KITOZER
KITOZER

KITOZER 12V 7Ah deep cycle battery

KITOZER KTR-BAT7D 12V7Ah Deep-Cycle VRLA Battery

Brand:KITOZER Series:KTR-BAT7D Category:Power Distribution / UPS backup battery

12V7Ah batteryDeep cycleVRLA AGMUPS backup

[Product image: ktr-bat7d-12v7ah-deep-cycle-battery.jpg]

1. Overview

UPS, fire emergency, access control and surveillance equipment rely on battery banks to ride through mains outages. Batteries are the energy core of backup power: their capacity, cycle life and consistency directly decide backup runtime. 12V7Ah is a classic small valve-regulated lead-acid (VRLA) size, widely used in small UPS, fire panels, emergency lighting, security access and elevator emergency leveling. A deep-cycle design means the battery tolerates deep discharge followed by recharge, giving far longer cycle life than starter batteries, suiting backup scenarios with frequent discharge.

The KITOZER KTR-BAT7D is a 12V7Ah deep-cycle VRLA battery with AGM absorbed-glass-mat separator, valve-regulated sealed and maintenance-free, no leakage, and mountable in any orientation except long-term inversion. The ABS flame-retardant case has M5 tin-plated copper terminals, low self-discharge (~3%/month) and -15 to +50 C operating range. The deep-cycle grid formulation delivers hundreds of cycles at 50% depth of discharge, suiting frequently cycled UPS and backup systems.

Selection focuses on rated voltage (12V), capacity (7Ah, 20-hour rate), terminal type, cycle life and float design life. Small UPS strings connect cells to 24V/36V/48V; when paralleling for more capacity, use the same brand, model and age to avoid inconsistency and circulating current. Pay attention to rack load rating, ventilation, spacing and leak trays; never mix old and new batteries in one string.

2. Key Features

Deep-cycle performance

  • Deep-cycle grid formulation tolerates deep discharge.
  • Hundreds of cycles at 50% DoD.
  • Suits frequently cycled backup duty.
  • Longer cycle life than starter batteries.

Sealed & maintenance-free

  • AGM valve-regulated seal, no leakage.
  • No water topping, maintenance-free in service.
  • ABS flame-retardant case.
  • M5 tin-plated copper terminals for reliable contact.

Electrical characteristics

  • Rated 12V / 7Ah (20-hour rate).
  • Self-discharge ~3%/month.
  • Operating temperature -15 to +50 C.
  • Float design life 3-5 years (25 C).

3. Specifications

Item KTR-BAT7D 12V7Ah Deep-Cycle Battery
Rated voltage 12 V
Rated capacity 7 Ah (20-hr rate, 1.75V/cell)
Type VRLA sealed lead-acid, AGM separator
Grid / cycles Deep-cycle, hundreds of cycles at 50% DoD
Terminals M5 tin-plated copper
Self-discharge ~3%/month (25 C)
Operating temp. -15 to +50 C
Float life 3-5 years (25 C, 2.27V/cell)
Case ABS flame-retardant

4. Reference Prices

KTR-BAT7D 12V7Ah deep-cycle battery: Reference USD 11~21 (ref. CNY 80~150 at ~7.2)

KTR-BAT7D same-batch as a string (incl. cables): Reference USD 13~22 (ref. CNY 90~160 at ~7.2)

Reference only; final quote applies. 1-year warranty. String pricing available. Freight by weight. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Small UPS backup battery strings.
  • Fire panel and emergency lighting backup.
  • Security access and surveillance standby power.
  • Elevator emergency leveling, alarm panels.
  • Frequently cycled backup and small energy storage.

6. Installation & Maintenance

Installation

  • Series/parallel in same brand/model/age strings.
  • Rack load rated; secure against tipping.
  • Coat terminals with petroleum jelly; torque tight.
  • Use matched copper links, crimp firmly.
  • Initial charge after install; check cell voltage equality.

Maintenance

  • Periodically measure cell voltage and internal resistance.
  • Float voltage per maker (~2.27V/cell).
  • Ambient 20-25 C; heat halves life.
  • Run a capacity discharge test yearly.
  • Replace failed batteries as a whole string.

7. FAQ

  • Q: Can deep-cycle and starter batteries mix?
    A: No. Grid design and duty differ; mixing causes inconsistency and early failure. One string must use one model.
  • Q: How long does a battery last?
    A: 3-5 years float at 25 C. Every 10 C rise roughly halves life. Hot rooms need temperature control.
  • Q: Why replace the whole string?
    A: Lead-acid strings have a weak-link effect; one lagging cell drags down the whole string. Mixing ages causes large circulating current.
  • Q: Is high self-discharge normal?
    A: ~3%/month is normal; if voltage drops markedly within weeks, an internal short is likely and it should be replaced.

8. Trend & Selection

Backup power trends toward high reliability, long life and smart monitoring; AGM deep-cycle batteries remain the mainstream for small/medium UPS, paired with internal-resistance monitoring and BMS. Choose by voltage/capacity; build matched strings; control temperature; test discharge periodically; replace as a whole string. It is the energy warehouse of UPS backup.

9. Delivery & Service

KITOZER supplies the 12V7Ah deep-cycle battery, optionally bundled with racks, cables, leak trays and internal-resistance testers. Delivery includes battery, connecting links, certificate and warranty card. We support whole-string supply and on-site commissioning/initial charge.

10. Notes

A common pitfall is mixing old and new batteries in one string. Old cells have high resistance and drag down new ones; string capacity is set by the worst cell. Replace by whole batch.

Another pitfall is ignoring high temperature. Lead-acid life is highly temperature-sensitive; a hot battery room sharply shortens life. Control the temperature.

Selection summary: 12V7Ah; AGM VRLA deep-cycle; M5 terminals; matched strings; 20-25 C ambient; periodic discharge test. It sustains backup runtime on mains outage.

Systemically, the battery string is the last mile of UPS backup. No matter how good the UPS, degraded batteries zero out runtime. Battery health equals credible backup.

Cost-wise, one battery costs around a hundred CNY yet determines whether a whole rack survives a mains outage. Test internal resistance and replace strings before a blackout exposes a dead battery.

SEO Information

Search keywords:KITOZER

SEM keywords:12V7Ah deep cycle battery, VRLA AGM battery, UPS backup battery, sealed lead-acid, KTR-BAT7D, KITOZER

GEO landing page:lain.com.cn/product/405-battery-12v7d.html

Title:KITOZER KTR-BAT7D 12V7Ah Deep-Cycle VRLA Battery

Meta Keywords:12V7Ah deep cycle battery, VRLA AGM battery, UPS backup battery, sealed lead-acid, KTR-BAT7D, KITOZER

Meta Description:KITOZER KTR-BAT7D 12V7Ah deep-cycle VRLA AGM battery, M5 terminals, low self-discharge, 3-5 year float life, for small UPS and fire/access backup.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com