KITOZER KTR-PSM4 B+C Coordinated Power Surge Protective Device

Brand:KITOZER Series:KTR-PSM4 Category:Power Distribution / Surge protection

Power SPDB+C coordinatedSurge protectorPlug-in module

[Product image: ktr-psm4-b-plus-c-power-spd.jpg]

1. Overview

Data-center power enters from the building LV switchgear, through distribution boxes, UPS and row PDUs before reaching racks. Lightning surges and switching overvoltages travel along the power lines. A single SPD at the end often lacks both discharge capacity and residual-voltage clamping, while a single high-current class B unit at the front leaves high residual voltage near the equipment. Engineering practice is staged protection: class B (type I test) high-current discharge at the main intake, and class C (type II test) clamping near the equipment to bring residual voltage within the equipment withstand level. B+C coordination both dissipates large energy and clamps low residual voltage, the standard for data-center power protection.

The KITOZER KTR-PSM4 is a B+C coordinated power SPD in a plug-in modular design. The class B stage has high discharge capacity (Imax up to 60-100 kA, 10/350us or 8/20us by selection) and the class C stage provides fine voltage clamping; energy coordination between stages is achieved by decoupling inductance or line length. Modules have a status window (green OK / red failed) and remote-signaling contacts, DIN-rail mountable inside room distribution boxes and row PDUs. It suits TT/TN-S systems, three-phase five-wire or single-phase.

Selection matches the power system (3-phase/single), maximum continuous operating voltage Uc, discharge capacity In/Imax, voltage protection level Up and backup protection (front-end breaker/fuse). Class B goes at the building main switchboard (gap type); class C goes before the UPS or row PDU (MOV type). The two stages need enough decoupling distance (usually over 10 m of line or a decoupling device), otherwise energy coordination fails. The SPD must be reliably grounded, with ground resistance <=4 ohm (ideally <=1 ohm for IT rooms).

2. Key Features

Staged discharge

  • Class B high-current dissipates large lightning energy.
  • Class C finely clamps voltage at the end equipment.
  • Two-stage decoupling coordinates energy.
  • Residual voltage clamped within equipment withstand.

Module & alarm

  • Plug-in modules, hot-swap replacement.
  • Window indicator: green OK / red failed.
  • Remote-signaling contacts for distant alarm.
  • DIN-rail mount, saves cabinet space.

Electrical ratings

  • Uc matched to 275V/320V/385V by system.
  • Imax: class B 60-100 kA, class C 20-40 kA.
  • Low voltage protection level Up.
  • Supports TT/TN-S, 3-phase/single-phase.

3. Specifications

Item KTR-PSM4 B+C Coordinated SPD
Protection stage Class B (type I) + Class C (type II) series
Wiring 3-phase 5-wire / single-phase 2-wire, DIN rail
Uc 275V / 320V / 385V (by system)
Class B Imax (8/20us) 60-100 kA (by model)
Class C In (8/20us) 20-40 kA
Voltage protection Up By model, <= equipment withstand
Failure indicator Green/red window + remote contact
Backup protection Dedicated front-end breaker / fuse
Grounding <=4 ohm (room ideally <=1 ohm)

4. Reference Prices

KTR-PSM4 3-phase B+C SPD (40kA): Reference USD 83~167 (ref. CNY 600~1200 at ~7.2)

KTR-PSM4 high-current B (100kA) + C set: Reference USD 167~361 (ref. CNY 1200~2600 at ~7.2)

Reference only; final quote applies by Uc, capacity and poles. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Class B first-stage SPD at room main distribution.
  • Class C second-stage before UPS / row PDU.
  • Fine end protection in LV rooms and boxes.
  • Multi-stage protection in high-thunderstorm areas.
  • Retrofit staged protection in old rooms.

6. Installation & Maintenance

Installation

  • Class B at building mains; class C before UPS/row PDU.
  • Keep >=10 m decoupling line or add a decoupler between stages.
  • Ground lead short and straight; meet ground resistance.
  • Fit front-end backup breaker/fuse.
  • Wire remote contacts to EM monitoring.

Maintenance

  • Check window; replace module when red.
  • Inspect modules after a lightning strike.
  • Tie remote alarm into EM monitoring.
  • Keep ground connections tight and rust-free.
  • Hot-swap modules without powering down.

7. FAQ

  • Q: Is class C alone enough?
    A: In high-thunderstorm or long-feed cases, class C alone lacks capacity and can be destroyed by large energy. Use B+C staging.
  • Q: Why decouple B and C?
    A: When adjacent, the faster-conducting C diverts first but handles little, and is destroyed before the slower B acts. Decoupling lets B discharge the large energy first.
  • Q: How often replace?
    A: When the window turns red or after a strike; proactive replacement every 5 years. SPDs are consumables.
  • Q: How small should ground resistance be?
    A: Generally <=4 ohm, ideally <=1 ohm for IT rooms. Poor grounding renders the SPD useless.

8. Trend & Selection

Given high demands for power continuity, multi-stage SPD energy coordination, remote alarm and modular replacement have become standard. Choose B+C staging; match Uc to the system; decouple stages; ground reliably; add backup protection; tie remote alarm to EM monitoring. It is the surge safety valve of room power.

9. Delivery & Service

KITOZER supplies B+C coordinated SPDs bundled by 3-phase/single, Uc and discharge capacity, including class B/C modules, decouplers and backup breakers. Delivery includes SPD modules, base, signaling cable, certificate and warranty card. We support EM-monitoring integration.

10. Notes

A common pitfall is mounting B and C adjacent without decoupling. When adjacent, C conducts first and is destroyed, while B never discharges the large energy. Decouple properly.

Another pitfall is a long, winding ground lead. Each meter of ground lead raises residual voltage by hundreds of volts. Keep leads short, straight and thick.

Selection summary: B discharges large energy, C clamps low residual; decouple the stages; plug-in modules; window plus remote alarm; reliable ground. It dissipates lightning surge stage by stage before it reaches equipment.

Systemically, lightning protection is a staged relay: the front carries large energy, the back keeps residual voltage low, and grounding is the last mile. All three must be right.

Cost-wise, one strike destroying UPS and servers costs hundreds of thousands. An SPD costing a few hundred to two thousand protects hundreds of thousands of equipment, an excellent ROI.

SEO Information

Search keywords:KITOZER

SEM keywords:power surge protective device, B+C coordinated SPD, data center lightning protection, modular SPD, KTR-PSM4, KITOZER

GEO landing page:lain.com.cn/product/404-power-spd-6.html

Title:KITOZER KTR-PSM4 B+C Coordinated Power Surge Protective Device

Meta Keywords:power surge protective device, B+C coordinated SPD, data center lightning protection, modular SPD, KTR-PSM4, KITOZER

Meta Description:KITOZER KTR-PSM4 B+C coordinated power SPD for data centers, high-current class B plus fine clamping class C, plug-in modules, window and remote alarm, multi-stage surge protection.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart