.
  • Power up; press test to verify upload.
  • Commission linkage to fire panel / suppression.

Maintenance

  • Press test monthly.
  • Rinse the chamber mesh yearly.
  • Shorten cleaning cycles in dusty sites.
  • If false alarms recur, check drafts/steam.
  • Prioritize battery-room checks (hydrogen).
  • Find the cause before resetting.

7. FAQ

  • Q: Photoelectric vs ionization?
    A: Use photoelectric in halls/archives – it catches smoldering gray smoke. Ionization is for flaming black smoke but carries a radioactive source; data centers choose photoelectric ceiling type.
  • Q: Too many false alarms?
    A: Often mounted under AC diffusers, near steam or in dusty air. Move away from diffusers and heat sources, clean the mesh, and add a confirmation delay. Confirm real fires on site.
  • Q: How does it link to suppression?
    A: On alarm, sounder + human confirm; only after confirmation release clean agent. First shut off AC and dampers so the gas is not blown away. Link logic is designed by the fire/DCIM vendor.
  • Q: How much area per detector?
    A: About 60-80 m² each, ceiling up to 12 m; in long corridors space them ≤10 m. Beams and diffusers reduce coverage – follow fire codes.

8. Trend & Selection

Data-center fire safety moves toward very-early air sampling (VESDA), multi-sensor combos (smoke+temp+CO) and smart alarms, but the photoelectric ceiling detector remains the普及 baseline. Choose photoelectric scatter; one per 60-80 m²; relay + RS485; away from diffusers/heat; monthly test; link to suppression. It is the first sentry, sounding at the very start of smoldering.

9. Delivery & Service

KITOZER supplies photoelectric detectors with DCIM host, relay modules and RS485 bus, sized by room area and count. Bundled with fire, suppression, access control and video linkage. Delivery includes detector, base and certificate; the warranty covers alarm-link tuning and fire-acceptance support.

10. Additional Notes

A common pitfall is mounting the detector right under an AC supply diffuser. Drafts blow smoke away before it accumulates, killing sensitivity. Mount on the return side and in room centers, away from supply diffusers and lights.

Another pitfall is install-never-test. Years without a test button reveal a broken wire or wrong address only in a real fire. Press test monthly and rinse the chamber yearly – two minutes buys years of peace of mind.

Selection summary: photoelectric scatter; ceiling one per 60-80 m²; relay + RS485; away from diffusers/heat; monthly test; link to suppression. It is one of the cheapest insurances in the room – a ~$15 sensor guarding equipment worth hundreds of thousands.

System-wide, a detector only “detects”; complete fire safety is a loop of detect, alarm, confirm, suppress, vent. High-value halls add VESDA air sampling to alarm at trace smoke; clean-agent suppression extinguishes; venting and dampers control spread. Layers work together, not one detector alone.

On ops, the window is short. On alarm: confirm location, shut AC/dampers, evacuate, release suppression on confirmation, call 119. Drill this flow beforehand and map detector zones to suppression cylinders so staff know which AC to cut and which bottle to open.

SEO Information

Search keywords:KITOZER

SEM keywords:photoelectric smoke detector, ceiling smoke sensor, data center fire alarm, smoke detector relay RS485, early smoke warning, KTR-SD3, KITOZER

GEO landing page:lain.com.cn/product/383-smoke-det3.html

Title:KITOZER KTR-SD3 Photoelectric Ceiling Smoke Detector

Meta Keywords:photoelectric smoke detector, ceiling smoke sensor, data center fire alarm, smoke detector relay RS485, early smoke warning, KTR-SD3, KITOZER

Meta Description:KITOZER KTR-SD3 photoelectric ceiling smoke detector, scatter-type sensitive to smoldering smoke, relay + RS485 output, DC12/24V, for early fire warning in server and battery rooms.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart