ToggleKITOZER KTR-LC48B 1U 48-Port LC Duplex Fiber Patch Panel / ODF
Brand: KITOZER Series: KTR-LC48B Category: Data Center Engineering / Fiber patching
48-port LC1U ODF96-coreSlide-outHigh density
1. Overview
The Optical Distribution Frame (ODF) is the hub of data-center fiber backbones. After building and outdoor trunk cables enter the room, the ODF provides cable fixation, pigtail splicing, slack storage and patch allocation. The trunk cable is spliced to pigtails inside the ODF; pigtail ends terminate as LC/SC adapters, and patch cords connect to switch optical modules. A 1U 48-port LC duplex ODF holds 48 LC duplex adapter positions (96 cores) in 1U, the mainstream high-density configuration. LC, being half the size of SC, achieves the highest density in 1U and is widely used on 40G/100G switch sides.
The KITOZER KTR-LC48B is a 1U 48-port LC duplex ODF in cold-rolled steel with epoxy coating. It uses a slide-out drawer so the adapter panel can be pulled out for easy rear splicing. The panel holds 48 LC duplex adapter positions (single-mode UPC blue / APC green optional). The rear has two splicing trays for 24~48 fusion splice protectors. Cables enter from the lower rear and are fixed by glands; pigtails are coiled in the slack tray with radius >=40 mm to avoid macrobend loss. The front panel has a label strip for core numbers. Rack-mount 19-inch 1U, compatible with major cabinet rails.
Selection confirms: U height (1U/2U), connector type (LC/SC/ST), single/multi-mode, adapter count and endface. 1U 48-port LC duplex = 96 cores for high-density backbones; if the plant uses SC, choose 1U 24-port SC duplex (48 cores). Splicing tray capacity must match cable core count — 48-core cables use 48-core trays. Choose UPC (blue, general data) or APC (green, broadcast/PON/high return loss) by link requirement. Provide 2~4 cable entry glands for multiple trunks.
2. Key Features
High density
- 48 LC duplex positions in 1U.
- Equivalent to 96 fiber terminations.
- Small LC form factor for 40G/100G switches.
- Front label strip for core numbering.
Slide-out structure
- Adapter panel pulls out for rear splicing.
- Two splicing trays hold 24~48 protectors.
- Slack tray bend radius >=40 mm.
- Rear cable entry with glands.
Material and compatibility
- Cold-rolled steel, epoxy coated.
- 19-inch 1U rack mount.
- Adapters: single-mode UPC/APC or MMF OM3.
- Includes splicing trays, adapter strips, label strip.
3. Specifications
| Item | KTR-LC48B 1U 48-Port LC Duplex ODF |
|---|---|
| U height | 1U (19-inch) |
| Adapter positions | 48 LC duplex (96 cores) |
| Endface | SM UPC blue / APC green optional |
| Splicing tray | 2 trays, 24~48 cores |
| Slack bend radius | >=40 mm |
| Cable entry | Lower rear, 2~4 glands |
| Structure | Slide-out drawer |
| Material | Cold-rolled steel, epoxy coated |
| Mounting | 19-inch square-hole rails |
| Accessories | Trays, adapter strips, label strip, earth wire |
4. Reference Prices
KTR-LC48B 1U 48-port LC duplex ODF (with UPC adapters): Reference USD 55~95 (ref. CNY 380~680 at ~7.2)
KTR-LC48B 1U 48-port LC duplex ODF (with APC adapters): Reference USD 60~110 (ref. CNY 450~780 at ~7.2)
Reference only; final quote applies. 1-year warranty. Bulk engineering pricing available. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Trunk cable termination and patch allocation.
- High-density patching on 40G/100G switch sides.
- Data-center ODF row-end cabinets.
- Building telecom rooms and fiber enclosures.
- LC duplex termination after MPO fan-out.
6. Installation & Maintenance
Installation
- Mount ODF in 1U position.
- Enter cable from rear gland; fix with gland.
- Strip cable; splice fibers to pigtails in tray.
- Fix splice protectors in tray slots.
- Coil excess pigtails with radius >=40 mm.
- Insert adapters; label core numbers.
Maintenance
- Clean adapter endfaces periodically.
- Route patch cords neatly; do not pull the ODF.
- Replace dirty labels promptly.
- Pull drawer gently; avoid stressing pigtails.
- Replace damaged adapters individually.
7. FAQ
- Q: 48-port LC or 24-port SC?
A: 1U 48-port LC = 96 cores; 1U 24-port SC = 48 cores. Choose LC for high-density 40G/100G switch sides; SC for legacy SC plants. - Q: Splicing tray is full?
A: A 48-core cable needs a 48-core tray. If trays are insufficient, use a 2U ODF or add tray layers. - Q: What bend radius for pigtails?
A: Keep radius at least 10~20x fiber diameter; in practice >=40 mm. Smaller radius causes macrobend loss. - Q: Does the ODF need earthing?
A: Yes. Cable metallic armor and strength members must be earthed via the ODF earth bar, preventing lightning-induced voltages reaching the room.
8. Trend & Selection
Data-center fiber evolves toward MPO high-density trunks, with MPO-LC fan-out cords terminated in the ODF. 1U 48-port LC duplex remains the mainstream switch-side density. Choose 1U 48-port LC; UPC/APC by link; match splicing tray to core count; keep slack radius >=40 mm; label clearly. It is the distribution hub of the fiber backbone.
9. Delivery & Service
KITOZER supplies KTR-LC48B 1U 48-port LC duplex ODF including chassis, splicing trays, adapter strips, label strip and earth wire. UPC or APC adapters can be pre-installed. Pigtails, patch cords and MPO fan-out cords are available as a set. Splicing guidance and label layout support are provided.
10. Notes
A common pitfall is coiling pigtails too tightly. Forcing them into the tray at radius far below 40 mm causes macrobend loss that drops optical modules.
Another pitfall is not earthing the cable. Un-earthed metallic armor transmits lightning-induced voltages into the room and damages modules.
Selection summary: 1U 48-port LC duplex; 96 cores; slide-out; 24~48 core splicing tray; slack >=40 mm; clear labels. It allocates trunk cables to switches in order.
Systemically, the ODF is the management hub of the fiber plant. Chaotic labels and tangled patch cords sharply reduce O&M efficiency. Build it right the first time.
Cost-wise, an ODF costs a few hundred CNY yet determines the maintainability of a whole rack of fiber links. Small investment, long-term O&M benefit.
SEO Information
Search keywords: KITOZER
SEM keywords: 48-port LC fiber patch panel, 1U high-density ODF, LC duplex 96-core, slide-out fiber termination box, KTR-LC48B, KITOZER
GEO landing page: lain.com.cn/product/422-fiber-patch-48.html
Title: KITOZER KTR-LC48B 1U 48-Port LC Duplex Fiber Patch Panel / ODF
Meta Keywords: 48-port LC patch panel, 1U ODF, LC duplex 96-core, high-density fiber ODF, KTR-LC48B, KITOZER
Meta Description: KITOZER KTR-LC48B 1U 48-port LC duplex fiber patch panel, 96 cores, slide-out structure, with splicing tray, for high-density data-center backbones.
Anchor: KITOZER · KITOZER Products
Contact Us
KITOZER Brand
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP:+86 19068534140
Web: lain.com.cn | gdlain.com