Table of Contents
ToggleKITOZER KTR-TH6 Duct Temperature & Humidity Sensor
Brand:KITOZER Series:KTR-TH6 Category:Environmental Monitoring / Temp-humidity
Duct mountTemp+RHRS485EM monitoring
1. Overview
Temperature and humidity are the two most basic yet important parameters in room EM monitoring. High temperature triggers server throttling alarms; high humidity causes condensation shorts; low humidity causes ESD that chips components. A wall sensor measures return-air room air, but the supply-air duct’s actual air temperature and humidity are the direct feedback to the AC. A duct sensor probes into the supply/return duct, measures air T and RH in real time, and sends RS485 or 4-20mA to the EM platform or AC controller, closing the loop: if supply air is too warm, the AC ramps cooling; if too dry, the humidifier adds moisture.
The KTR-TH6 is a duct temp/RH sensor with probe lengths of 150-300 mm, inserted into the duct and fixed by a flange plate. The sensing element is a capacitive RH sensor plus NTC temperature sensor. Temperature range -40 to +80 C, accuracy +/-0.5 C; RH range 0-100%, accuracy +/-3%. Output is RS485 Modbus-RTU or two-channel 4-20 mA loop, powered by DC12-24V. ABS flame-retardant housing, IP54 (probe IP65). Used on precision AC supply/return ducts, fresh air and exhaust ducts; it is the front-end pickup for AC group control and EM monitoring.
Selection considers range and accuracy, output (RS485/4-20mA/0-10V), probe length (by duct wall thickness), mounting (duct/wall/channel) and supply voltage. Rooms usually use RS485 to the EM platform; +/-0.5 C and +/-3% RH is enough. Industrial harsh environments choose higher accuracy and protection. The probe must reach the duct center, not touch the wall – wall contact reads metal temperature, not air.
2. Key Features
Measurement
- Temp -40 to +80 C, +/-0.5 C.
- RH 0-100%, +/-3% RH.
- Capacitive RH sensor, fast response.
- NTC temp, long-term stable.
Output & power
- RS485 Modbus-RTU.
- Optional dual 4-20 mA loop.
- DC12-24V wide supply.
- Baud 9600/19200 selectable.
Structure & mount
- Probe 150/200/300 mm options.
- Flange plate fixes to duct.
- ABS housing, IP54.
- Probe head IP65 moisture-proof.
3. Specifications
| Item | KTR-TH6 Duct Sensor |
|---|---|
| Temp range | -40 to +80 C |
| Temp accuracy | +/-0.5 C |
| RH range | 0-100% RH |
| RH accuracy | +/-3% RH |
| Output | RS485 Modbus-RTU / 4-20mA |
| Power | DC12-24V |
| Probe length | 150 / 200 / 300 mm |
| Mounting | Duct insertion, flange |
| Protection | Housing IP54 / probe IP65 |
| Response | <=15 s (at 2 m/s airflow) |
4. Reference Prices
KTR-TH6 duct sensor (RS485): Reference USD 25~44 (ref. CNY 180~320 at ~7.2)
KTR-TH6 duct sensor (4-20mA): Reference USD 31~53 (ref. CNY 220~380 at ~7.2)
Reference only; final quote applies. 1-year warranty. Probe length by duct wall. RS485 and 4-20mA priced differently. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Precision AC supply/return duct measurement.
- Fresh air and exhaust duct monitoring.
- Room EM monitoring T/RH pickup.
- AC group control closed loop.
- Lab and cleanroom duct air checks.
6. Installation & Maintenance
Installation
- Drill a 16-22 mm hole in the duct.
- Insert probe to duct center; fix flange.
- Wire DC12-24V and RS485 A/B.
- Add sensor on EM platform; set Modbus address.
- Calibrate against a reference T/RH meter.
Maintenance
- Brush probe dust with a soft brush.
- Calibrate RH yearly with saturated salt solution.
- Seal the duct hole to prevent air leakage.
- Add 120-ohm terminator at the RS485 bus end.
- Wait for probe to dry after condensation before reading.
7. FAQ
- Q: Duct vs wall sensor?
A: Duct probes into the duct for AC closed-loop control; wall mounts on the wall for room air monitoring. Different positions and uses. - Q: How many sensors per RS485 bus?
A: Theoretically 32 per bus (128/256 with repeaters), each with a unique Modbus address. Rooms usually need only a dozen. - Q: RH reading off?
A: Check probe dirt or condensation first; then calibrate with saturated salt (e.g. NaCl = 75% RH); replace the RH element if offset remains. - Q: How deep should the probe go?
A: Reach the duct center; not the wall. 150-200 mm usually; use 300 mm for large ducts.
8. Trend & Selection
Room EM monitoring trends to IoT, high accuracy and multi-parameter integration; T/RH sensors are the most basic pickups. Choose duct-mounted at duct center; RS485 to EM; +/-0.5 C / +/-3% RH; probe length by duct; calibrate periodically. It is the sense organ of AC closed-loop control.
9. Delivery & Service
KITOZER supplies KTR-TH6 sensors, optionally bundled with RS485 converters, EM hosts, duct flanges and shielded signal cable. Delivery includes sensor, flange, manual, certificate and warranty card. We can produce a sensor-point list from your AC duct layout.
10. Notes
A common pitfall is mounting the probe against the duct wall. Wall contact reads sheet-metal temperature, skewed hot in summer and cold in winter – not real air temperature. Extend the probe to the duct center.
Another pitfall is omitting the RS485 terminator. Without a 120-ohm resistor at both bus ends, signal reflection causes unstable communication. Always add it on long buses.
Selection summary: duct-mounted; RS485/4-20mA; +/-0.5 C / +/-3% RH; probe at duct center; calibrate periodically; 120-ohm terminator. It is the sense organ of AC closed loop.
Systemically, AC group control relies on sensor feedback to close the loop. Bad supply-air readings make the AC regulate poorly, leaving room temperature to swing and servers to run unstable.
Reliability-wise, the sensor is cheap but critical. One failed sensor and the EM platform shows “normal” while the room overheats; by the time servers alarm, it is too late. Periodic calibration and redundant points matter.
SEO Information
Search keywords:KITOZER
SEM keywords:duct temp humidity sensor, duct humidity transmitter, data center temp sensor, RS485 T/RH, KTR-TH6, KITOZER
GEO landing page:lain.com.cn/product/415-temp-hum-6.html
Title:KITOZER KTR-TH6 Duct Temperature & Humidity Sensor
Meta Keywords:duct temp humidity sensor, duct humidity transmitter, data center temp sensor, RS485 sensor, KTR-TH6, KITOZER
Meta Description:KITOZER KTR-TH6 duct temperature humidity sensor, probes into duct, RS485/4-20mA output, accuracy +/-0.5C / +/-3%RH, for room AC duct and EM monitoring.
Anchor: KITOZER by Guangzhou Laian · KITOZER products
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com