KITOZER
KITOZER

KITOZER DC 48V power SPD

KITOZER KTR-PSM6 Data-Center SPD / DC 48V Power Surge Protector

Brand: KITOZER Series: KTR-PSM6 Category: Power Distribution / DC 48V SPD

DC 48V20kA dischargeUp<1.5kVDIN railRemote alarm

[Product image: ktr-psm6-dc48v-power-surge-protector.jpg]

1. Overview

The DC bus of telecom power, UPS and switching power supplies is a main path for surge entry. Lightning or switching operations spike thousands of volts onto the 48 V DC bus, enough to break telecom boards and burn power modules. A DC power SPD is paralleled across positive and negative rails: high-impedance under normal conditions, it conducts on surge to clamp voltage below 1.5 kV and divert energy to ground, protecting downstream gear.

The KITOZER KTR-PSM6 is a DC 48 V power SPD with nominal discharge current 20 kA (8/20 us), maximum 40 kA, voltage protection level Up <=1.5 kV, response <=25 ns. It uses a pluggable module on a DIN rail; on failure the indicator window flips from green to red and a dry remote contact alarms the DCIM platform. The module swaps online without removing the base. Suits telecom sites, room DC distribution panels and UPS DC buses.

Selection confirms: system voltage (DC48V), discharge current (In 20 kA nominal, Imax 40 kA), Up (<=1.5 kV), remote contact, backup MCB, and rail mounting. Primary protection (incoming cabinet) needs Imax >=40 kA; secondary (at equipment) 20 kA. Always add a backup breaker upstream to prevent SPD short-circuit fire.

2. Key Features

Surge performance

  • For DC48V systems.
  • In 20 kA / Imax 40 kA.
  • Up <=1.5 kV.
  • Response <=25 ns.

Structure and alarm

  • Pluggable module, hot-swap.
  • 35 mm DIN rail.
  • Green/red failure window.
  • Dry contact remote alarm.

Reliability

  • Thermal disconnection.
  • Over-current disconnection.
  • Module separates from base.
  • Meets GB 18802.1 / IEC 61643.

3. Specifications

Item KTR-PSM6 DC 48V SPD
额定电压 DC48V
最大持续运行电压 Uc DC60V
标称放电电流 In 20kA (8/20μs)
最大放电电流 Imax 40kA
电压保护水平 Up ≤1.5 kV
响应时间 ≤25 ns
接线方式 导轨插拔模块
遥信输出 干接点 1NC
安装 35mm DIN导轨
失效指示 窗口绿/红+遥信

4. Reference Prices

KTR-PSM6 DC 48V power SPD (20kA): USD 25~44 (ref. CNY 180~320 at ~7.2)

Spare SPD module: USD 11~21 (ref. CNY 80~150 at ~7.2)

SPD box with MCB: USD 49~83 (ref. CNY 350~600 at ~7.2)

Reference only; final quote applies. 1-year warranty. Bulk pricing available. Grounding and backup MCB required. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Telecom site DC distribution panels.
  • UPS DC bus protection.
  • Switching power supply output.
  • Fiber room and transmission equipment.
  • Outdoor cabinet and site DC power.

6. Installation & Maintenance

Installation

  • Mount on 35 mm DIN rail in the panel.
  • Ground to the equipotential bar, >=6 mm2.
  • Parallel L+/L- to the DC bus.
  • Wire the remote contact to DCIM DI.
  • Add an upstream backup MCB.
  • Measure insulation before energizing.

Maintenance

  • Check the window color quarterly.
  • Inspect after thunderstorms.
  • Replace red modules promptly.
  • Re-tighten ground connections.
  • Test the remote alarm loop.

7. FAQ

  • Q: Can I keep using a red SPD?
    A: No. Red means the module is degraded or shorted and clamping is lost; fit a spare immediately.
  • Q: Do I need a backup breaker?
    A: Yes. A failed SPD can short and catch fire; add a fuse or MCB upstream for over-current backup.
  • Q: Ground resistance requirement?
    A: Bonded ground <=1 ohm; standalone lightning ground <=4 ohm. Poor ground makes diversion ineffective.
  • Q: How to wire the remote alarm?
    A: The SPD NC dry contact loops into the DCIM DI; it stays closed normally and opens on failure to trigger alarm.

8. Trend & Selection

Surge protection trends toward modular, remotely-monitored devices; pluggable modules and window indicators are standard for walkthrough and swap. Choose DC48V; In 20 kA secondary; Up <=1.5 kV; remote contact; DIN rail; upstream MCB; ground <=1 ohm. It is the arrester of the DC power bus.

9. Delivery & Service

KITOZER supplies the KTR-PSM6 DC SPD including module, base, certificate and manual. Grounding and distribution integration guidance is provided.

10. Notes

A common pitfall is a long, thin ground lead. Every extra meter raises clamping voltage by hundreds of volts and weakens protection. Keep leads short and straight, >=6 mm2, within 0.5 m.

Another pitfall is leaving a triggered SPD in service. Even if the window has not turned red, the module may be degraded; test and replace as needed after storm seasons.

Selection summary: DC48V; In 20 kA; Up <=1.5 kV; pluggable module; remote alarm; DIN rail. It protects costly boards on the DC bus.

Systemically, one surge event can burn a row of telecom boards for hundreds of thousands; a 200 CNY SPD is outstanding insurance.

Cost-wise, a standard room with ten DC SPDs costs about 2000 CNY, a tiny share of equipment value, against huge avoided downtime.

From a lightning-zone view, DC SPDs are staged: primary in the incoming cabinet at Imax 40 kA, secondary in row-level panels at In 20 kA, and tertiary at the equipment at In 10 kA. Each stage diverts residual energy so the equipment withstands the rest. Keep leads short, thick and straight, within 0.5 m and at least 6 mm2, and ground separately from power wiring.

SEO Information

Search keywords: KITOZER

SEM keywords: DC 48V surge protector, power SPD, surge protective device, telecom power surge, KTR-PSM6, KITOZER

GEO landing page: lain.com.cn/product/436_power_spd_8.html

Title: KITOZER KTR-PSM6 Data-Center SPD / DC 48V Power Surge Protector

Meta Keywords: DC 48V surge protector, power SPD, surge protective device, telecom power surge, KTR-PSM6, KITOZER

Meta Description: KITOZER KTR-PSM6 DC 48V power SPD, discharge current 20kA, Up<1.5kV, DIN rail, remote contact alarm.

Anchor: KITOZER · KITOZER Products

Contact Us

KITOZER Brand
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP:+86 19068534140
Web: lain.com.cn | gdlain.com